Laserfiche WebLink
<br />Exhaust Fan <br />This fan is equipped with a non-sparking blade that is driven by belts enclosed in a <br />cylinder. This location of the belts provides maximwn protection form the air stream. <br />The motor duct is located outside of the duct area. and air velocity over the face of the <br />booth has a minimwn of 100 LFPM (Linear feet per minute). <br /> <br />ELectric Motor <br />This motor conforms to National Electric Manufacturers Association (NEMA) ratings, <br />Class insulated. (Most government and industry motor standards are based on NElvlA.) <br /> <br />KIT7F927-12"fanandmotor(Ll2hp) 0.250 @static pressure is 1515 cfm <br />The motor in Dayton blower, Model No. 3N553A, is an Underwriters <br />Laboratories Inc. (UL) Recognized Component motor in Dayton UL File <br />E47479, Component - Motors, Guide PRGY2. 'This motor is covered <br />under Motor Reference No. R603467 which is on the motor nameplate. <br /> <br />The electrical insulation system in this motor is a UL Recognized <br />Component under Dayton UL File E61921, Component- Systems, <br />Electrical Insulation; Guide OBJY2. <br /> <br />KlT7F831-24"fanandmotor(2hp) 0.250 @static pressure 1s 8500 cfm <br />The motor in Dayton blower, Model no. 3N553A, is an Underwriters <br />Laboratories Inc. (UL) Recognized Component motor in Dayton UL File <br />E47479, Component- Motors~ Guide PRGY2. This motor is covered <br />WIder Motor Reference No. R606795 which is on the motor nameplate. <br /> <br />The electrical insulation system in this motor is a UL Recognized <br />Component under Dayton UL File E61921, Component -Systems, <br />Electrical Insulation; Guide OBJY2. <br /> <br />KIT7F862-34"fanandmotor(3hp) 0.2S0 @'static_pressure is 15350 cfrn <br />The motor in Dayton blower, Model No. 3N556B, is an Underwriters <br />Laboratories Inc. (UL) recognized Component motor in Dayton UL File <br />E47479, Component - Motors, Guide PRGY2. This motor is covered <br />under Motor Reference No. 0029 which is on the motor nameplate. <br /> <br />The electrical insulation system in this motor is a UL Recognized <br />Component under Dayton UL File E61921, Component - Systems, <br />Electrical Insulation; Guide OBJY2. <br />