<br />GENERAL NOTES <br /> <br />20, HiE FINAL CONNECnON AT ALL MOTORS OR MOTORIZED EQUiPMENT <br />SHALL BE MADE \111m A MINIMUM Of 12" OF LIQUID llGHT FLEXIBLE <br />CONDUIT VV1TH APPROVED GROUNDING MEANS. CONDUIT AND FITTINGS <br />SHALL CON~ORM TO THE ~OlLOWlNG: STEEL CONDUIT, ELBOWS, AND <br />COUPLINGS SHALL BE HOT DIPPED GAL VAN/ZED, CONFORM TO THE <br />LA rEST (ANSI) SPECIFICA 11 ON FOR STEEL CONDUIT, ZINC COATED, <br />AND SHALL BE PITTSBURGH, REPUBLIC, TRIANGLE, YOUNGSTOWN OR <br />APPROVED EQUAL. <br /> <br />21. BOXES AND FITTINGS SHALL BE STEEL CIT'(, APPLETON ELECTRIC, <br />RACO OR RUSSELL AND STOLL, GALVANIZED STEEL, CODE THICKNESS, <br />A MINIMUM OF 1-1/3" DEEP, AND OF SUFFICIENT SIZE TO <br />ACCOMMODATE THE DEVICES SHOWN ACCORDING TO NEC REQUIREMENTS. <br /> <br />22, ALL EQUIPMENT, NEW OR EXISTING, INSTALLED ABOVE A CEILING <br />USED AS A PLENUM FOR ENVIRONMENTAL AIR SHALL BE SO RATED <br />FOR THAT PURPOSE. NO OPEN CABLING OR PVC PLASTIC CONDUITS <br />SHALL BE INSTALLED IN THE PLENUM SPACE AS NOTED IN NEC #300-22. <br /> <br />23. WIRE AND CABLE SHALL BE OF COPPER VV1TH 98% CONDUCTIVITY AND <br />SHALL MEET THE STANDARD SPECIFICATIONS AND TESTS <br />EST ABUSHED FOR SUCH MATERIALS AND CONSTRUCTlON OF ASTM, <br />NEMA, UL, ANSI, AEIC AND IPECA, iM1ERE APPLICABLE MATERIAL <br />CONSTRUCTION DATA, INSULATION THICKNESS, JACK ET THICKNESS <br />TEST DATA, AND SAMPLE SHALL BE SUBMITTED FOR APPROVAL UPON <br />REQUEST. WIRE AND CABLE SHALL BE AS MANUFACTURED BY ANACONDA, <br />AMERICAN STEEL AND WIRE, GENERAL CABLE, GENERAL ELECTRIC, <br />OKONITt, PHELPS DODGE, REYNOLDS, SIMPLEX, TRIANGLE OR <br />APPROVED EQUAL. <br /> <br />WIRE FOR CENERAl INTERIOR BRANCH CIRCUIT USE <br />(#8 AWG AND SMALLER) SHALL BE TINNED, STRANDED, <br />ANNEALED COPPER, INSULATION SHALL BE A MQlSTURE <br />AND HEAT RESISTING THERMOPLASTIC MEETING UL <br />REQUIREMENTS FOR TYPE .THHN/THWN", 600 VOLT, 90 <br />DEGREES C, <br /> <br />WIRE FOR FEEDERS AND POWER EQUIPMENT (#6 AWG <br />AND LARGER) SHALL BE STRANDED COPPER; INSULATION <br />SHALL BE A MOISTURE AND HEAT RESISTANT CROSS-LINKED <br />SYNTHETlC POLYMER, MEE11NG UL REQUIREMENTS FOR <br />TYPE XHHW, 600 VOLT, 90 DEGREES C (DRY LOCA nONS), <br /> <br />FUSES FOR PROTECTION OF EQUIPMENT OTHER THAN <br />THOSE LISTED ABO\1: SHALL BE "FUSETRONS", <br /> <br />34. LOCAL WALL SWITCHES SHALL BE SPECIFICATION GRADE, 20 AMP, <br />120/277 VOLT, RATED NON-MERCURY "QUIETTE: TOGGLE SVvHCHES <br />WITH WHITE OPERATING HANDLES. SW1TCHES