Laserfiche WebLink
<br />72-28 <br /> <br />:-;.-\TJO~AL FIRE AL-\RM CODE <br /> <br />1-7.2.3 Central Station Fire Alarm Systems. It shall be <br />conspicuously indicaled by lhe prime contractor (st't' Chaptn <br />-I) that the fire alarm system prO\'iding sen'ice at a prolecled <br />premises complies with all applicable requirements of lhis <br />code by providing a means of verification as specified in <br />either 1-7.2.3.1 or 1-7.2.3.2. <br /> <br />1-7.2.3.1 The installation shall be certificated. <br /> <br />1-7.2.3.1:1 Central station fire alarm systems providing <br />service that complies with all requirements of this code shall <br />be certificated by the organization that has listed the prime <br />contractor, and a document attesting to this certification <br />shaH be located on or near the fire alarm system control unit <br />or, where no control unit exists, on or near a fire alarm sys- <br />tem component. <br /> <br />1-7.2.3.1.2 A cemral repository of issued certification doc- <br />uments, accessible to the authority having jurisdiction, shall <br />be maintained by the organization that has listed the central <br />slation. <br /> <br />1.7.2.3.2 The installalion shall be placarded. <br /> <br />1-7.2.3.2.1 Central station fire alarm systems providing <br />sen-ice that complies with all requirements ofthis code shall <br />be conspicuously marked by lhe prime contractor to indicate <br />compliance. The marking shall be by means of one or more <br />securely affixed pla~ards. <br /> <br />1-7.2.3.2.2 The placard(s) shall be 20 in.2 (130 cm2) or <br />larger, shall be located on or near the fire alarm syslem con- <br />trol unit or, where no comrol unil exists, on or near a fire <br />alarm system component, and shall identify the central sta- <br />lion and, where applicable, the prime contractor by name <br />and telephone number. <br /> <br />1-7.3 Records. A complete unalterable record of the tests <br />I and operations of each syslem shall be kept until the next <br />test and for 1 year lhereafter. The record shall be available <br />for examination and, where required, reported to the <br />aUlhority having jurisdiction. Archiving of records by any <br />means shall be permitted ifhard copies oflhe records can be <br />provided promptly when requested. <br /> <br />Exaption: Whert' off-premises monitoring is provided, records of <br />all signo.ls, tests, and opt'ralions rt'cordt'd at the superoising Slo.tion <br />shall be mainto.int'd for not less than 1 Jt'ar. <br /> <br />Chapter 2* Household Fire Warning Equipment <br /> <br />I 2-1 Introduction. <br /> <br />2-1.1. Scope. This chapter contains minimum require- <br />, ments for the selection, installation. operation, and mainte- <br />nance of fire warning equipment for use within family living <br />units. The requirements of the other chapters shall not apply. <br /> <br />Exception: Whert' specifically indicatt'd. <br /> <br />2-1.2 Purpose. <br /> <br />2-1.2.1 Household fire warning syslems shall be designed <br />and installed to prO\;de sufficient warning of a fire to enable <br />occupants to escape. II is recognized that household fire warn- <br />ing systems might nOI be of material assistance to all occupants, <br />such as persons intimate with the ignition of a fire. <br /> <br />1996 Ealtion <br /> <br />J 2-1.2.2 This chapter is primarily concerned with life safety, <br />not Wilh protection of property. It presumes lhat a family <br />has an exit plan. <br /> <br />J 2-1.3 General. <br /> <br />2-1.3.1 A control and associaled equipment, a multiple or <br />J single station alarm(s), or. any combination thereof shall be <br />permiued to be used as a household fire warning system, <br />provided lhe requirements of2-1.3.7 are met. <br /> <br />2-1.3.2 Detection and alarm systems for use within the <br />protected household are covered by this chapter. <br /> <br />2-1.3.3 Supplementary functions, including the extension <br />of an alarm beyond the household, shall be permitted and <br />shall not interfere with the performance requirements of <br />this chapter. <br /> <br />2-1.3.4 Where the authority having jurisdiction requires a <br />household fire warning system to comply with the require- <br />ments of Chapter 4 or any other chapters of this code, the <br />requirements of Section 2-2 shall still apply. <br /> <br />2-1.3.5 The definitions of Sect on 1-4 shall apply. <br /> <br />2-1.3.6 This chapter does not exclude the use of fire alarm <br />systems complying with other chapters of this code in house- <br />hold applications, provided all of the requiremenu of this <br />chapter are met or exceeded. <br /> <br />2-1.3.7 All devices, combinations of devices, and equip- <br />ment to be installed in conformity with this chapter shall be <br />approved or listed for the purposes for which they are <br />intended. <br /> <br />.. <br /> <br />2-1.3.8 A device or system of devices having materials or <br />forms that differ from those detailed in this chapter shall be <br />permitted to be examined and tested according to the intent <br />of the chapter and, iffound equivalent, shall be permitted to <br />be approved. <br /> <br />2.1.3.9 Equivalency. Nothing in this code is intended to <br />prevent the use of systems, methods, or devices of equivalent <br />or superior quality, strength, fire resistance, effectiveness, <br />durability, and safety over those prescribed by this code, <br />provided technical documentation is submitted to the <br />authority having jurisdiction to demonstrate equi\'alency <br />and the system, method, or device is approved for the <br />intended purpose. <br /> <br />2.2 Basic Requirements. <br /> <br />2-2.1 Required Protection. <br /> <br />2-2.1.1* This code requires the following detectors within <br />the family living unit. <br /> <br />2-2.1.1.1 Smoke detectors shall be installed outside of each <br />separate sleeping area in the immediate vicinity of the bed- <br />rooms and on each additional story of the family living unit, <br />including basements and excluding crawl spaces and unfin- <br />ished attics. In new construction, a smoke detector also shall <br />be installed in each sleeping room. <br /> <br />2-2.1.1.2. For family living units with one or more split <br />levels (i.e., adjacent levels with less than one full story sepa- <br />ration between levels), a smoke detector required by <br />2-2.1.1.1 shall be permitted for an adjacent lower level, <br />including basements. (See Figure A-2-2.1.1.2.) <br />