Laserfiche WebLink
<br />Notes: (1) Base Panel includes the main controller board with no load, only EOl <br />resistors. <br />Standby current: three zones- 11 OmA, five zones- 120mA, ten zones 145mA. <br />Alarm current: three zones- 145mA, five zones- 170mA, ten zones- 250mA. <br />(2) The maximum battery size the panel can charge is 18Ah (Power-Sonic PIN PS-12180- <br />NB or equivalent). Refer to "Panel Specifications" in chapter 2 for more information. If <br />batteries over 7 Ah are required for the three- and five- zone panels, you must use the BC. <br />2 battery cabinet. Refer to installation sheet PIN 3100027. (3) Use <br />maximum value or actual calculated value from form B. The IDC alarm current is <br />included in the panel alarm current. <br /> <br />#8361 ZEPHRYHlllS WOMEN'S CLUB 05.20.03 <br />STANDBY <br />CURRENT (ma) <br /> <br />ALARM <br />CURRENT (ma) <br /> <br />Base Panel (1) <br /> <br />120 <br /> <br />I <br /> <br />170 <br /> <br />Aux current <br />(see form A) <br /> <br />o <br /> <br />o <br /> <br />IDC detector current <br />(see form B) <br /> <br />0.084 <br /> <br />o <br /> <br />NAC 1 load <br /> <br />o <br /> <br />0.518 <br /> <br />NAC 2 load <br /> <br />o <br /> <br />0.204 <br /> <br />NAC 3 load <br /> <br />o <br /> <br />NAC 4 load <br /> <br />o <br /> <br />o <br /> <br />I TOTAL CURRENT I <br /> <br />120.084 <br /> <br />170.722 <br /> <br />Required standby and <br />alarm time: <br /> <br />x <br /> <br />24 <br /> <br />0.085 <br /> <br />2882.016 <br /> <br />mAh <br /> <br />14.51137 <br /> <br />Battery amp hours total: <br /> <br />2896.52737 <br />2.89652737 <br />4ah <br />