SHALL BE HUBBELL <br />#1211 SERIES, ARROW-HART, BRYANT, GENERAL ELECTRIC, OR <br />P & S FOR OPERATING ON 120 VOLT CIRCUITS. SI^.1TCHES SHALL <br />BE MOUNTED 4'_0. ABOVE TIiE FLOOR, <br /> <br />35, COVER PLATES AND RECEPTACLES FOR EXTmlOR OUTLETS <br />(~A THERPROOF TYPE) SHAll BE MOUN1ED HORILONTALL Y W1TH <br />DOUBLE LIFT CO\1:RS AND CAST ALUMINUM, BOX AND COVER PLATES <br />SHALL BE SIMILAR TO HUBBELL U5200 SER1ES OR OTHER APPROVED, <br />ALL EXTERIOR RECEPTACLES SHALL BE GFI CIRCUIT PROTECTED, <br /> <br />36. DIMENSION NEXT TO OUTLETS: INDICATE AFF (ABOVE FINISHED FLOOR) <br />ElEVA TION TO CENTER OR JUNC110N BOX, <br /> <br />37. LIGHTING FIXTURES SHALL BE Ul lISTtD. COMPLETE IN EVERY DETAIL. <br />INCLUDING PLASTER FRAMES WHERE REQUIRtD, PROPERLY WIRED AND <br />CONNECTED IMTH CONDUITS SUPPLYING SAME. ALL INCANDESCENT AND <br />HID FIXTURES SHALL BE PREWIRED, COORDINATE INSTALLA 11 ON OF <br />FIXTURES WITH CEILING TYPE CONSTRUCTION AND GRID LAYOUT, <br /> <br />~ .. .. I ~ c:.. I::1....U rr. ~:A f/ t:=D c::... <br />I--'-""" N:;:::jr v.....!:;'.::f ~l:':.'- t-'l'!>..r~,;..;J' <br />.. ~R rT....:'::JH-oI~ ~.J: J fT'(:.11 <C<::>" w- L.. .. . <br />: . ..~I':tl .. . .'r+lj\ t'\. .1,!.I~_ <br /> <br />40, NOTING IN THESE PLANS OR NOTES SHALL BE CONSTRUED <br />TO CREATE A CONDITION WHERE BY THE CONDUCTORS HAVE <br />A HIGHER MAXIMUM TEMPERAruRE RATING THAN THEIR <br />ASSOCIA TED TERMINA TlONS. <br />ALL CONDUCTORS AND TERMINATIONS SHALL HAVE A <br />90 DEGREE MAXIMUM TEMPERATURE RATING. <br /> <br />PROVIDE GFl BREAKERS AS NOTED AND AS REQUIRED. <br /> <br />PROVIDE GROUND BUS AS INDICATED IN PANEL SCHEDULE <br />AND/OR RISER DIAGRAMS, <br /> <br />IN GENERAL, ENCLOSURES SHALL BE NEMA 1 OR NEMA 12 <br />EXCEPT iM1ERE wtA THt.RPROOf SIM TCH IS REQUIRED. <br />ENCLOSURES SHALL BE NEMA 3R, <br /> <br />UNITS SHALL BE "GENERAL DUTY" TYPE AND SHALL BE <br />SIMILAR TO SQUARE 0 TYPE "GO" OR OTIlER APPROVED, <br /> <br />3.3. FUSES FOR THIS PROJECT SHALL 8E AS MANUFACTURED BY BUSSMAN <br />MANUFACTURING CO, CHASE-GOULD CO, OR RELIANCE FUSE, AND <br />SHALL BE Of THE SIZE AS INDICA TED ON mE DRA'MNGS OR AS <br />REQUIRED. COOROIN A TION AND VERIFICATION Of FINAL SIZING AND <br />INTERRUPTING CAPACITY OF FUSES SHALL BE THE RESPONSIBILITY <br />Of THE CON TRACTOR AT T11E COMPLETION OF THE PROJECT. ALL <br />FUSES FOR THIS PROJECT SHALL BE PRO'v1DED BY T11E CONTRACTOR <br />AND SHALL BE or ONE MANUFACTURER. <br /> <br />AUDIO SYSTEM-(fVr<t-J. f '~I~Tt'tl$t) r.