Laserfiche WebLink
<br />ELECTRICAL SPECIFICATIONS <br /> <br />GENERAL <br />A. PROVIDE ALL LABOR, MATERIALS, EQUIPMENT AND SERVICES NECESSARY FOR <br />AND INCIDENTAl TO THE COMPLETE INSTALLATION AND OPERATION Of AlL <br />ELECTRICAL WORK AlL WORK SHALL BE DONE BY QUALIFIED PERSONNEL. <br /> <br />B. CONFORM TO THE NATIONAl ELECTRICAl CODE 11996 EDiTION>, AND THE NATIONAl <br />ELECTRICAl SAFETY CODE 1996 EDITIONS. THE INSTAlLATION SHAlL COMPLY WITH <br />i'PPUCABLE RULES ~ REGULATIONS Of LOCAl AND STATE AUTHORITIES HAVING <br />JIJRISOIC T ION <br />C. COORDINATE THE WORK Of AlL TRADES. <br /> <br />D ARRANGE CONDUIT, WIRiNG, EQUIPMENT, AND OTHER WORK GENERAlLY AS <br />SHOWN, PROVIDING PROPER CLEARANCES AND ACCESS. CAREFUlL ~ EXAMINE <br />AlL CONTRACT DRAWINGS AND FIT THE WORK iN EACH LOCATION WITHOUT <br />SuBSTANTiAl AlTERATION WHERE DEPARTURES ARE PROPOSED BECNJSE OF <br />FIELD CONDITIONS OR OTHER CAUSES, PREPARE A'iD SUBMIT DETAILED <br />DRAWINGS FOR ACCEPTANCE, THE RIGHT IS RESERVED TO MAKE REASONABLE <br />CHANGES IN LOCATION Of EQUIPMENT, CONDUIT, AND WIRING UP TO THE TIME <br />OF ROUGH-IN OR FABRICATION <br />THE CONTRACT DRAWINGS ARE GENERALL ~ DIAGRAMMATIC A'iD AlL OfFSETS, <br />BENDS, FITTINGS AND ACCESSORIES ARE NOT NECESSARilY SHOWN <br />PROVIDE ALL SUCH ITEMS AS MA~ BE REQUIRED TO FIT THE WORK TO THE <br />CONDITIONS <br />F. THERE SHAlL BE NO INTERRUPTION Of POWER TO EXISTING ELECTRICAl <br />SYSTEMS WITHOUT PRIOR CONSENT OF THE BUILDING OWNER SUCH <br />INTERRUPTlO'iS SHAlL BE KEPT TO A MINIMUM AND SHAlL BE SCHEDULED <br />WITH THE OWNER AT LEAST THREE BUSINESS DA~S IN ADVANCE OF THE <br />OUT AGE ANY COST FOR WORK THAT MUST BE DONE ON AN OVERTIME <br />BASIS SHAlL BE INCLUDED iN THE BID, <br />G vISIT THE SITE AND INSPECT THE EXISTiNG CO'iDITIONS BEFORE BID IN <br />ORDER TO ENSURE PROPER EVAlUATION OF WORKING CONDiTiONS AND <br />LOCATION OF EXIS TING CONDITIONS <br />H WHERE OUTLETS ARE REMOVED OR CIRCUITS INTERRUPTED OR BROKEN, PROVIDE <br />THE REQUIRED RELOCATION, RECONNECTION OR REARRANGEMENT TO RESTORE <br />SERVICE TO AlL ITEMS, OUTLETS, ETC NOT MADE OBSOLETE BY THIS WORK. <br />MOUNTING AND SUPPORTING OF AlL EQUIPMENT PROVIDED UNDER THIS SECTION <br />SHAlL BE COORDINATED WITH THE CONSTRUCTION MANAGER IN THE FIELD <br />PERMITS AND FEES <br />A. OBT !\iN, PAY FOR, AND DElIVER AlL PERMITS, CERTIFICATES OF INSPECTION, <br />ETC., REQUIRED BY THE AUTHORiTIES HAVING JURISDICTION DELIVER <br />CERTIFICATES TO THE OWNER PRKlR TO FINAl ACCEPTANCE Of THE WORK. <br /> <br />MATERIAL AND EQUIPME.NT <br />A_ MATERiAl AND EQUIPMENT INSTAlLED AS A PART Of THE PERMANENT <br />~tETC,}~lD~!