<br />HVAC GENERAL NOTES
<br />
<br />t ALL WORK SHALL CQt\FORM TO THE REQUREMENTS Of THE
<br />ST MUARD MECHANCAL CODE, NA T10NAL ELECTRIC CODE, STATE
<br />Et-fRGy CODE, ALL t\f"PA REOOIn'ENTS 00 ALL lOCAl CODES.
<br />2. ALL WORK SHALL BE COOROINA TED WITH ARCHTECMAl, ClVl,
<br />STRUCTl,RAl, MECHANICAL At.[) ELECTRICAL DRAWNGS. CONTRACTOR
<br />SHALL BE REOURED TO ~ INSTALL MU C<UlECT WITH
<br />APPROPRlA TE SERVICES ALL ITEMS SHOWN ON 1lE ORA wm AT NO
<br />ADDITIONAL COST TO OWt-ER.
<br />3. REFER TO ARCHTEC1l.RAL PlANS FOR EXACT CELNG GRD N-f)
<br />DFFUSER LOCATIONS.
<br />4. PRIOR TO SUl3UTTING A 80, TliE CONTRACTOR SHALL HAVE STWED
<br />At() COM'ARED 1lE CONTRACT DOCUMENTS WITH EXlSTN1/PROPOSED
<br />Ca-.DlTlONS At() NOT LATER THAN TEN (10) DAYS PRIOR TO 11-E BD
<br />~ SHALL REPORT TO 1lE ENGNEER ANY ERROR, INCONSISTENCY,
<br />OR Ot.tSSlON IN THE CONTRACT DOCUMENTS.
<br />5. ALL DUCTWORK SHALL BE SEALED WITH A NON-HARDENING.
<br />NON-MGRA TING MASTIC OR LIQUD ELASTIC SEALANT. PROVDE
<br />HOT -DIPPED GAL VmZEO STEEL F ASTE~ ANCHORS, ROOS, STRAPS,
<br />TRIM AN) ANGLES FOR StPPORT OF DUCTWORK.
<br />6. F ABRlCA TE DUCT FITTNGS TO MATCH ADJOINNG DUCTS At() TO
<br />COM='L Y WITH DUCT REOUREtIENTS AS APPLICABlE TO FITTNGS. LMT
<br />ANGU..AR TAPERS TO 30 DEGREES FOR CONTRACrnG TAPERS At() 20
<br />DEGREES FOR EXPAN)NG TAPERS.
<br />7. PROVDE FLEXI3LE Cor.uCTION FROM EACH DUCTWORK COf'UCTION
<br />TO AR HANDLERS At() FANS.
<br />8. ALL DUCTS SHOWN ARE NSDE ClEAR DIMENSIONS.
<br />9. PROVDE ACCESS PANELS IN DUCTS FOR ACCESS TO VOlUME DM'PERS,
<br />FIRE DAMPERS, DUCT MOUNTED SMOKE DETECTORS, At() Wl-ERE
<br />REQUIRED FOR MAINTENANCE Cf" ALL FANS At() MECHANICAL
<br />EOUPMENT. PANELS SHALL HAVE A FIRE RATING EQUAL TO 11-E
<br />PENETRA TED ASSEMBLY (tvtNM.JM 1 HOUR). PROVDE FRE DMf'ERS AT
<br />ALL DUCT PENETRATIONS OF FREWALlS.
<br />10. NSLlA TE OUTSVE AR, EXHAUST, SUPPLY, AND RETURN DUCTWORK
<br />WITH NSU..ATlON. WHICH HAS A MtMJM R-VALUE OF 6. ALL
<br />DUCTWORK NSU..A TION. FlTrnGS, COVERS AN) FtB-ES SHALL HAVE
<br />A MAXMJM FLAME SPREAD RA rnG OF 25 At() A MAXMJM SMOKE
<br />DEVELOPED RATNG OF 50 At() ALL BE IN COM='LIANCE WITH NFPA 9OA.
<br />1t LOCATE ALL THERMOSTATS 50" ftFF LN..ESS OTHERWISE NOTED.
