<br />LIGHTING SYSTEM CONTROL REQUIREMENTS: <br /> TOTAL EQUIVALENT <br /> SPACE NO. CONTROLS CONTROL POINTS <br />NO. DESCRIPTION AREA TASKS TYPE 1 NO. TYPE 2 NO. DESIGN CRITERIA <br />29 Reading, T 1120.0 1 lion/off 8 I None 011 8 > 2 <br /> ******** PASSES ******** <br /> <br />PROJECT TITLE <br />BUILDING TYPE <br />BUILDING LOCATION <br />BUILDING AREA(ft2) : <br /> <br />NEUKOM GROVES <br />Service Establishments <br />HILLSBOROUGH COUNTY <br />1120 <br /> <br />HVAC SYSTEM REQUIREMENTS: <br /> <br />Cooling System Measure Minim. Minim. System System Result Result <br /> Type #1 #2 #1 #2 Eff.#l Eff.#2 for #1 for #2 <br />Evap. Cooled EER, IPLV 9.30 8.50 10.50 10.50 PASSES PASSES <br />Heating System Measure Minimum Req. Efficiency Result <br />Ele. Resis. Et 0.92 N/A <br /> <br />******** PASSES ******** <br /> <br />AIR DISTRIBUTION SYSTEM INSULATION REQUIREMENTS: <br /> <br />Zone # Duct Location <br /> <br />Minimum R-Value <br /> <br />Design R-Value <br /> <br />Result <br /> <br />1. Unconditioned Space <br /> <br />4.20 <br /> <br />6.00 <br /> <br />PASSES <br /> <br />******** PASSES ******** <br /> <br />PROJECT TITLE <br />BUILDING TYPE <br />BUILDING LOCATION <br />BUILDING AREA(ft2) : <br /> <br />NEUKOM GROVES <br />Service Establishments <br />HILLSBOROUGH COUNTY <br />1120 <br /> <br />WATER HEATING SYSTEM REQUIREMENTS <br /> <br />System Measure Minimum Maximum Design Design Result <br />Type EF / Et SL EF / Et SL <br />Electric <= 12kW EF 0.8900 0.0000 0.920 0.020 PASSES <br /> <br />******** PASSES ******** <br /> <br />PIPING INSULATION REQUIREMENTS: <br /> <br />Pipe Insulation Thickness (in) <br />