Laserfiche WebLink
<br />liRE IILI\Rll \Cl~ES;:;1 ) f':: " <br /> <br />5104 Fire Control <br />Communicator <br /> <br />Specifications <br /> <br />Electrical <br /> <br />Slave Applications - Not UL Listed <br />Input: 24VDC from a UL Listed Fire Control Panel <br />Total DC load: 75mA minimum at 24VDC <br />600mA maximum at 24VDC <br /> <br />Current: <br />Standby <br />Alarm <br /> <br />50 mA <br />135 mA <br /> <br />Stand Alone Applications <br /> <br />Input: <br />Standby: <br /> <br />120VAC 60Hz. 40 watts <br />12 volt 7 amp hour rechargeable battery <br />(supplied) <br /> <br />5230 Remote Annunclator (three maximum per system) <br /> <br />Load: <br /> <br />60mA standby <br />120mA alarm <br /> <br />Indicator Lights (LEDs): <br /> <br />Power On (Green) <br /> <br />Trouble Silenced (Yellow) <br />Until Trouble Is Cleared/Flashing = Supervisory <br /> <br />Dialer Failure (Yellow) <br /> <br />Telephone Line Fault (2 Red) <br />Inside Cabinet at L 1 and L2 Inputs <br /> <br />Telephone Requirements: <br /> <br /> <br />--- ,...,~,~_,,,,- I <br />,"I","~' =-J <br /> <br />._~.._ f~ l&lARN <br />,______-=-.::.~...,~_'roR <br /> <br />Model 5230 <br /> <br /> <br />FCC Registration #: AC698R-17462-AL-E <br />RINGER EQUIVALENCE 0.08 <br /> <br />Type of Jack: RJ31X (2 required) <br /> <br />Mechanical: <br /> <br />Dimensions: <br /> <br />Weight: <br />Color: <br /> <br />12.25" W x 14.5" H x 3.0" D <br />(31.1cm W x 36.8 Gm H x 7.6cm D) <br /> <br />15 Ibs. (6.75 kg) <br /> <br />Red <br /> <br />Optional Accessories: <br /> <br />5230 Remote Annunciator/Programmer <br /> <br />5561 Download Package <br /> <br />7181 Fire Zone Converter Module <br /> <br />7860 Telephone Connecting Cord for RJ31X Jack (2 required) <br /> <br />Communication <br />Formats: SIA, SK 3/1, Sescoa 3/1, Contact ID, <br />SK 4/2, Radlonlcs BFSK <br /> <br />Approvals: <br /> <br />UL Listed - UL864/NFPA 72 Central and Remote Supervising <br />Station Fire Alarm System Service. <br /> <br />FM Approved <br /> <br />CSFM Approved <br /> <br />MEA - New York City <br /> <br />ULC - Canada <br /> <br />Model 5230 Remote <br />Alphanumeric Annunciator <br /> <br />The 5104 can be programmed <br />through the use of the optional <br />Model 5230 Remote Alphanumeric <br />Annunciator. Programming options <br />include: <br />telephone numbers, reporting <br />format, account number, loop <br />response times (electronic retard), <br />test time, output activation, user <br />and installer codes. System <br />programming is stored in a non- <br />volatile EEPROM chip which is <br />reprogrammable hundreds of times. <br />The 5104 accommodates up to <br />three remote annunciators via a <br />four-wire connection. A quick- <br />connect plug allows temporary <br />connection of the annunciator for <br />programming. <br /> <br />The Model 5561 Downloading <br />Package <br /> <br />Allows for remote programming <br />and status checking of the 5104. <br />Includes a 3 1/2-inch disk and <br />Silent Knight proprietary modem, <br />Allows the installing company to <br />view the default programming, <br />modify it, and if necessary, <br />troubleshoot the system. Designed <br />to be used on an IBM or <br />compatible PC. The downloading <br />software also contains programs for <br />other Silent Knight downloadable <br />products. 5 1/4-inch disks available <br />upon request. <br />