<br />SECTION IV - SYSTEM DESIGN <br />UL EX. 3470 ULC CEx747 Page 4-46 <br />REV. 3 10-1-02 <br /> <br />DISTRIBUTION PIPING REQUIREMENTS (Continued) <br /> <br />Distribution Piping Requirements - 3.0 Gallon System <br /> <br />1. The maximum leng1h between the start of the first branch line <br />and the start of the last branch line must not exceed 24 ft. <br />(7.3 m). When the supply line is split. the combined total of <br />both legs of the supply line (from the start of the first branch <br />line to the start of the last branch line) must not exceed 24 ft. <br />. (7.3 m). See Figure 84. <br /> <br />2. The total length of all branch lines must not exceed 36 ft. <br />. (10.9 m). See Figure 84. <br /> <br />3. Use a 3/8 in. union to connect the tank adaptor to the 3/8 in. <br />supply line. <br /> <br />4. A maximum of two nozzles are allowed per duct branch line. <br /> <br />5. The requirements of the following table must not be exceeded: <br /> <br /> <br />3 BRANCH LINES <br /> <br /> <br />L <br /> <br />'Exceptions: <br />1. Twelve (12) flow numbers are allowed in any one tank not containing two-flow appliance nozzles, and/or. a 1N nozzle for wok or griddle protection, and/or, a 1F nozzle for range <br />protection, and/or, e 3N nozzle for f~r protection. <br />. 2. Twelve (12) flow numbers are aHowed in any one tank for hood and duct protection. <br />3. Twelve (12) flow numbers are allowed with any one tank using only two-flow eppliance nozzles. <br />4. Twelve (12) flow numbers ere allowed with any one tank using only three-flow appliance nozzles. <br />Special Instruction.: <br />1. Twelve (12) flow numbers are allowed when four (4) Dean Industries GTI Gas F~rs are protected at low proximity as shown in Figure 101 on pags 4-52. The discharge piping <br />must be as shown in Figure 102 on Page 4-52. <br />2. For certain McOonald's applications. 11.5 flow numbers are allowed when using a combination of one (1) 2W duct nozzle, one (1) 112N electrostatic precipitator nozzle, <br />one (1) 1N plenum nozzle, and four (4) two-flow appliance nozzles. Contact Ansul Applications Engineering Department for additional information. <br />