My WebLink
|
Help
|
About
|
Sign Out
Browse
Search
04-2772
Zephyrhills
>
Building Department
>
Permits
>
2004
>
04-2772
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
3/6/2009 3:25:51 PM
Creation date
1/23/2007 6:58:29 AM
Metadata
Fields
Template:
Building Department
Building Department - Doc Type
Permit
Permit #
04-2772
Building Department - Name
STANLEY,SCOTT
Address
7135 APPLEGATE DR
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
8
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
<br />. <br />~ <br /> <br />Architectural Testing <br /> <br />15 April 2002 <br /> <br />Mr. Marsh Fembaugh, Director of Testing <br />Alside, Window Company <br />3773 State Road <br />Akron, Ohio 44309-1365 <br /> <br /> <br />RE: Masonry Installation of 0201 Double Hung Window, 3' 0" by 6' 0" <br /> <br />Dear Mr. Fembaugh: <br /> <br />At your request, I have performed an installation fastener analyses into masonry <br />block walls for Alside double hung windows, Model 0201. The testing of the actual <br />windows was done under AT! project 05-30324.02. The fastener analyses provides a 3' <br />0" wide by 6' 0" high window with an allowable installation design wind pressure (D.P.) <br />of +/- 55.0 psf. <br /> <br />To provide this D.P. in a masonry block wall requires 6 Tapcons, each 3/16" in <br />diameter. There should be 3 Tapcons through each window jamb frame, one near the top, <br />one at the midheight, and one near the bottom. The minimum penetration of the Tapcons <br />into solid masonry must be 1-1/4". <br /> <br />These results are appropriate for the size window stated in the first paragraph <br />above, and any size smaller. If there are any questions about this analyses, please advise <br />me. <br /> <br />Sincerely yours, <br /> <br />ARCHITECTURAL TESTING, INe. <br /> <br />~ <br /> <br />t2L4." n, ~ <br />Allen N. Reeves, P.E. <br />Director - Engineering Services <br />/~ v'VL)" 2. Od2- <br /> <br />ANR:anr <br />cc: 01-41462 <br />05-30137 <br /> <br />-- <br /> <br />..,.... <br /> <br />130 Derry Court <br />York, PA 17402-9405 <br />phone: 717.764.7700 <br />fax: 717.764.4129 <br />
The URL can be used to link to this page
Your browser does not support the video tag.