Laserfiche WebLink
<br />. <br /> <br />. Electrical Specifications <br />Primary AC: 120 VRMS @ <br />50/60 hz, 2.75A <br />Total Accessory Load: 6 A @ 24 VDC <br />6 Amps @ 24 VOC of power-limited notification power <br />Standby Current: 206 mA <br />Alarm Current: 356 mA <br />Battery Charging Capacity: Up to 33 Ah <br /> <br />Notification Appliance Circuits <br />Four programmable circuits which can be programmed <br />individually as: <br />Notification Circuits: 3 amps of power-limited power per circuit <br />at 24 VOC. <br />Auxiliary Power Circuits: <br /> <br />Telephone Requirements <br /> <br />3 amps of power-limited <br />power per circuit at 24 VDC. <br />FCC Part 15 and <br />Part 68 approved <br />RJ31X (two required) <br /> <br />Type of Jack: <br /> <br />Accessory Product Information <br /> <br />RA-100 Remote Annunciator-80 character backlit LCD <br />display with a built-in keypad. The system can be fully <br />programmed and operated from any remote annunciator. The <br />IFP-100 can support up to 8 RA-100 remote annunciators per <br />system. <br />5824 Serial Parallel Module-The 5824 is a serial/parallel <br />interface that is used to connect a serial or parallel computer <br />printer to the IFP-100 control panel via the RS-485 system <br />bus. Up to two 5824 modules can be used with a system. <br />5880 LEDllnput-Output Module-The 5880 provides 40 <br />programmable LED outputs and eight supervised dry contact <br />inputs. Up to eight 5880 modules can be used on the IFP- <br />100's SBUS. <br />5865-3 and 5865-4 LED Fire Annunciators-The 5865 series <br />annunciators provide a visual indication of the current state of <br />the zone inputs on the control panel.Up to 8 Model 5865s can <br />be used on the IFP-100's SBUS. Each 5865 has 30 <br />programmable LED outputs-15 red and 15 yellow. The 5865s <br />come with a piezo sounder which gives an audible indication <br />during alarms, troubles and supervisory troubles. <br />5883- The 5883 Relay Interface Board provides 10 general <br />purpose Form C relays that can be used to control any device <br />that requires a dry contact closure. <br />SD505-APS-Analog addressable photoelectric smoke <br />detector. <br />SD505-AIS-Analog addressable ionization smoke detector. <br />SD505-AHS-Analog addressable heat sensor. <br />SD505-6AB-Six inch base designed for use with detector <br />head models S0505-APS, S0505-AIS, and S050S-AHS. <br />SD505-4AB-Four inch base designed for use with detector <br />head models S0505-APS, SD505-AIS, and SD505-AHS. <br />SD505-6IB-6 inch isolator base. The S0505-61B isolates a <br />short circuit wiring fault on a Style 7 (Class A) SLC loop. <br />SD505-6RB-6 inch relay base. The S0505-6RB adds a <br />programmable relay output to any detector on the SLC Loop. <br />SD505-6S8-6 inch sounder base adds an audible output <br />function to Farenhyt analog addressable detectors. <br />SD505-SDM- Two-wire smoke detector module allows you to <br />assign an address to a loop of conventional detection devices. <br />SD500-PS- The SD500-PS is a single action addressable fire <br />pull station featuring rugged metal construction with visible <br />LED. <br />SD505-ADHR/DTS- The SD505-ADHR analog addressable <br />duct smoke detector with built-in relay module detects products <br />of combustion present in air moving through an HVAC system. <br /> <br />The S0505-AoHR is compatible with the S0505-0TS, which <br />provides remote annunciation and testing capabilities for the <br />S0505-AOHR. <br />SD505-ADH-Analog addressable duct housing. Unit ships <br />with an attached detector base which is compatible with the <br />S0505-AIS or S0505-APS smoke detectors. (Detector and <br />sampling tubes ordered separately.) <br />SD500-AIM-Addressable input module used to connect pull <br />stations, water flow switches, and other applications requiring <br />dry contact alarm initiation devices. The AIM mounts into a 4" <br />square electrical box. <br />SD500-LED-An LED driver capable of driving 80 LEOs <br />through the SLC loop. Up to 40 S0500-LEos can be used per <br />system. <br />SD500-MIM-Mlni Addressable input module used to connect <br />pull stations, water flow switches, and other applications <br />requiring dry contact alarm initiation devices. The MIM mounts <br />into a single gang electrical box. <br />SD500-L1M-Addressable Line isolator module.that isolates a <br />short circuit wiring fault on a Style 7 (Class A) SLC loop. <br />SD500-ARM-Addressable Relay Module allows you to control <br />a normally open or closed device such as; elevator recall, door <br />closing, fan operations, and auxiliary notification. Relay can be <br />mapped to any zone condition. The ARM has two Form C <br />contacts and mounts into a 4" square electrical box. <br />SD500-ANM-Addressable Notification Module. The S0500- <br />ANM is an supervised addressable notification device that <br />provides an additional circuit on the IFP-100 SLC 100p.The <br />S0500-ANM can be programmed to use any of the IFP-100 <br />notification patterns. <br />5496 Intelligent Power Module-The Model 5496 is a 6 <br />amp. notification power expander that provides four additional <br />power-limited notification appliance circuit outputs. <br />RPS-1000 Intelligent Power Module--Adds 5 amps of output <br />power, six programmable Flexput™ I/O circuits and 2 Form C <br />relay circuits to the system. Up to eight RPS-1000 modules <br />can be used on the FACP. <br />5650 Down load Software-User-friendly software for remote <br />programming of the IFP-100. The software is compatible with <br />Window™ 95, Windows™ 98, and Windows™ NT. <br />5670 IntelliView Facility Management Software-End-user <br />software allows viewing of detector status and event history via <br />modem or direct connect. <br /> <br />~ SILENT <br />I<NIGHT <br /> <br />'" <br /> <br />7550 Meridian Circle, Maple Grove, MN 55369-4927 <br />1-800-446-6444 or in Minnesota 763-493-6435 <br />FAX: 763-493-6475 <br />World Wide Web: http://www.farenhyt.com <br /> <br />.~~~~=~~ <br /> <br />.,. <br /> <br />Made in the U.S.A. <br /> <br />("'.~ <br />.~!!J! <br /> <br /> <br />