~DS~:iAtLB~ENC~'r~~L~~S AO~~~:mJ~L ~ND~l~b1PNlPrD TESTING LAB, <br />FOR INSTAlLATION IN EACH PARTICULAR CASE, WHERE STANDARDS <br />HAVE BEEN ESTABLISHED. <br /> <br />CUTTING AND PATCHING <br />A. PROVIDE AlL CUTTING AND PATCHING NECESSARY FOR THE INSTAlLATION OF <br />THE ELECTRICAL WORK. ANY DAMAGE DONE TO THE WORK AlREADY IN PLACE <br />BY REASON OF THIS WORK SHAlL BE REPAIRED AT THE CONTRACTOR'S EXPENSE <br />BY A QUAliFIED MECHANIC EXPERIENCED iN SUCH WORK, PATCHING SHAlL BE <br />UNIFORM IN APPEARANCE AND SHAlL MATCH THE SURROUNDING SURf ACE. DO <br />~OT CUT STRUCTURAl MEMBERS WITHOUT APPROVAl BY THE CONSTRuCTION <br />MANAGER WHERE PENETRATIONS ARE NECESSARY THROUGH THE ROOF, <br />PROVIDE AlL NECESSAR~ CURBS, SLEEVES, SHIELDS, FLASHING, FITTINGS, <br />AND CAULKING TO MAKE THE PENETRATIONS ABSOLUTELY WATERTIGHT. <br /> <br />ELECTRICAl WORK UNDER OTHER DIVISIONS <br />A oN GENERAl POWER WIRING FOR SYSTEMS ARE INCLUDED UNDER THIS <br />SPECIFICATION_ CAREFULL ~ REVIEW THE CONTRACT DOCUMENTS AND <br />COORDINATE THE ELECTRICAl WORK TO BE PERFORMED UNDER THE <br />OTHER DIVISIONS <br /> <br />GUARANTEE <br />A, GUARANTEE THE ELECTRICAl SYSTEM INSTAlLED BY THE CONTRACTOR FREE <br />FROM AlL MECHA~ICAl AND ELECTRICAl DEFECTS FOR THE PERIOD OF ONE <br />~EAR BEGINNING FROM THE DAY OF FINAl ACCEPTANCE Of THE WORK OR <br />BENEFICiAl OCCUPANCY BY THE OWNER, WHICHEVER OCCURS FIRST <br />B UPON RECEIPT OF NOTICE FROM THE OWNER OF FAILURE OF ANY PART OF THE <br />ELECTRICAl INSTAlLATION DuRING THE GUARANTEE PERIOD, NEW REPLACEMENT <br />PARTS SHAlL BE FURNISHED AND INSTAlLED PROMPTLY AT NO COST TO <br />THE OWNER <br /> <br />CONDUIT AND FITTINGS <br />A, MINIMUM CONDUIT SIZE SHALL BE r." (UNLESS OTHERWISE INDICATED) <br /> <br />B SUPPORT AlL CONDUIT NOT EMBEDDED IN CONCRETE OR MASONRY SO "HAT <br />STRAIN IS NOT TRANSMITTED TO OUTLET BOXES AND PULL BOXES, ETC <br />SUPPORTS TO BE SUFFICIENTLY RIGIO TO PREVENT DISTORTION Of CONDUITS <br />DURING WIRE PUlliNG. <br /> <br />C. ALUMINUM CONDUIT IS PROHIBITED, <br />D. AlL CONDUITS SHALL BE ELECTRICAl METAlLIC TUBING IEMT), PVC, OR RIGID <br />GAlVANIZED STEEL (EXTERIOR EXPOSED) <br /> <br />E. EMT CONDUIT FITTINGS SHAlL BE FERROUS COMPRESSION TYPE <br /> <br />F IN DAMP OR WET LOCATIONS USE FLEXIBLE, LIQUID-TIGHT METAl CONDUIT <br />WITH APPROVED FITTINGS <br />COORDINATIO'4 <br /> <br />A. COORDINATE THE WORK OF POWER, GROUNDING AND TELCO <br />AT EQUIPMENT