>'(ThU'W.ff) <br /> <br />1. ELECTRICAL CONTRACTOR SHALL INSTALL IN SALES ROOM CEiliNG (AT <br />LOCA llONS SHOWN ON CEILING POWER PLAN) 8" ROUND SPEAKERS <br />(FURNISHED BY FASHION BUG). CONNECT SPEAKERS w/ 16 GUACE <br />SPEAKER WIRE (RUNS OVER 25 FEET), CRITERIA - (1) SPEAKER <br />/ 1000 SQ. FT, <br />SPEAKER W1RE SHALL TERMINA IT BELOW CEILING @ LOUNGE COUN lER, <br />w/ ADDITIONAL 8 FT. OF FEED WIRE FOR TENANT INSTALLATION OF <br />AUDIO SYSTEM. ( REFER TO A-l/E-1 FOR COUNTER LOCATION) <br /> <br />FUSES FOR PROTECTION OF ALL MOTOR CIRCUITS <br />SHALL BE DUAL ELEMENT, TIME DELAY TYPE, "LOW PEAK", <br /> <br />FUSES FOR PROTECTION OF CIRCUIT BREAKERS SHALL BE <br />F AS T ACTING "lIMI TROt~S": . <br /> <br />1 ALL ELECTRICAL WORK SHALL CONFORM WI fii LOCAL AND <br />STA TE ELECTRICAL CODES. OSHA AND THE LA TEST t~EC <br />SPECifiC A TIONS. <br /> <br />2, ALL ELECTRICAL LIGHT AND POWER WIRE SHALL NOT BE <br />SMALLER TIlAN #12 AWG COPPER WIRE. ALUMINUM CONDUCTORS <br />SHALL NOT BE PERIAITTED. ALL SERV1CE FEEDERS AND BRANCH <br />CIRCUIT CONDUCTORS SHALL HAVE 1YPE THHN (90'C) INSULA nON. <br />L1GHnNG F1XruRE WIRE INSULA DON SHALL HAVE A TEMP. RATlNG <br />Of NOT LESS THAN TI1E LIGHTING FIXTURE'S MANUFAC1\JRER <br />RECOMMENDED RATING, NON-METALlC CABLE IS NOT PERMITTED. <br />(IE. RO~EX) <br /> <br />J. ALL 'MRING IN EXPOSED AREAS SHALL BE IN CONDUI T' <br />BOTH ON WALLS AND THROUGH EXPOSED JOIS1S, ALUMINUM <br />CONDUIT IS NOT PERMITTED. ALL WIRING ABOVE DROPPED <br />CEILINGS, 'MilCH ARE usm AS A.C. RETURN AIR PLENUMS, SHALL <br />BE IN ELECTRICAL METAWC ruBING. ALL CONDUIT SHALL BE <br />SIZED IN ACCORDANCE 'Mlli THE LA TEST NEC TABLES, <br />MINIIJUM CONDUIT SIZES SHALL OE 3/4 INCH. EXCEPT FOR L1GHTltJG <br />FIXTURES TO FIXTURES I^.1RING AND LOW VOLTAGE CONTROL WIRING. <br /> <br />4. E.C. SHALL FURNISH AND INSTALL FOR WORK DESIGNATED HIS <br />RESPONSIBILITY ALL WIRE. W1REWA Y, CONDUIT, CONNECTIONS, <br />OUTLETS, ETC. NECESSARY TO ACHIEVE A COMPLETE ELECTRICAL <br />INST ALLA nON. WHERE A DEVICE IS REQUIRED BY CODE BUT NOT <br />SHO\AM, IT SHALL BE FURNISHED BY THE E. C. AS THOUGH FULLY <br />SliOWN AND SPECIfiED. <br /> <br />5. E.C, SHALL OBTAIN ROUGH-IN AND FINAL ELECTRICAL INSPEC11Ot~ <br />APPROVAL CER11FlCATES FOR ALL ELECTRICAL WORK AND COPIES <br />Of TIiE CERTIFleA TES SHALL BE IMMEDIA TEL Y FORWARDED TO <br />CHARMING SHOPPES, INC. A TTN: CONSTRUCTION DEPT. <br />INSPECT10NS SHALL BE MAOE BY INSPECTION AGENCY OR EQUAL. <br /> <br />6 OUTLETS IN SALES