<br />FORM 600A-2001
<br />
<br />Code Compliance Checklist
<br />Residential Whole Building Performance Method A - Details
<br />
<br />ADDRESS: 6208 Silver Oaks BLVD., Zephyrhills, FL,
<br />6A-21 INFILTRATION REDUCTION COMPLIANCE CHECKLIST
<br />
<br />PERMIT #:
<br />
<br />COMPONENTS SECTION REQUIREMENTS FOR EACH PRACTICE CHECK
<br />Exterior Windcws & Doors 606.1 ,ABC,1 ,1 Maximum:,3 cfmlsa,ft, window area' ,5 cfmlsa,ft, door area,
<br />Exterior & Adjacent Walls 606,1.ABC,1.2,1 Caulk, gasket, weatherstrip or seal between: wlndowsIdoors & frames, surrounding wall;
<br /> foundation & wall sole or sill plate; Joints between exterior wall panels at comers; utility
<br /> penetrations; between wall panels & toplbottom plates; between walls and floor,
<br /> EXCEPTION: Frame walls where a continuous Infiltration blIrrier is installed that extends
<br /> from and is sealed to the foundation to the too DIale.
<br />Floors 606,1,ABC,1,2,2 Penetrationsfopenings >118" sealed unless backed by truss or joint members,
<br /> EXCEPTION: Frame floors where a continuous infiltration blIrrier Is installed that Is sealed
<br /> to the oerimeter oenetrations and BeBms,
<br />Ceilings 606,1.ABC,1,2,3 Between walls & ceilings; penetrations of ceiling plane of top floor; around shafts, chases,
<br /> soffits, chimneys, cabinets sealed to continuous air blIrrier; gaps in gyp board & top plate;
<br /> attic access, EXCEPTION: Frame ceilings Where a continuous Infiltration blIrrier is
<br /> installed that is sealed at the oerimeter at oenetrations and seams,
<br />Recessed Ughting Fixtures 606,1 ,ABC,1 ,2,4 Type IC rated with no penetrations, sealed; or Type IC or non-IC rated, installed Inside a
<br /> sealed box with 112" clearance & 3" from insulation; or Type IC rated with < 2,0 cfm from
<br /> conditioned soace tested,
<br />MuJti-storv Houses 606,1.ABC,1,2,5 Air blIrrier on oerimeter of fJoor cavitY between floors,
<br />Additional Infiltration reqts 606,1 ,ABC ,1 ,3 Exhaust fans vented to outdoors, dampers; combustion space heaters comply with NFPA,
<br /> have combustion air,
<br />
<br />6A-22 OTHER PRESCRIPTIVE MEASURES Imust be met or exceeded bv all residences.)
<br />COMPONENTS SECTION REQUIREMENTS CHECK
<br />Water Heaters 612,1 Comply with effICiency requirements in Table 6-12, Switch or clearly marked circuit
<br /> breaker (e1ectrlcl or cutoff Caasl must be orovided, External or built-in heat traD reauired,
<br />Swimming Pools & Spas 612,1 Spas & heated pools must have covers (except solar heated), Non-commercial pools
<br /> must have a pump timer, Gas spa & pool heaters must have a minimum thermal
<br />.. efflciencv of 78%,
<br />Shower heads 612,1 Water flow must be restricted to no more than 2,5 aallons oar minute at 80 PSIG,
<br />Air Distribution Systems 610.1 All ducts, fittings, mechanical equipment and plenum chambers shall be mechanically
<br /> attached, sealed, insulated, and installed in accordance with the criteria of Section 610.
<br /> Ducts in unconditioned attics: R-6 min, insulation,
<br />HVAC Controls 607.1 Seoarate readilY accessible manual or automatic thermostat for each sYStem,
<br />Insulation 604,1 , 602,1 Celfings-Min, R-19, Common walls-Frame R-11 or CBS R-3 both sides,
<br /> Common ceiling & floors R-11,
<br />
<br />EnergyGauge TII DCA Form 600A-2001