Laserfiche WebLink
<br />Wendle Sheet Metal Inc. <br />CSC056662 '" 335 N Buena Vista Drive <br />Lake Alfred, FL 33850 <br />Phone 863-956-2217 '" Fax 863-956-5102 <br /> <br />Jobsite: Young Life Health Foods <br />5914 Gall Blvd <br />Zephyrhills, FL 33539 <br />Contact: Linda Reffit <br />813-782-5405 <br /> <br />HOOD SPECIFICATIONS <br /> <br />HOOD: 4 FT X 25" - 18 GA GALVANIZED, 29 INCHES <br />HIGH AS PER NFPA CODE 96-5.1, 5.3 & 6.2. AND <br />FBC 507.4 AND FBC 507.7, 507.12-13 <br /> <br />FILTERS: HIGH VELOCITY BAFFLE TYPE AS PER <br />NFPA CODE 96-6.1, 6.2.3 AND FBC 507.11 <br /> <br />HOOD HEIGHT: APPROXIMATELY 6 FT INCHES FROM THE <br />FLOOR. CEILING CLEARANCE MINIMUM 18" <br />TO COMBUSTIBLES PER NFPA 96-4.2.1 <br /> <br />EXHAUST STACK: 16 GAGE EXTERNALLY WELDED (LlQUIDTIGHT) <br />SIZED FOR A MINIMUM OF 1500 FPM VELOCITY. <br />TERMINATES 18" ABOVE ROOF LINE WITH WELDED <br />FLANGE FOR SUPPORT. AS PER NFPA CODE 98-7.5,96- <br />7.3,96-7.8 AND FBe 506.3.3, 506.3.4, 506.3.8 PROTECTED <br />AS PER NFPA CODE 96-4.2.3 AND FBC 308.6. <br /> <br />EXHAUST OUTLET: LOCATED AT LEAST 10 FT FROM AIR INTAKE AS <br />PER FBC 506.3.14, 507.16 AND NFPA CODE 96-7.8. <br /> <br />EXHAUST FAN: ONE 1400 CFM @ 1/8" S.P., EXHAUST AIR FLOWS <br />AWAY FROM THE SURFACE OF ROOF AS PER <br />NFPA CODE 96-7.8.2,96-8 AND FBC 507.13.1- 4 <br /> <br />EXHAUST DISCHARGE: ROOF TERMINATION TO BE 40 INCHES ABOVE THE <br />ROOF LINE AS PER 'BC 506.3.14..1 AND NFPA <br />CODE 96-5-8.2. <br /> <br />REPLACEMENT AIR: 1200 CFM FILTERED AIR INTEGRATED INTO THE HOOD <br />AS PER NFPA CODE 96-8.3, AND FBC 508.1. <br />