<br />ESL 449 Series Smoke Detectors
<br />
<br />Architectural and Engineering Specifications
<br />The ESL 449 Series low-profile, self-diagnostic, four-wire smoke
<br />detectors work on the light scattering principle. A pulsed infrared
<br />light-emitting diode serves as the light source, and a high-speed
<br />photodiode as the sensing element. When the amount of light
<br />reflected onto the photodiode reaches the sensitivity setting, the
<br />smoke sampling rate increases, Three (3) successive smoke
<br />sensings above the sensitivity setting are required to sound an alarm.
<br />This design has superior protection against false alarms caused by
<br />dust, insects, RF and ambient-light.
<br />
<br />A confirmed alarm causes the normally flashing power indicator LED
<br />to light continuously and the alarm relay to operate, A trouble
<br />indication is automatically displayed by flashing the LED every
<br />second, This meets NFPA 72 field sensitivity testing requirements.
<br />An internal 85 dB horn (available in "S" models) emits a steady tone
<br />when the detector alarms and a pulsed tone when power polarity is
<br />reversed.
<br />
<br />Product Data
<br />Sensitivity....,.......,....,.......,.......,...,...........3.1 - 1,O%/ft, (max,)
<br />3,1 + O,50%/ft. (min)
<br />Operating temp. range ,.........., 320F to 1200F (OOC to 50oC)
<br />Operating humidity range ....,................,.....,..,.. 0 to 95% RH
<br />Minimum voltage - C, CT, CRT, CST, CSRT, CSST, CSRH, .
<br />CTE, CL T, CSL T, CSTE .........,.............,..,................ 8,5 V
<br />
<br />_ AT ....,...,..,.,.....,...,........................,.....,............,.......... 5,1 V
<br />Maximum voltage - C, CT, CRT, CST, CSRT, CSST, CSRH,
<br />CTE, CLT, CSLT, CSTE ......................,...,.....,........... 33 V
<br />
<br />_ AT .......,.......,.........,......,.....................,.,.........,........,...27 V
<br />Maximum ripple (peak to peak) ..,....,...............,.......,..... 10%
<br />Typical average standby current ..................,.............. 70llA
<br />- CTE, CSTE ...............,.................,...,.........,...........,.... 25MA
<br />Typical alarm current - C, CT and AT ....,..............,.... 15 mA
<br />
<br />_ CRT .......,.....................,..,.........,......,......,............. 31 mA
<br />
<br />Selection Guide
<br />
<br />The proprietary optical sensing chamber is field replaceable, allowing
<br />quick and easy cleaning and maintenance.
<br />Models with auxiliary relays are approved for releasing service.
<br />This low profile product is equipped with a hinged cover, a concealed
<br />tamper-resistant latch, and insect screens,
<br />Wiring terminates in plug-in, clamp-type screw terminals, Detectors
<br />mount to a standard single-gang electrical box, a four-inch octago-
<br />nal, four-inch square electrical box, or WIREMOLD 5739 fixture box,
<br />
<br />Smoke Detector Spacing
<br />On smooth ceilings (as defined in NFPA 72), spacing of 30 feet (9,1 meters)
<br />may be used as a guide. Other spacing may be used depending on ceiling
<br />height, high air movement, and other conditions or response requirements,
<br />
<br />'.5'~)~ 61.J5=)~
<br />j == LV
<br />
<br />- CST and CSST ,........,.....................................,...., 40 mA
<br />- CSRT, CSRH, CSTE ............,.............................., 51 mA
<br />Typical avg, polarity reverse current
<br />- CST, CSRT, CSST, CSLT, CSTE, AND CSRH ,.... 10 mA
<br />Sounder specifications ,.......................,........., 85 dB at 10 ft.
<br />Heat detector specifications
<br />- fixed temperature ,......,......,.......,............. 1350F (57.20C)
<br />- rp.te of rise .... 150F/min, & >1050F (8.30C/min. & >40.60C)
<br />Low Temperature Output ............... 430F :t50F (6.1 oC :t2.80C)
<br />Auxiliary relay contacts2A @ 28 V DC or 120 V AC (resistive)
<br />Alarm contacts ,..........,..,....... 500 mA @ 36 V DC (resistive)
<br />Field wiring size...................,..,.....................,.. 14 - 24 AWG
<br />Packaging ..................., 10 detectors are packed in a carton
<br />Color...........,..,....,......,..,................,.. white cover/white base
<br />with UV inhibitor to prevent yellowing
<br />Listing ............................ UL 268, ULC FM, CSFM and MEA
<br />
<br />Designator Feature Description ,
<br />H Isolated Fixed Temp. Isolated fixed 1350F (570C) and rate of rise heat detector, independently trips the LED and alarm
<br /> and Rate of Rise Heat output. Smoke detector activates internal sounder (local alarm) and auxiliary relay, but
<br /> Detector does not latch, Approved as both single station smoke alarm and system heat detector. Ideal for
<br /> hotel, motel and dormitory rooms where smoking is allowed,
<br />R Auxiliary Relay Used to activate other devices such as elevator recall, door holders, strobes, etc. Listed for
<br /> releasing service.
<br />S Built-in Sounder 85dB built-in sounder alarms when smoke is detected or when power wiring polarity is reversed.
<br />SS Built-in Sounder with 85dB built-in sounder alarm when smoke is detected or when power wiring polarity is reversed,
<br /> Sensitivity Status Also, chirps every 5 minutes when unit goes outside the approved sensitivity range for more
<br /> Output than one day, Resetting detector will silence chirp for one day, until unit is restored to
<br /> proper sensitivity,
<br />T Integrated Fixed Integrated Fixed 1350F (570C) temperature and rate of rise heat detector offers double
<br /> Temp, and Rate of Either heat detector or smoke detector can trip and latch LED and alarm protection,
<br /> Rise Heat Detector relay outputs.
<br />L Low temperature Separate relay output that energizes when temperature around detector reaches 430F
<br /> output :t 50F (6.1 oC :t 2,8OC)
<br />E Built-in end of line Relay is normally energized and will trip with loss of power, Can also provide notification
<br /> power supervision relay when detector needs maintenance.
<br />
<br />@1999 Sentrol. Certain of the items in the Product Information Bulletin are protected under one or more of the following patents: 5,546,074; 5,708,414;
<br />5,798,701; 5,821,866.
<br />
<br />SENTROL
<br />12345 SW Leveton Dr., Tualatin, OR 97062
<br />Tel.: 503.692.4052 Fax: 503,691.7566
<br />http;//www.sentrol.com
<br />U.S. & Canada: 800.547.2556
<br />Technical Service: 800,648.7424
<br />FaxBack: 1.800.483.2495
<br />
<br />ESL.
<br />
<br />A PRODUCT OF SENTROL
<br />
<br />Sentrol reserves the right
<br />to change specifications
<br />without notice.
<br />
<br />@1999 Sentrol
<br />
<br />E-2447-FLG15K-D996
<br />
|