Laserfiche WebLink
<br />Hometown Pools <br />2002 N.E.C. <br />5251 - 5th Street <br /> <br />680. 22(A)(3) <br />Dwelling Units <br /> <br />Where a permanently installed pool installed at a dwelling(s), no tewer than one llb-volt lb- or lU-ampere receptacle <br />on a general-purpose branch circuit shall be located not less than 3.0 m (10ft) from and not more than 6.0 m (20ft) <br />from the inside wall of the pool. This receptacle shall be located not more than 2 m (6ft 6in) above the floor, <br />Dlatform. or orade level servino the DOol. <br /> <br />680. 22(AX5) <br />GFa Protection <br /> <br />All 125-volt receptacles located within 6.0 m (20 ft) of the inside walls of a pool or fountain shall be protected by a <br />ground-fault circuit interrupter. Receptacles that supply pool pump motors and that are rated 15 or 20 amperes, 120 <br />volt through 240 volts, single phase, shall be provided with GFCI protection. <br /> <br />680. 22(A)(6) <br />Measurements <br /> <br />In determining the dimensions in this section addressing receptacle spacing, the distance to be measured shall be the <br />shortest path the supply cord of an appliance connected to the receptacle would floor without piercing a floor, wall, <br />ceiling, doorway with hinged or sliding door, window opening, or other effective permanent barrier. <br /> <br />680. 26(B) <br />Bonded Parts <br /> <br />The parts specified in 680.26(B)(1) through (B)(5) shall be bonded together. <br />