Laserfiche WebLink
<br /> <br />MAINTENANCE <br /> <br />The 2400 Series has been designed to seal the sensing cham- <br />ber from back-pressure air flow, dust, dirt, and insects. The <br />back of the detector is sealed. The chamber is protected by a <br />fine mesh screen. Testing is accomplished by insertion of a <br />0.1" (2.54 mm) max. diameter tool. If cleaning is required, it is <br />easy to remove the cover and obtain access to the screen and <br />chamber to perform a thorough cleaning. <br /> <br />ENGINEERING SPECIFICATIONS <br /> <br />Smoke detector shall be a photoelectronic type (model 2400) <br />or a combination photoelectronic/thermal (model 2400TH) with <br />thermal sensor rated at 1350F (57"C) as manufactured by Sys- <br />tem Sensor. Wiring connections shall be made by means of <br />SEMS screws. The detector will have a visible LED which will <br />blink in standby and latch on in alarm. The detector shall have <br />a nominal sensitivity of 3% per foot as measured in the UL smoke <br />box. The detector screen and cover should be easily remov- <br />able for cleaning. It shall be possible to perform a sensitivity <br />and functional test without the need of generating smoke. De- <br />tector circuitry shall perform a self test on the sensing chamber <br />and internal electronics every 40 seconds. If circuitry fails, the <br />detector LED shall stop blinking. The detector shall have a <br />mounting bracket that allows for mounting to a 3-1/2" (88.9 mm) <br />or 4" (101.6 mm) octagonal or a 4" square electrical box. <br /> <br />GENERAL SPECIFICATIONS <br /> <br /> <br />Model 2400 <br /> <br />Control Panel Applications <br />Built-in Thermal <br />Visual LED Local Alarm <br />Remote LED Annunciator Capability <br />Operating Voltage Range <br />Current Limit, Standby (maximum) <br />Current Limit, Alarm (typical) <br /> <br />2-wire <br />No <br />Yes <br />Yes <br /> <br />8.5 to 35 VDC <br />120 IJA <br />(see NOTE 1) <br /> <br />(see NOTE 1) <br /> <br />Current Limit, Alarm (maximum) <br /> <br />Reversed Voltage (non-alarm) <br /> <br />Alarm Signal <br /> <br />Shunt on <br />power leads. <br /> <br />T Wiring Diagram: 2400, 2400TH, 2400AT <br /> <br />1190d1.wmf <br /> <br />(-) <br /> <br />EOl <br />Resistor <br /> <br />(+) <br /> <br />(+) <br /> <br /> <br />RA40QZ <br /> <br />I <br />.." <br />.." <br /> <br />(-) <br /> <br />(-) <br /> <br />OPTIONAL <br /> <br />OPTIONAL <br /> <br />- -- - - -~- - - - - - - -- - - - - - - - - - - - - - - - - -- - - - - - - - - --- --- - - - - - -- - - - - - - - - -- - - --- - - - - - -- <br /> <br />OPTIONAL CLASS 'A" LOOP <br /> <br />Page 2 of 2 - DA-44061 . 07/27/00 <br /> <br />PRODUCT LINE INFORMATION <br /> <br />Model <br />2400 <br /> <br />Description <br /> <br />Photoelectric smoke detector, two-wire, surface <br />mount. <br /> <br />Photoelectric smoke detector with built-in 1350F <br />(570C) fixed-temperature thermal, two-wire, sur- <br />face mount. <br />Photoelectric smoke detector with integral 1350F <br />(57"C) fixed-temperature thermal, and 85 dBA <br />horn, two-wire, surface mount. <br />Photoelectric smoke detector with isolated 1350F <br />(57"C) fixed-temperature thermal, and 85 dBA <br />horn, two-wire, surface mount. <br />Field-test module for all of the System Sensor <br />2400 Series smoke detectors. <br />Remote annunciator (LED). Mounts to single- <br />gang box. <br /> <br />2400TH <br /> <br />2400A T <br /> <br />2400AIT <br /> <br />MOD400R <br /> <br />RA400Z <br /> <br />NOTES for GENERAL SPECIFICA TIONS: <br /> <br />1) Control panels must limit current to 100 mA or less. <br /> <br />2) Maximum air velocity for photoelectric sensor operation is <br />3,000 feet (914.4 m) per minute. <br /> <br />3) Relative humidity range: 10 to 93% (non-condensing). <br /> <br />Model 2400TH <br /> <br />2-wire <br />Yes <br />Yes <br />Yes <br />8.5 to 35 VDC <br />120 IJA <br />(see NOTE 1) <br /> <br />(see NOTE 1) <br /> <br />Model 2400AT Model 2400AIT <br />2-wire 2-wire <br />Yes Yes (Isolated) <br />Yes Yes <br />Yes Yes <br />10 to 32 VDC 10 to 32 VDC <br />120 IJA 120 IJA <br />15mA@10V 15mA@10V <br />67 mA @ 32 V 67 mA @ 32 V <br />48 mA @ 24 V 48 mA @ 24 V <br />5mA@10V 5mA@10V <br />15 mA @ 24 V 15 mA @ 24 V <br />19 mA @ 32 V 19 mA @ 32 V <br />Shunt on Shunt on <br />power leads. power leads. <br /> 119011.tbl <br /> <br />Shunt on <br />power leads. <br /> <br />T Wiring Diagram: 2400AIT <br /> <br />1190d2.wmf <br /> <br />(-) <br /> <br />SMOKE DETECTION LOOP <br /> <br />EOL <br />Resistor <br /> <br />THERMAL DETECTION LOOP <br />