Laserfiche WebLink
<br />SECTION 16130 <br /> <br />OUTLET AND JUNCTION BOXES <br /> <br />PART - 1 GENERAL <br /> <br />1.01 WORK INCLUDED <br /> <br />A. Outlet Boxes <br /> <br />B. Junction Boxes <br /> <br />1.02 RELATED WORK <br /> <br />A. Section 16010: Electrical General Provisions <br /> <br />B. Section 16050: Basic Materials and Methods <br /> <br />C. Section 16140: Wiring Devices and Plates <br /> <br />PART-2PRODUCTS <br /> <br />2.01 OUTLET AND JUNCTION BOXES <br /> <br />A. Outlet and junction boxes constructed of galvanized steel by Appleton, Raco, or Steel <br />City, 1-1/2" deep minimum. <br /> <br />B. Provide boxes for lighting fixtures with fixture studs in center. <br /> <br />C. Provide outlet boxes for lighting, switches and receptacles in interior areas with <br />exposed conduit manufactured of pressed steel and in exterior areas with exposed <br />conduit use cast metal with threaded hubs, "FS" type. Use galvanized steel for <br />concealed boxes. <br /> <br />D. Provide receptacle boxes with green (CU) grounding screw in accordance with detail in <br />NFPA-99. <br /> <br />E. Provide seperate backboxes for normal and emergency devices (including switches). <br /> <br />July 12, 2000 <br />November 22,2000 <br /> <br />16130 - 1 <br /> <br />99087.00 <br />Revision No.5 <br />