Laserfiche WebLink
<br />I--'..'~_,,,,,,,,,,,,' _. <br /> <br />INSTALLATION AND MAINTENANCE INSTRUCTIONS <br /> <br />.~ SYSTEM <br />'--~ SENSOR- <br /> <br />2100D and 2100TD Photoelectronic <br />Smoke Detectors <br /> <br />A Division ol Piuway <br />3825 Ohio Avenue, 51. Charles, Illinois 60174 <br />, \.800.SENSOR2, FAX: 630.377.6495 <br />, <br /> <br />Specifications <br />Diameter: <br />Height (including mounting bracket): <br />Weight: <br />Operating Temperature Range: <br /> <br />Operating Humidity Range: <br />Latching Alarm: <br />Heat Sensor (Model 2100TD only): <br />Electrical Ratings <br />System Voltage - <br /> <br />Maximum Ripple Volt~ge: <br />Start-up Capacitance: <br />Standby Current: <br />Alarm Rating'; <br /> <br />Reset Voltage: <br />Reset Time: <br />Start-up Time: <br /> <br />5.S inches (140 mm) <br />1.7 inches (43 mm) <br />5.3 oz. (Iso g) <br />ModeI2IOOD: 32Q to 120"F (0" to SO"C) <br />Mode12100TD: 32Q to 100" F (OQ to 39" C) <br />10% to i:J3 % Relative Humidity. Noncondensing <br />Resel by momentary power interruption <br />13S"F Fixed Tt!mperature Electronic Thermistor <br /> <br />Nominal: 12 or 24 VDC <br />Minimum: 8,5 VDC <br />Maximum: 3S VDC <br />30 % of nom. Voltage (peak to peak) <br />0.02 fJ.F maximum <br />SO fJ.A maximum <br />4.2 VDC minimum at 10 mA. <br />6.6 VDC maximum at 100 mA. <br />(Alarm current must be limited to 100 mA maximum by the control panel. If <br />used. the RA400Z Remote Annuncialor operates within the specified detector <br />alarm currents.) <br />2.5 VDC minimum <br />0.3 seconds maximum <br />30 seconds maximum (af(er 60 second reset) <br /> <br />Befor. 1nst8l11ng <br />Please thoroughly read System Sensor manual 156-407. <br />Guide for Proper Use of System Smoke Detectors, which pro- <br />vides detailed information on detector spacing. placement. <br />zoning. wiring, and special applications. Copies of t~lis <br />manual are available at 00 charge from System Sensor. <br /> <br />NanCE: This: manual should be lefl with the owner/user <br />of this equipment. <br /> <br />IMPORTAN'r. This detector must be tested and mainlained <br />regularly following NFPA 12 requirements. The detector <br />should be cleaned at least once a year. <br /> <br />General Deswlptlon <br />Model 2100D is a 2-wlre pholoelectronic smoke deteclor <br />that uses a state-of-the-art oplical sensing chamber. Tnis <br />detector is designed to provide open area prolection and to <br />be used With compatible UL-listed panels only. Model <br />2100TD features a restorable. built-in. fixed-temperalure <br />(1350 F) thermal detector. <br /> <br />02.00.54.00 <br /> <br />Installalion of these detectors is simplified by the use of a <br />mounting bracket and a plug-in screw terminal block th~t <br />can be prewired to the syslem, allowing the detector to be <br />easily instaUed or removed for cleaning. The delector's sen- <br />sitivity can be tested in place using th~ M0D400R Test <br />Module. An LED on the detector provides a local visual in- <br />dication of lhe detector's slalus. If power is applied to lhe <br />detector. and it is funclioning normally in standby, the sta- <br />tus LED blinks every len seConds. The LED also lalches on <br />in alarm. <br /> <br />Models 2100D and 2100TD feature a visual indication thai <br />maintenance is required - if the seming chamber drifts out <br />oC its sensitivity limits, the LED cease~ to blink. <br /> <br />The delectors also include an OUlPUl that allows an <br />optional Model RA400Z Remore Annunciator 10 be <br />connected. <br /> <br />156-710-09 <br />