WITH EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN <br />FINAl TERMINATIONS TO BE AT THE DIRECTION OF THE <br />EQUIPMENT SUPPLIER <br /> <br />B PRIOR TO BEGINNING WORK CONTRACTOR SHAlL COORDINATE AlL POWER <br />~ TELCO WITH THE LOCAl UTILITY COMPA'4Y AS IT MAY i'PPL Y TO THIS <br />SITE AlL WORK TO COMPL ~ WITH THE RULES AND REGULATIONS OF THE <br />UTILITIES IN VOL VED. <br /> <br />WIRES AND CABLES (600 VOLTS) <br />A. BUILDING WIRE, UNLESS OTHERWISE INDICATED SHAlL BE 600 VOLTS, TYPE <br />THWN I'4SUlATlON CONDUCTORS SHAlL BE SIZED AND RUN AS INDICATED <br />CONDUCTORS SHAlL BE SOfT DRAWN COPPER Of NOT LESS THA'4 981. <br />CONDUCTIVITY <br /> <br />AlL <br /> <br />CONDUCTOR INSULATION <br /> <br />AlL CONDUCTORS SHAlL BE COLOR CODED AS REQUIRED B~ NEC A'40 FURTHER <br />IDENTIFIED AND CODED AS SPECIFIED HEREIN?fTER COLOR CODING SHAlL BE <br />B~ MEANS OF COLORED INSULATING MATERiAl, COLORED BRAID OR JACKET <br />OVER THE INSULATION OR BY MEANS Of SUIT ABLE COLORED, PERMANENT, <br />NON-AGING, INSULATiNG T i'PE i'PPlIED TO CONDUCTORS AT EACH CABINET <br />OR JUNCTION POINT THE COLOR CODING SHAlL BE ACCOMPliSHED AS THE <br />CONDUCTORS ARE INSTAlLED THE FOLLOWING SYSTEMS OF COLOR CODiNG <br />SHALL BE STRICTLY ADHERED TO <br /> <br />~ GROUND LEADS' GREEN <br />B) GROUNDED NEUTRAl LEADS' WHITE <br />C) 12D/208 VOL T (120/240 VOLT) UNGROUNDED PHASE WIRES: <br />BLACK, RED, BLUE <br /> <br />THE COLOR CODE ASSIGNED TO EACH PHASE WIRE SHAlL BE CONSISTENTLY <br />FOLLOWED THROUGHOUT <br /> <br />CONDUIT SUPPORTS <br /> <br />A_ SUPPORT SURF ACE RUNS OF CONDUIT USING ONE OR TWO HOLE PIPE STRi'PS <br />STRAP SPACING 6 FOOT ON CENTERS, MAXIMUM, UNLESS NOTED OTHERWISE. <br /> <br />B. FASTEN STRi'PS TO CONCRETE USING INSERTS OR EXPANSION BOLTS AND TO <br />HOLLOW MASONRY USING TOGGLE BOLTS WOODEN PLUGS ARE UNACCEPTABLE. <br /> <br />OUTLET, JUNCTION AND PULL BOXES <br /> <br />A. AlL BOXES, WHETHER OUTLET, JUNCTION, PULL, OR EQ(JIPMENT SHAlL BE <br />FURNISHED WITH APPROPRIATE COVERS. <br /> <br />13. NO SECTIONAlIZED BOXES SHAlL BE USED. <br /> <br />C. OUTLET, JUNCTION AND PULL BOXES SHAlL BE SHEET STEEL WHERE REQUIRED <br />TO F AC III T ATE PULLING Of WIRES OR CABLES, SUCH BOXES SHAlL BE RIGIDLY <br />MOUNTED AND INSTALLED IN ACCESSIBLE LOCATIONS <br /> <br />SEE DRAWINC NOTE OF SAME NUM8ER <br />8, M KILOWATTHOUR METER <br />6' CONDUIT OR CABLE-UP, DOWN <br />__ --... "? U'i.'b~R~i:6~Ni?lID, T1""'ED COPPER CONDUCTOR <br />......