<br />EXACT LOCATION OF ALL THERMOSTATS SHALL BE APPROVED BY THE
<br />ARCHTECT AN) TI-E ENGINEER
<br />12. CONTRACTOR SHALL ClEAN ALL COLS AN) REPLACE ALL FL TERS
<br />At() BELTS AT SUBST ANTlAL COM'LETION.
<br />13. AR C~TIONING EOUFMENT SHALL BE AS SPEC FED. ARCHTECT
<br />AN) ENGt-EER WLL REVEW ANY SUBSTlTUOON FOR COWATI8LITY.
<br />14. DUCT SIZES At() EOOPMENT QPENt.lGS l1-fiU ROOFS. SLABS MU
<br />WALL PARTITIONS SHALL SUIT EOUAv€NT F~NSl-E:D. SEE SHOP
<br />DRAWNGS FOR EQUPMENT DIMENSIONS.
<br />15. PROVDE "p" TRAP AT AIR HMa.ER UNTS.
<br />
<br />~
<br />
<br />REFRIGERANT PIPING DETAIL
<br />
<br />N. T.S.
<br />
<br />ALL VMES SHALL BE SECIoft: 00 STABLE
<br />N NST ALLED OPERA TNG POSlTlON
<br />
<br />16. SLEEVE At() SEAL ALL PPNG PASSING 1ffiOUGH WALLS. FLOORS
<br />AN) ROOf LN..ESS NOTED OTI-ERWlSE.
<br />17. ROUTE COt-.vENSATE DRAIN PPNG AS SHOWN ON DRAWNGS IN..ESS
<br />NOTED OTHERWISE.
<br />18. ALL CUTTNG, PATCHt4G AN) REPAR WORK SHALL BE 11-E
<br />RESPONSIBLITY OF TI-E TRADE NVOL VED.
<br />19. Tl.RN OVER TO Owt-ER ALL EQlPMENT REMOVED. THS
<br />CONTRACTOR SHALL REMOVE EQlJPMENT NOT ACCEPT ABLE TO Owt-ER
<br />FROM JOB SITE.
<br />20. TI-E MECHANICAL CONTRACTOR SHALL PROVDE AM) NSTALL A
<br />SMOKE DETECTOR IN Tl-E SlPPl Y AN) RETURN AR STREAM OF ALL AR
<br />HAN:X..ERS WHICH HAVE A Slm.. Y AR QUANTITY N EXCESS OF 2,000 CfM
<br />OR SERVE AN AREA OF EGRESS. 11-E t..ECHANlCAL CONTRACTOR IS
<br />RESPONSI3lE FOR MOl.t-4TNG AM) WRING Cf" Tl-E SMOKE DETECTORS TO
<br />Tl-E AR HAN:>lERS.
<br />2t A COPY OF 11-E FINAL TEST AN) BALANCE REPORT, REVEWED AN)
<br />ACCEPTED BY Tl-E ENGt.EER Cf" RECORD SHALL BE MADE A V ALAEl..E AT
<br />11-E FINAL CONSTRUCTION SURVEY. NO FINAL INSPECTION OF HVAC
<br />CONSTRUCTION BY THE ENGt-EER OF RECORD WLL BE Cot-nJCTEO
<br />PRIOR TO RECEIPT AN) ACCEPTANCE OF A FINAL TEST At() BALANCE
<br />REPORT.
<br />22. THE MAXM.,t4 ALLOWABLE LEAKAGE FOR 11-E DUCTWORK IS 2 %.
<br />23. 11-E CONTRACTOR SHALL PROVIDE SHOP DRAWNGS AN)
<br />sum.tTTALS FOR HVAC EQUIPMENT AND DUCTWORK SHOWN ON 1lE
<br />PLANS AN) SPECFICA TIONS FOR THE ENGt-.EERS APPROVAL. THE
<br />ENCt.EER MAY REOURE TI-E CONTRACTOR TO REDO ANY WORK. WHCH
<br />WAS NOT APPROVED, OR TI-E ENCt-EER MAY REQUIRE A CREDIT TO THE
<br />OWNER. PROVDE A SET OF AS BUL TS AFTER THE JOB IS CotJPlETED.
<br />THS SET SHALL BE CONTNJOUSL Y UPOA TED DlJRt.lG CONSTRUCTION.
