Laserfiche WebLink
<br />RODAN 'FIRE SPRINKLERS INC. Page 8 <br />FLA MED CLINIC - L.H. MEZZ. Date <br />Node Elevation K-Fact pt Pn Flow Density Area Press <br />No. Actual Actual Added Req. Req. <br />1 21.5 5.6 7 na 14 .82 .1 77.5 7 <br />2 21.5 5.6 7.58 na 15.42 .1 77.5 7 <br />3 21.5 5.6 10.99 na 18.56 .1 96 7 <br />4 21. 5 5.6 15.22 na 21. 84 .1 96 7 <br />5 21.5 5.6 19.96 na 25.02 .1 196 12.25 <br />6 21.5 5.6 26.75 na 28.96 .1 196 12.25 <br />7 20.5 29.18 na <br />8 20,5 30.71 na <br />9 21.5 5.6 11. 84 na 19.27 .1 77.5 7 <br />10 21.5 5.6 13.32 na 20.44 .1 77.5 7 <br />11 21.5 5.6 16.21 na 22.55 .1 96 7 <br />12 21.5 22.84 na <br />13 21.5 26.49 na <br />14 21.5 30.46 na <br />15 20.5 30.89 na <br />16 20.5 31. 31 na <br />17 21.5 31. 29 na <br />18 21.5 31. 29 na <br />19 21.5 31. 29 na <br />20 21.5 31. 29 na <br />21 21.5 31. 29 na <br />22 20.5 31.73 na <br />23 20.5 34.96 na <br />24 16 40.18 na <br />25 16 41.35 na <br />26 16 43.59 na <br />27 16 44.12 na <br />28 10 47.12 na <br />29 10 47.15 na <br />TR 1 51.09 na <br />BR -3 52.91 na <br />A -3 52.94 na <br />B -3 53.04 na 100 <br />C 2 51. 05 na <br />TEST 2 51.17 na <br />The maximum velocity is 20.87 and it occurs in the pipe between nodes 11 and 12 <br /> <br />Computer Programs by Hydratec Inc. <br /> <br />Route 111 <br /> <br />Windham N.H. USA 03087 <br />