<br />Electrical Notes <br />2002 Electrical Code <br />Hometown Pools <br />5307 - 20th Street <br /> <br />680.22(A)(3) Dwelling Unit(s): <br /> <br />Where a permanently installed pool is installed at a <br />dwelling unites), no fewer than one 125-volt 15- or 20- <br />ampere receptacle on a general-purpose branch circuit shall <br />be located not less than 3. Om (10ft) from and not more <br />than 6.0m (20 ft) from the inside wall of the pool. This <br />receptacle shall be located not more than 2.0m (6 ft 6 in.) <br />above the floor, platform, or grade level serving the pool. <br /> <br />680.22(A)(5) GFCI Protection: <br /> <br />All 125-volt receptacles located within 6.0m (20 ft) of the <br />inside walls of the pool or fountain shall be protected by a <br />ground- fault circuit interrupter. Receptacles that supply <br />pool pump motors and that are rated 15 or 20 amperes, 120 <br />volt through 240 volts, single phase, shall be provided with <br />GFCI protection. <br /> <br />05/19/03 <br />3:12 PM <br />