Laserfiche WebLink
<br />FORM 8 <br /> <br /> Detector <br />Quanity of current Total current (4) ( quanity <br />detectors (2) (mA) (3) X current in mAl <br /> <br />D <br /> <br />IDC 1 5 0.007 0.035 <br />IDC2 1 0.007 0.007 <br />IDC3 1 0.007 0.007 <br />IDC4 2 0.007 0.014 <br />IDC5 3 0.007 0.021 <br />IDC6 0 0 0 <br />IDC7 0 0 0 <br />IDC8 0 0 0 <br />IDC9 0 <br />IDC 10 0 <br /> Total current for alllDCs = 0.084 <br /> <br />NOTES: <br /> <br />(1) Use of FSRSI, FSRZI-A, and FSRRM is limited as follows: Three and five <br />zone panels supports 2 FSRSls, 2 FSRZI-As, and 4 FSRRMs, ten zone panels <br />support 2 FSRSls, 4 FSRZI-As, and 6 FSRRMs. <br />(2) See the FireShield UL and ULC Compatibility List (pIN 3100468) for <br />Maximum number of detectors per IDC. <br />(3) See FireShield UL and ULC Compatibility List (PIN 3100468) for detectors <br />current rating. <br />(4) Maximum current per IDC may not exceed 1.5 mA. <br />(5) Aux power supplied by panel cannot exceed 0.5 A. If more than 0.5 A is <br />required, you must use compatible UUULC listed fire alarm power supply. <br /> <br />(6) When using an auxiliary power supply, you must connect the -24 OUT <br />connection on the panel to the negative connection on the auxiliary power <br />supply. Refer to the installation section for more information. <br />