AREA TO BE AT 12" A.F.F HORIZONT All Y MOutHED <br />A T THE CENTERUNE Of EACH COLUMN LOCATION. <br /> <br />7 ALL MRING TO CARRY EQUIPMENT BOND. <br /> <br />a E.C. SHALL SUBMIT TO THE LL. A CERTIFICATE AND FINAL <br />iNSPEC110N FROM A LOCAL INSPECTlOt~ DEPT <br /> <br />9. PROVIDE A KEY SWITCH fOR EACH O.fi, MOTORIZED GRILLE AS NEEDED <br /> <br />10. PROVIDE A DEDICATED WATERPROOF CONVENIENCE OUTLET AT EACH <br />RllJ AS PER NEe (210-63) <br /> <br />11. E.C, TO SET TiME CLOCK TO THE HOURS BEf\VEEN 4: 00 PM TO 10: 00 PM. <br /> <br />24, STEP DOWN TRANSfORMERS SHALL BE EQUAL 10 CE OR y.{STINCHOUSE <br />500 VOLT CLASS "DRY TYPE" SINGLE OR TIlREE PHASE (PER PLAN) <br />CLASS "R" INSULATION WITH MULTIPLE TAPS ABOVE AND BELOW <br />RA TED VOLTAGE. <br /> <br />25, LIGHTING AND RECEPTACLE P ANELBOARDS SHALL BE CIRCUIT BREAKER <br />TYPE VV1TH DiERMAL MAGNETIC, TRIP FREE, TRIP INDICA nNG, <br />INVERSE TIME, MULTIPLE POLE. BREAKERS SHALL BE COMMON 1R1P <br />CIRCUIT BREAKERS, EQUIPPED WITH SILVER ALLOY CONTACTS AND <br />QUICK-MAKE, QUICK-BREAK MECHANISM, AND WITH INSULATEO SCREW <br />TERMINAL SOLID NEUTRAL BAR. PANELS TO HAVE MAiN BREAKERS <br />OR MAIN LUGS ONLY AS NOTED. <br /> <br />LIGHTING AND RECEPTACLE PANELS SHALL BE FLAT FRONT <br />AND TRIM UNITS EQUIPPED W1TH CONCEALED HINGED DOOR <br />AND TYPE'WRITTEN CIRCUIT DIRECTORIES <br /> <br />LIGHTING FIXTURES SHALL BE SECURELY SUPPOR1ED <br />AS REQUIRED. SUPPORTS SHALL BE BY mE ELECTRICAL <br />CONTRACTOR, SURFACE-MOUNTED OF SUSPENDED <br />FLUORESCENT LIGHTING FIXTlJRES SHALL HAVE A MINiMUM <br />OF TWO (2) SUPPORTS PER 4 FEET OF LENGTIl, <br /> <br />EXIT LIGHTS SHALL NOT BE SUPPOR1ED FROM THE <br />CElLlNG TILES. ALL RECESSED FLUORESCENT flXnJRES <br />TO HAVE SAfETY GRID CLIPS AS REQUIRED BY NEe 1981 <br />ARTICLE 410-16 PARAGRAPH (C), <br /> <br />VERIFY EXACT LOCA TION OF ALL CEILING MOUNTED <br />LIGHTING FIXTURES AND CEILING CONSTRUCTION W1TH <br />ARCHITECTURAL REFLECTED CEIUNG PLANS PRIOR TO <br />INST AlLA TlON. <br /> <br />ALL lIGHT1NG FlXruRES SHALL BE PANEL SWITCHED <br />UNLESS OTI1ERWISE INDICA TED ON TI1E PLANS OR DETAILS, <br /> <br />26. ALL ELECTRICAL WORK IN THE DEMISED PREMISES, UNLESS <br />OTHERWISE NOTED, INCLUDING, BUT NOT LIMITED TO, ALL <br />LIGHTING FIXTURES, SHALL BE OF A MANUFACTURER APPROVED <br />BY FASHION BUG'S CONSTRUCTION DEPARTMENTS PROVISIONS AND <br />INSTALLATION or ELECTRICAL PANELS, BREAKERS, WALL OUTLETS, <br />BOXES, POWER SYSTEM FEEDERS, EMPTY CONDUIT FOR COMMUNICATION <br />SYSTEMS WIRING, AND INSTALLATION OF UGHTING FlXTURES <br />SHALL BE BY THE ELECTRICAL CONTRACTOR, CONSULT PLANS AND <br />DETAILS FOR EXTENT OF WORK. ALL ELECTRICAL MATERIALS SHALL <br />BE NEW AND SHALL BE NA TlONAL ELECTRICAL CODE STANDARD, <br />UNLESS BETTER GRADE IS MENTIONED HEREiN, AND SHALL BEAR THE <br />UNDERWRITERS' LABORATORIES LABEl, <br /> <br />27, ELECTRICAL CONTRACTOR SHALL GUARANTEE AGAINST MECHANICAL AND <br />ELECTRICAL DEfECTS OF ANY OR ALL EQUIPMENT, MATERIALS <br />AND WORKMANSHIP COVERED BY THESE SPECIFICA noNS AND SHALL <br />MAKE GOOD, REPAIR, OR REPLACE AT HIS OWN EXPENSE. 'IY <br />DEFECTIVE EQUIPMENT, MA TERIAL, WORK OR PART WHICH MAY <br />SHOW ITSELF 'MTHIN A PERIOD OF ONE (1) YEAR AFTER FINAL <br />ACCEPTANCE Of WORK, <br /> <br />28. UPON COMPLETlON OF ELECTRICAL WORK, THE INSTALLA nON SHALL <br />BE ENTIRELY FREE FROM GROUNDS AND SHORT CIRCUITS. ALL <br />CIRCUITS SHALL BE GROUND OUT AND PROPERLY LABELED, ALL <br />CIRCUITS SHALL BE BALANCED ACROSS ALL PHASES--NEW AND/OR <br />EXISTING. <br /> <br />29. THE ELECTRICAL SYSTEMS GROUNDING AND GROUNDING ON <br />NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT <br />SHALL IN ALL INSTANCES CONFORM TO THE MINIMUM REQUIREMENTS <br />OF DiE LA TEST EDITION Of' TI1E NATIONAL ELECTRICAL CODE WITH <br />ADDITIONAL GROUNDING AS SHOWN ON THE DRAWlNGS AND AS <br />SPECIFIED HEREINAFTER, THE MINIMUM SIZE CONDUCTOR TO BE <br />USED FOR ELECTRICAL SYSTEM GROUNDING SHALL BE NO 6, <br />IMlERE CONDUIT IS USED FOR MECHANICAL PROTECTION OF A GROUNDING <br />CONDUCTOR, THE CONDUCTOR SHALL BE SECURELY BONDED TO THE <br />CONDUIT AT EACH END. CONSULT DRA\II1NGS FOR EXACT SIZE OF <br />GROUNDING CONDUCTORS AND/OR CONSULT NEC ARTICLE #250, TABLE <br />250- 94, <br /> <br />LIGHTING FIXTURE CHANNELS SHALL NOT BE UTIlIZED <br />AS A 'HIRING RACEWAY UNLESS CHANNELS ARE PROVIDED <br />AND LABELED FOR SUCH USE BY UL AND AS APPROVED BY NEC, <br /> <br />IN GENERAL, ALL RECESSED FIXTURES SHALL COMPLY <br />VV1n-1 ARTiClES #410-64. #41-66, #410-68 AND #410-73 <br />OF NEe REGARDING TEMPERA TURf, CLEARANCE, CONSTRUCTlON <br />AND INST ALLA nON. <br /> <br />ELECTRICAL CONTRACTOR SHALL UPDATE EXISTING AND/OR <br />INSTALL NEW NIGHT LIGHT CIRCUI1S, EXIT LIGHTS, AND <br />EMERGENCY LIGHTING AS I~EOUIRED TO COMPLY VV1TH THE <br />REQUIREMENTS Of STATE AN LOCAL CODES AND AUTHORITIES, <br /> <br />VERIFY 'lETfER COLOR", STYLE, SIZE AND SPACING OF <br />EXIT LIGHTS WITH LOCAL CODES PRIOR TO INSTALLATlON. <br /> <br />A T THE COMPLETION OF WORK. ALL FlXllJRES SHALL BE <br />CLEAN AND FREE OF FOREIGN MATERIALS AND DEBRIS, <br />REPLACE ALL BURNED OUT OR DEFECTIVE lAMPS, BALLASTS, <br />FUSES, LENSES, ETC, <br /> <br />38, TIME flOCKS (SW1TCHES) FOR CON1ROl Of SIGNS SHALL BE <br />SYNCHRONOUS MOTOR TYPE, MANUAL OVERRIDE SW1TCH, DAY <br />SKIPPER AND 24 HOUR DIAL. INTERfJATIC #T1471BR SERIES <br />OR OTHER APPROVED EQUAL. <br /> <br />12 ALL SUBTRADES SHALL COORDINATE THEIR WORK WITH WORK OF <br />OTI1ERS OR 'MTI~ EXISllNG CONDITIONS OCCURRING ABOVE OR <br />BELOW THE LEASED PREMISES AND SHALL MAKE CHANGES FROM <br />TilAE TO TIME AS REQUIRED TO ACCOMMODATE SUCH WORK OR CONDITIONS. <br /> <br />13 ALL NORK AND MA1ER1ALS SHALL CONFORM TO DiE REQUIREMENTS <br />Of' ALL FEDERAL, STATE' AND LOCAL LAWS, ORDINANCES, AND <br />REGULATIONS AS ~ll AS TliE RULES AND STANDARDS Of TIlE <br />NA llONAL BOARD OF FIRE, UNDER\~ITERS, THE NATIONAL <br />ELECTRICAL CODE, THE NEMA, AlEE, AND OSHA. <br /> <br />14 THE CONTRACTOR SHAU OBTA1N AND PAY FOR ALL PERMITS <br />AND CERTlflCAlt:S OF INSPECTION fOR WORK HEREIN SPECIFIED. <br />THE COST Of SUCH PERMITS AND CERTIFICATES SHALL BE INCLUDED <br />IN THE BID PROPOSAL. <br /> <br />15. ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND BUILDING <br />AND SHALL EXAMINE TO HIS/HER SATlSFACTlON ALL OF THE <br />PHYSICAL CONDtnONS THAT AFFECT THt CONTRACT PRICE, NOTING <br />THE lOCATION Of EXISnNG EQUIPMENT. NO ADDI110NS TO THE <br />CONTRACT PRICf WIll BE PERMITTED DUE TO IGNORANCE OF EXISnr~G <br />CONDITIONS. <br /> <br />16, ELECTRICAL CONlRACTOR SHALL ~RE COI.lPLETE ALL NEW SERVICE <br />S'MTCHES, EQUIPMENT PANELS, S'MTCHES, LIGHT FIXTURES, <br />DUPLEX OUTliTS. ETC. AS REQUIRED AND AS SHOI'iN. <br /> <br />17. SHOULD ANY OOESTlONS ARISE REGARDING OUTLET LOCA TION, <br />ACCESS DOOR REQUIREMENTS. ETC" CONTACT FASHION BUG, INC, <br />CONSTRUCTION DEPARTMENT. <br /> <br />18, It~ GENERAL, 'MRES SHAU BE RUN IN CORROSION RESISTANT, <br />TI-lREADED INTER~EOIATE' IJETAL CONDUIT (I.M.C.), OR ELECTRICAL <br />METALLIC T1JBING (E.!.t.T.), OR PRE-WtRED FLEXIBLE CONDUIT <br />(REFER NEe ARTICLE 333) UNLESS OTHERW1SE NOTED. <br /> <br />1\) !'!-<oVlor "lHLON" COATED I'l1RE, OR THINWALl UA T (ONOllIr <br />SlSl1 M fOR LOW VOLTAGE SYSTEMS, <br /> <br />30. