<br />ESL 449 Series Smoke Detectors
<br />
<br />Architectural and Engineering Specifications
<br />The ESL 449 Series low-profile, self-diagnostic, four-wire smoke
<br />detectors work on the light scattering principle, A pulsed infrared
<br />light-emitting diode serves as the light source, and a high-speed
<br />photodiode as the sensing element. When the amount of light
<br />reflected onto the photodiode reaches the sensitivity setting, the
<br />smoke sampling rate increases. Three (3) successive smoke
<br />sensings above the sensitivity setting are required to sound an alarm.
<br />This design has superior protection against false alarms caused by
<br />dust, insects, RF and ambient-light.
<br />
<br />A confirmed alarm causes the normally flashing power indicator LED
<br />to light continuously and the alarm relay to operate. A trouble
<br />indication is automatically displayed by flashing the LED every
<br />second. This meets NFPA 72 field sensitivity testing requirements,
<br />An internal 85 dB horn (available in "S" models) emits a steady tone
<br />when the detector alarms and a pulsed tone when power polarity is
<br />reversed.
<br />
<br />Product Data
<br />Sensitivity....,...,..............,......,..............,.., 3.1 - 1,O%/f1. (max.)
<br />3,1 + O,50%/ft, (min)
<br />Operating temp, range .......,.... 320F to 1200F (OOC to 50oC)
<br />Operating humidity range .........,...,.........,........, 0 to 95% RH
<br />Minimum voltage - C, CT, CRT, CST, CSRT, CSST, CSRH, .
<br />CTE, CL T, CSL T, CSTE .....,..,..,........,...........,..,..,..., 8,5 V
<br />
<br />_ AT ........,..........,.......,......,.......,......,....,........,.............. 5,1 V
<br />Maximum voltage - C, CT, CRT, CST, CSRT, CSST, CSRH,
<br />CTE, CLT, CSLT, CSTE .......,...............,....,.........,...., 33 V
<br />
<br />_ AT ...........,....,..,...,..,........,.......,......,..,..........,...........,.. 27 V
<br />Maximum ripple (peak to peak) ,.,..........,......................, 10%
<br />Typical average standby current ,....,.....,..,.......,...,...... 70 JlA
<br />
<br />_ CTE, CSTE ............,....,..........,...,......,..,.....,....,.......,.. 25MA
<br />Typical alarm current - C, CT and AT .........,......,..,..., 15 mA
<br />
<br />_ CRT ,.......,.,.,..........,..........,..,......,....,.......,............ 31 mA
<br />
<br />Selection Guide
<br />
<br />The proprietary optical sensing chamber is field replaceable, allowing
<br />quick and easy cleaning and maintenance,
<br />Models with auxiliary relays are approved for releasing service.
<br />This low profile product is equipped with a hinged cover, a concealed
<br />tamper-resistant latch, and insect screens,
<br />Wiring terminates in plug-in, clamp-type screw terminals. Detectors
<br />mount to a standard single-gang electrical box, a four-inch octago-
<br />nal, four-inch square electrical box, or WIREMOLD 5739 fixture box.
<br />
<br />Smoke Detector Spacing
<br />On smooth ceilings (as defined in NFPA 72), spacing of 30 feet (9,1 meters)
<br />may be used as a guide, Other spacing may be used depending on ceiling
<br />height, high air movement, and other conditions or response requirements.
<br />
<br />185';&:;1~ 61,J5""1~
<br />1== LV
<br />
<br />_ CST and CSST..........,.........,......,....,...,................ 40 mA
<br />_ CSRT, CSRH, CSTE .....,...,.......,..........,....,..,....... 51 mA
<br />Typical avg, polarity reverse current
<br />_ CST, CSRT, CSST, CSLT, CSTE, AND CSRH ..,.. 10 mA
<br />Sounder specifications ......,..........,......,...,...... 85 dB at 10 ft.
<br />Heat detector specifications
<br />_ fixed temperature ......,.....,.......,..,............ 1350F (57.20C)
<br />_ r.ate of rise .... 150F/min. & >1050F (8.30C/min. & >40,60C)
<br />Low Temperature Output ,..,.........., 430F ::!:50F (6,10C ::!:2,80C)
<br />Auxiliary relay contacts2A @ 28 V DC or 120 V AC (resistive)
<br />Alarm contacts ..,.....,............. 500 mA @ 36 V DC (resistive)
<br />Field wiring size..,............,...,......,....,..,......,...., 14 - 24 AWG
<br />Packaging ,................... 10 detectors are packed in a carton
<br />Color......,...............,...................,...... white cover/white base
<br />with UV inhibitor to prevent yellowing
<br />Listing ...........,................ UL 268, ULC FM, CSFM and MEA
<br />
<br />Designator \\... DeScription ..... .
<br />H Isolated Fixed Temp. Isolated fixed 1350F (570C) and rate of rise heat detector, independently trips the LED and alann
<br /> and Rate of Rise Heat output, Smoke detector activates intemal sounder (local alann) and auxiliary relay, but
<br /> Detector does not latch, Approved as both single station smoke alann and system heat detector, Ideal for
<br /> hotel, motel and donnitory rooms where smoking is allowed.
<br />R Auxiliary Relay Used to activate other devices such as elevator recall; door holders, strobes, etc. Listed for
<br /> releasing service,
<br />S Built-in Sounder 85dB built-in sounder alarms when smoke is detected or when power wiring polarity is reversed.
<br />SS Built-in Sounder with 85dB built-in sounder alarm when smoke is detected or when power wiring polarity is reversed,
<br /> Sensitivity Status Also, chirps every 5 minutes when unit goes outside the approved sensitivity range for more
<br /> Output than one day, Resetting detector will silence chirp for one day, until unit is restored to
<br /> proper sensitivity,
<br />T Integrated Fixed Integrated Fixed 1350F (570C) temperature and rate of rise heat detector offers double
<br /> Temp, and Rate of Either heat detector or smoke detector can trip and latch LED and alann protection.
<br /> Rise Heat Detector relay outputs,
<br />L Low temperature Separate relay output that energizes when temperature around detector reaches 430F
<br /> output ::!: 50F (6.1 oC ::!: 2,8OC)
<br />E Built-in end of line Relay is nonnally energized and will trip with loss of power. Can also provide notification
<br /> power supervision relay when detector needs maintenance,
<br />
<br />@1999 Sentrol. Certain of the items in the Product Information Bulletin are protected under one or more of the following patents; 5,546,074; 5,708,414;
<br />5,798,701; 5,821,866.
<br />
<br />SENTROL
<br />12345 SW Leveton Dr., Tualatin, OR 97062
<br />Tel.: 503.692.4052 Fax: 503.691.7566
<br />http://www.sentrol.com
<br />U.S. & Canada: 800.547.2556
<br />Technical Service: 800.648.7424
<br />FaxBack: 1.800.483.2495
<br />
<br />ESL.
<br />
<br />A PRODUCT OF SENTROL
<br />
<br />Sentrol reserves the right
<br />to change specifications
<br />without notice.
<br />
<br />@1999 Sentrol
<br />
<br />E-2447-FLG15K-0996
<br />
|