<br />. FORM 600A-97
<br />
<br />Code Compliance Checklist
<br />Residential Whole Building Performance Method A - Details
<br />
<br />I ADDRESS: , ZEPHYRHILLS, FL,
<br />6A-21INFIL TRATION REDUCTION COMPLIANCE CHECKLIST
<br />
<br />PERMIT #:
<br />
<br />COMPONENTS SECTION REQUIREMENTS FOR EACH PRACTICE CHECK
<br />Exterior Wmdows & Doors 606.1 ABC,1.1 Maximum:,3 cfm/sa.ft. window area' ,5 cfmlsa.ft. door area.
<br />Exterior & Adjacent Walls 606.1.ABC,1.2,1 Caulk, gasket, weatherstrip or seal between: windows/doors & frames., surrounding wall;
<br /> foundation & wall sole or sill plate; joints between exterior wall panels at corners; utility
<br /> penetrations; between wall panels & toplbottom plates; between walls and floor.
<br /> EXCEPTION: Frame walls where a continuous infiltration barrier is installed that extends
<br /> from, and is sealed to, the foundation to the too plate.
<br />Floors 606,1 ABC,1,2.2 Penetrationsfopenings >1/8" sealed unless backed by truss or joint members,
<br /> EXCEPTION: Frame floors where a continuous infiltration barrier is installed that is sealed
<br /> to the perimeter penetrations and seams.
<br />Ceilings 606,1 ,ABC, 1 ,2,3 Between walls & cei6ngs; penetrations of ceiling plane of top floor; around shafts, chases,
<br /> soffits, chimneys, cabinets sealed to continuous air barrier; gaps in gyp board & top plate;
<br /> attic access, EXCEPTION: Frame ceilings where a continuous infiltration barrier is
<br /> instaUed that is sealed at the perimeter at penetrations and seams.
<br />Recessed Ughting Fixtures 606,1 ABC,1,2,4 Type IC rated with no penetrations, sealed; or Type IC or non-IC rated, instaUed inside a
<br /> sealed box with 112" clearance & 3" from insulation; or Type IC rated with < 2.0 cfm from
<br /> conditioned SDace tested,
<br />Multi-story Houses 606,1 ,ABC, 1 ,2,5 Air barrier on perimeter of floor cavity between floors,
<br />Additional Infiltration reqts 606,1.ABC,1.3 Exhaust fans vented to outdoors, dampers; combustion space heaters comply with NFPA,
<br /> have combustion air.
<br />
<br />6A-22 OTHER PRESCRIPTIVE MEASURES (must be met or exceeded bv all residences.)
<br />COMPONENTS SECTION REQUIREMENTS CHECK
<br />Water Heaters 612,1 Comply with efficiency requirements in Table 6-12. Switch or clearly marked circuit
<br /> breaker (electric) or cutoff (oas) must be provided, Extemal or built-in heat trap reauired,
<br />Swimming Pools & Spas 612.1 Spas & heated pools must have covers (except solar heated). Non-commercial pools
<br /> must have a pump timer. Gas spa & pool heaters must have a minimum thermal
<br /> efficiency of 78%,
<br />Shower heads 612,1 Water flow must be resbicted to no more than 2,5 oallons per minute at 80 PSIG.
<br />Air Distribution Systems 610.1 All ducts, fittings, mechanical equipment and plenum chambers shall be mechanically
<br /> attached, sealed, insulated, and installed in accordance with the criteria of Section 610.
<br /> Ducts in unconditioned attics: R-6 min. insulation,
<br />HV AC Controls 607,1 SeDarate readily accessible manual or automatic thermostat for each system.
<br />Insulation 604,1,602,1 Ceilings-Min, R-19, Common walls-Frame R-11 or CBS R-3 both sides.
<br /> Common cemng & floors R-11,
<br />
<br />EnergyGauge 111 DCA Form 600A-97
<br />
<br />EnergyGauge4M=laRES'97 FLRCNA-200
<br />
|