-------.. #',/ AWG BARE, SOLID, TINNED COPPER CONDVCTOR ROVTlNG <br />AS SHOWN ON DWG'S <br />~ CONDUIT TERMINATED OR TRANSiTION AS INDICATED IN PLAN <br />--il. STANDARD GROUND ROO -Y,"xl0'-0" <br />, - E - - UNDERGROUND CONDUIT, POWER <br />- - T - - UNDERGROUND CONDUIT, TElCO <br />[DJ OJ FUSED SERVICE DISCONNECT SWITCH, NON-FUSED <br />. EXOTHERMIC WELD OR MECHANICAl GROUND BOND <br /> <br />A. <br /> <br />IDENTIFICATION Of EQUIPMENT <br />A MARK AND PERMANENTLY IDENTIFY AlL ELECTRICAl EQUIPMENT IDENTIFICATION <br />SHAlL BE LAMINATED PLASTIC PLATES, BLACK WITH WHITE ENGRAVED LETTERS USE <br />'/~" HIGH LETTERING, ATTACH PLATES WITH CHROME PLATED OR 316 STAINLESS STEEL <br />SCREWS TO THE DEVICE USE NOMENCLATURE ON DRAWINGS <br />13. AlL EQUIPMENT SHALL BE MARKED WITH WARNING LABELS AND SIGNAGE AS REQUIRED <br />BY THE NATIONAl ELECTRIC CODE AND OTHER APPliCABLE STANDARDS <br /> <br />ELECTRICAL LEGEND <br /> <br />SAFETY DISCONNECT SWITCH <br /> <br />A. PROVIDE S?fETY DISCONNECT SWITCHES AS SHOWN ON THE DRAWINGS AND WHERE <br />REQUIRED B~ THE NATIONAl ELECTRICAl CODE. SWITCHES SHALL BE HORSEPOWER-RATED <br />WHERE i'PPlICABlE, AND SHAlL BE THE SIZES REQUIRED SERVICE ENTRA'4CE SWITCH <br />SHAlL BE SO RATED, <br /> <br />B SWiTCHES SHAlL BE HEAVY DUTY TYPE FUSED OR UNFUSED, AS iNDICATED: SIDE HANDLE <br />OPERATED, 'lEMA 1 FOR GENERAl INTERIOR WORK AND 'lEMA 3R STEEL <br />FOR EXTERIOR, DAMP, OR WET LOCATIONS. SWITCHES SHAlL BE EQUIPPED WITH A <br />COVER INTERLOCK TO PREVENT OPERATION WITH COVER OPEN. <br /> <br />C SWITCHES SHAlL BE VISIBLE BLADE. EXTERNAlL Y OPERATED, WITH All CURRENT CARRYING <br />PARTS SILVER OR TIN-PLATED, AlL SWITCHES SHAlL HAVE PROVISIONS FOR NOT LESS THAN <br />TH.AN TWO EXTERNAl PADLOCK <br /> <br />-0- <br />-t- <br /> <br />INSPECTiON SLEEVE <br /> <br />GROUND ROO EXOTHERMiCN.L Y WElDED TO <br />BURIED GROUND RING <br /> <br />ELECTRICAL LOAD SUMMARY - NEXTEL <br />EXISTING 1201240V-SINGlE PHASE-3W 200 AMPERE SERVICE <br />22,000 A<C. <br />lOA<D DESCRIPTION IS..U <br /> <br />LICHTING <br /> <br />RECEP T AClES <br /> <br />A<R CONDITlONINC <br /> <br />COMMUNICATION EQUIPMENT <br /> <br />FANS <br /> <br />TOT N. CONNECTED lOAD <br /> <br />. VERIFY A<C - OBTAJN AVA<LABLE FAULT CURRENT IAFC) FOR <br />ElECTRIC UTILITY A<C MUST EXCEED AFC 0 POINT OF SERVICE <br /> <br />GROUNDING <br /> <br />A. ~~2~:S;ENGrLOyUN3,t ~~F fCLT I~~f~ WI~ Y 1Cg~~18~ct'4~1 ?HT I~t ~0~~M[SvrMOEFN T <br /> <br />THE '4ATIONAl ELECTRICAl CODE AND AS HEREINAFTER SPECIFIED AlL <br />GROUNOED NEUTRAl CONDUCTORS SHAlL BE CONTINUOUSLY IDENTIFIED. AlL <br />CROUNDING AND