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL TEMPORARY UGHTlriG AND <br />RECEPTACLES AS REQUIRED TO MEET OSHA REQUIREMENTS. <br /> <br />31. ALL CONTROl WIRING FOR HVAC SYSTEM SHALL BE BY THE HVAC <br />CONTRACTOR, <br /> <br />32, LIGHTING AND RECEPTACLE PANELS SHALL BE RATED IZO/20B VOLT, <br />.3 PHASE, 4 'MRE WITH MINIMUM RATED 10,000 Ale. BOLT-ON <br />BREAKERS, PANELBOARO SHALL BE NORMAL SIZE, 20. WIDE X 5-3/4" <br />DEEP WITH LOCKING DOORS AND VV1111 BUSSING AS SIZED ON ORAVV1NGS, <br />SIMILAR TO SQUARE D. TYPE "NOOB" OR Oll1ER APPROVED SAFETY <br />SVv1TCHES SHALL BE FUSIBLE OR NON-FUSIBLE TYPE AS INDICA TED <br />ON PLANS, UNITS SHALL BE QUICK-MAKE, QUICK-BREAK, SAfETY <br />INTERLOCK TYPE, SINGLE TI1ROW, SINGlE, f\VO OR THREE POLE, <br />250 VOlT RATING AS REQUIRED, AND 'MTH AMPERE AND/OR HORSEPOWER <br />RATINGS INDICATED OR REQUIRED FOR THE INSTALLATION AND AS <br />SHOYvN ON DRA'MNGS. <br /> <br />39, TI1E CIRCUIT USED TO POWER THE ELECTRIC CASH REGISTER (TERMINALS) <br />SHALL NOT BE USED FOR OTI-lER ELECTRO-MECHANICAL EQUIPMENT. <br />mE CIRCUITS SHALL NOT SHARE niE NEUTRAL UNE 'MTH OTHER <br />EQUIPMENT, SEPARA II POINER, NEUTRAL AND GROUND ~RES, 'MRE <br />SIZE SHALL BE N12 AWG AND SHALL BE RUN TO CIRCUIT BREAKER <br />BOX VV1111 GROUND W,RE TlED TO GROUND TERMINAL IN PANEL. <br />ISOlA TE GROUND WIRE AND BUS FROM NEU TRAL. DO NOT USE TI1lS <br />CONOUIT fOR GROUNDH~G AS THESE GROUNDS MAY NOT BE ADEQUATE AT <br />mE HIGH FREQUENCIES UTILIZED BY n-JE ELECTRIC CASH REGISTER, <br />THE PO'M:R LINES FOR THE ELECTRIC CASH REGISTE.RS, TELEPHONE AND <br />RECEPTACLE LOADS SHAll BE RUN SEPARATELY IN mE (.3) 3/4" CONDUITS <br />CONDUITS LOCATED AT EACH SALES DESK LOCA liON. <br /> <br />FASHION BUG <br />STORE NO. 3603 <br /> <br />"'j::o.i-_,! <br /> <br /> <br />~,""j(;fm~1IJ.~~" <br /> <br />.... 'ib~b <br />'U <br />.... <br /> ~4..lZ>1~ <br />.t:. MOJ <br />0 <br />0 04.02.2.004 <br />'U <br /> <br />en <br />CD <br />C <br />C <br />(J) <br /> < <br /> ;( <br /> r! <br /> 0 <br /> CI) <br /> .E <br /> - Q <br /> ~ ci <br /> ~ <br /> ~ <br /> ;S- <br /> ~:g ~~ <br /> UJ 0 <br /> J--~ <br /> ~~ <br /> Zl <br /> UJ..c: <br /> U~ <br /> Z <br /> 3= <br /> 0 <br /> J-- <br /> :c <br /> J-- <br /> ~ <br /> 0 <br /> Z <br /> . <br /> . <br />L:lJ ~~ <br />~~~ .. <br />gl <br />~ ~ <br />QCOg ~! <br />.c: co <br />,~ <br />LfZ= <br /> ... a 015 <br /> 0 'd <br />'53 0 cJd c~ <br />~ ,... <br /> c: 0 ~! <br />- ..... M <br />~ <br /> ~:Ci' <br /> 015 <br /> [V) .c: .......,. <br />Vl <( .~ l,i <br /> <u J: <br /> (/) " cD:- <br /> ro Vl ~2 <br />3JLJ...:") <br /> <br /> <br /> <br />1 <br />2 <br />3 .- <br />4 <br />SHEET <br /> -r-s <br />OF 8 <br />