<br />Page. 1 of 1. <br /> <br />katrina <br /> <br />From: <br />To: <br />Sent: <br />Subject: <br /> <br />"katrina" <zfd@innet.com> <br /><mwminie@wal-mart.com> <br />Friday, March 16, 2001 10:15 AM <br />Smoke Detector Tie in of Automatic Doors <br /> <br />Zephyrhills Fire Department <br />6907 Dairy Road, Zephyrhills, FL 33540 <br /> <br />Fire Chief <br />Robert Hartwig <br /> <br />Bus (813) 78Q-0041 <br />Fax(813)78~044 <br /> <br />March 16, 2001 <br /> <br />Wal-Mart <br />Michael Minieri, Manager Systems Engineering <br /> <br />Dear Mr. Minieri: <br /> <br />In reviewing the plans for fire protection based on NFPA 101, 2000 Edition, Chapter 36.3.4.2, requires a fire <br />alarm system in Class A mercantile. <br /> <br />Chapter 36 further references Chapter 9 for system requirements specifically 9.6.2. These codes leave room <br />for the smoke detectors which are required on the automatic doors included in this project, are part of the "fire <br />alarm system", and as such should be tied into the alarm circuit and upon activiation, send an alarm signal to <br />central receiving. <br /> <br />During our phone conversation on 3/15/01, we had referenced this issue. I presented our reasoning for this <br />change in the plans as submitted. <br /> <br />Thank you for your time and cooperation during the review process. <br /> <br />Sincerely, <br /> <br />Jim Johnston <br />Assistant Chief <br /> <br />JJ/klb <br /> <br />3/16/2001 <br />