BONDING CONNECTIONS SHALL BE SOlDERLESS, <br /> <br />B PROVIDE iNSULATED GROUNDING CONDUCTORS FOR FEEDER I-NO BRANCH CIRCUIT <br />WIRING AS CAlLED FOR ON THE PLANS. PROVIDE GROUNDING BLOCKS, <br />TERMINAlS, ETC ,FOR CONNECTION OF GROUND WIRE IN AlL DISTRIBUTION <br />EQUIPMENT, OUTLETS, JUNCTiON BOXES, AND UTILIZATION EOUIPMENT TERMINATE <br />WITH LUGS OR COMPRESSION TERMiNAlS. CONDUCTORS LOOPED UNDER BOLTS OR <br />SCREWS Will NOT BE ACCEPT ABLE. <br /> <br />C GROUNO ROOS WHEN NEEDED SHAlL BE STEEL, COPPER CLAD 'Ie" DIAMETER BY <br />TEN FEET LONG GROUND ROD SHIELDS TO BE PROVIDED FOR DRIVING RODS. <br /> <br />D PRIOR TO INSTAlLATION OF THE GROUNOING S~STEM, THE EARTH RESISTIVITY <br />SHAlL BE MEASURED USING WENNER FOUR TERMINAl METHOD REPORTS OF THE <br />MEASURED RESISTIVITY MUST BE SUBMITTED TO THE CONSTRUCTION MA'iAGER <br /> <br />E. THE MAXIMUM RESISTANCE OF THE COMPLETED GROUNDING S~STEM SHALL NOT <br />EXCEED 5 OHMS ON ANY PART Of THE SYSTEM, IF DUE TO SOil CONDITIONS <br />OR OTHER PARAMETERS THIS MAXIMUM VALUE IS EXCEEDED, CONTACT THE <br />ENGINEER FOR ADOITIONAl INSTRUCTIONS <br /> <br />10 KVA <br />16 KVA <br />120 KVA <br />250 KVA <br />037 KVA <br />3997 KVA <br /> <br />CALCULATED TOTAL DEMAND <br />DEMAND 18 KW NEXTEL (BASED ON SIMILAR SITES) <br />88 A<MPS 0 0 B5 Pf,240V . 441 <br /> <br />F. GROUND BAR PLATES ARE TO BE MANUFACTURED EXACTL~ AS DETAILED AND <br />DIMENSIONED DIMENSIONS TO BE ACCURATE TO ioS2" <br />G. AlL MOUNTING HARDWARE SHAlL BE STAINLESS STEEL <br />H, AlL BARE COPPER SURFACES SHALL BE COATED PRIOR TO LUGGING. JOINT <br />COMPOUND SHAlL BE KOPR-SHIELD BY THOMAS I< BETTS <br />I. CONNECTION OF CONDUCTORS BELOW GRADE TO GROUND RODS. GROUND <br />RINGS, GROUND WELL, ETC ,SHAlL BE EXOTHERMIC TYPE WELDiNG CONNECTIONS <br />"CADWELD" <br />J CONNECTION OF CONDUCTORS ABOVE GRADE TO METAlliC OBJECTS OR IN <br />HANDHOLES SHAlL BE WITH PRESSURE T~PE CRIMP CONNECTORS, BOl TED <br />CLAMPS, OR SPLIT BOLT CONNECTIONS WITH SOLiD BRONZE H!>RDWARE, CADMIUM <br />PLATED STEEL HARDWARE is NOT ACCEPTABLE CONNECTIONS TO INTERIOR HAlO <br />GROUND RING SHAlL BE WITH 'C' CLAMPS. SOLID TO SOliD AND STRANDED <br />CONOUCTORS REQUIRES TWO (2) CLAMPS AlL 'C' CLAMPS REQUIRE INSTAlLATION <br />WITH THE CORRECT HYDRAULIC CLAMP TOOL <br /> <br />ABBREVIATIONS & <br />SYMBOLS <br />A - AMPERE <br />AFF - ABOVE FINISHED FLOOR <br />AFG ,ABOVE FINISHED GRADE <br />AFR - ABOVE FINISHED ROOf <br />ACB - ANTENNA GROUND BAR <br />A<HU - A<R HANDlINO UNIT <br />A<C - AMPERES INTERRvPTING <br />AWG - EYER,{jE~ WIRE GA(X;E <br />BKR, C8 - CIRCUIT BREAAER <br />CAT - CATALOG <br />C, CONDo - CONDUT <br />CK T - CIRCUIT <br />DWO - DRAWING <br />EMT - ElECTRICAl METAllC TU81NO <br />FSS - FUSED SAFETY SWITCH <br />GFI - GROUND F AVLT INTERRUPTING <br />GRO - GROUND <br />KVA - KIlOVOL T-A<MPERES <br />MC8 - MAJN CIRCUT BREAAER <br />MGB - MA<N GROUND BAR <br />M.H - MOUNTING HEIGHT <br />lolL 0 - MAJN LUG ONLY <br />NEC - NATIONN. ElECTRICAL CODE <br />NEMA 'NATlONN. ElECTRICAl <br />MANUF ACTURERS ASSOCIATION <br />NETA - NATIONAl ElECTRICAl TESTING <br />ASSOCIA TlON <br />NFSS - NON-FUSED SAFETY SWITCH <br />NIC - NOT IN CONTRACT <br />NO. - NUMBER <br />OCP - OVER CURRENT PRO,ECTlON <br />P - POLE <br />PVC - POL YVINn CHL ORIDE <br />ReS 'RIGID GAlVANIZED STEEl <br />SPST - SINGLE POLE, SINGLE THROW <br />TYP - TYPICN. <br />V - VOlTS <br />WP - WEATHERPROOF <br />'1l - PHASE <br /> <br />SUPPORTS, HANGERS A'iD FOUNDATIONS <br /> <br />A_ PROVIDE AlL SUPPORTS, HA'iGERS, BRACES, ATT ACHME'4TS, AND FOUNDATIONS <br />REQUIRED FOR THE WORK SUPPORT AND SET THE WORK IN A THOROUGrlL ~ <br />SUBST ANTIAl AND WORKMANLIKE MANNER WITHOUT PLACINC STRAINS ON THE <br />MATERiAlS, EQUIPMENT, OR THE BUILDING STRUCTURE <br /> <br />B SUPPORTS, HANGERS, BRACES AND ATT ACHMENTS SHAlL BE ST A'4DARD <br />M,ANUF ACTURED ITEMS OR FABRICATED STRUCTURAl STEEL SHAPES. <br /> <br />AS-BUILT DATA <br /> <br />A, CONTRACTOR SHAlL PREPARE AND SUBMIT TO THE CO'4STRUCTION MANAGER <br />"AS-BUlL T" DRAWiNCS FOR CHA'iGES OR DEVIATIONS FROM CONTRACT DRAWINGS <br />TO THE FOLLOWING' <br /> <br />1. SOURCE, ORIGIN, AND/OR ROUTING OF MAlN FEEDERS <br /> <br />2. LOCATION OF MAJOR PIECES OF DISTRIBUTION EQUIPMENT <br />SUCH AS KllOWATTHOUR METER AND MNN FEEDER <br />OVERCURRENT DEVICES <br /> <br /> <br />NEXTEL CORPORATION <br />4710 EISE.....llOWER BLVD. <br />BLDG, D-1 <br />TAM.PA. FWRIDA 33634 <br />(813) 806-4000 <br /> <br />BIRD LAKE <br />SITE No, FL-3412-B <br /> <br />I DATE'DECEMBER 13,2005 <br /> <br />REVISIONS <br />NO. DATE <br />1 ISSUED FOR CONSTRUCTION <br /> <br />2 <br /> <br />3 <br /> <br />4 <br /> <br />5 <br />6 <br /> <br />~ <br />. <br />A <br />A <br />A <br />-..- <br /> <br />KC] <br /> <br />ISITE NAME <br /> <br />BIRD LAKE <br /> <br />I SHE NUMBER <br /> <br />FL-3412-B <br /> <br />I SITE ADDRESS <br /> <br />38122 HENRY DRIVE <br />ZEPHYRHILLS, FLORIDA 335~ <br />(PASCO COUNTY) <br /> <br />~~T TITLE ' <br /> <br /> <br />LECTRICAL SPECIFICATIO <br /> <br />rv\i~\ b'J E-' <br /> <br />10054100AB <br />