<br />24. PROVDE AR TURNNG VANES AT ALL 9O-DEGREE Raows. PROVDE
<br />VOlUME DMPERS AT EACH BRANCH TAKEOFF AS WICA TED N THE
<br />SMACNA "HV AC DUCT CONSTRUCTION ST At()ARDS'".
<br />25. PROVDE FL TER RACKS WHICH ARE ACCESSRE FOR MWTENANCE
<br />AM) SEALED AR "OO-IT.
<br />26. ROUND DUCT FITTNGS SHALL BE MAtU=' ACTURED BY LNTED,
<br />MCGLL, R. V. MOt-EY OR APPROVED EQUAL.
<br />27. CONTRACTOR SHALL NST ALL HV AC SYSTEMS AS REQUIRED BY THE
<br />MAtU=' ACTURER AN) ENGINEER TO INSlM QUET OPERA OON. NO
<br />lIDJE VIBRATION OR SOLN) SHAlL BE TRANSMTTED TO BUlDNG
<br />STRUCTURE At() OCCLPED AREAS. F Tl-E EQUPMENT NST ALLED HAS A
<br />HIGER SOlID PRESSURE LEVEL THAN TI-E EQUIPMENT SPECFED, THEN
<br />IT WLL BE THE CONTRACTORS AN) 11-E MANlf' ACTURES
<br />RESPONSIBUTY TO RIMNA TE ANY ADDITIONAL NOISE TRANSMISSION.
<br />28. 1lE MANJF ACTURER OF 1lE OX EOUFM::NT WlL BE RESPONSaE FOR
<br />THE SlZNG THE REFRIGERANT LINES AN) PROVDNG ALL REFRIGERANT
<br />ACCESSORES REQURED FOR PROPER OPERATION. IT IS 11-E
<br />MAMJF ACTURERS RESPONSBLITY TO SlU>Y 1lE PLANS At-V PROPOSED
<br />cotoTlON TO VERFY liS EQUIPMENT HAS THE CAPAOTY TO PROPERLY
<br />RETURN OL BACK TO THE COM>RESSORS.
<br />
<br />"'"
<br />"'"
<br />l
<br />l
<br />l
<br />l
<br />
<br />V.D.
<br />
<br />" ./
<br />III
<br />1:1
<br />III
<br />I
<br />
<br />TYPICAL ALL 8RANOi. -.
<br />SW-ffiANCH 00 ALL
<br />SN:U: DUCT T AI<E -a:FS
<br />TO GRLlES & REG.
<br />
<br />W~~
<br />
<br />V.D.
<br />
<br />".)/
<br />III
<br />1:1
<br />III
<br />I
<br />
<br />TYPICAL DUCT
<br />N. T.S.
<br />
<br />HANGER SlPPORTS: ~
<br />a'o.C. = 0-35" DUCTS "
<br />6'0.C. = 36-59" DUCTS
<br />
<br />HANGER STRAP: (, 22 GAGE
<br />...-.--- ~ 6' MAX. SPACf\G (TYPICAl)
<br />
<br />NOTES:
<br />
<br />SPN-N FITTNG: / ROlN) "SNAPlOCK" SKIT t-f:T AL
<br />Willi VC4J.M:: FOR ~TS GREATER 1liAN 6',
<br />::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::\: I DMffR ./ V Willi t' YIfV\P NSllA Tk)N
<br />~<:I" / ::::::' ~: \ TI - T - ,,~~:'ZED
<br />::::) SIZE~ u.u../ :.:.:. \ I J I "
<br />.......~ ......~ - -:EXRE c:, ~ \
<br />
<br />h~:':.:':':':':':':':-:.:':':':':':-:':':-:':':':-:':':':':.:.:.:.:.:.:-:.:.:-:.:.:.:-:.:-:.:.: NSllA TED, MAXMJM \ \ \
<br />~.........................................~. eI, 00 NOT SAG OR
<br />, ,
<br />L SAOO....E: 22 GAGE KN<
<br />
<br />t ALL REfRIGERANT PPf\lG SHAlL BE HARD Ca:>PER. TYPE 1."
<br />WIlli lONG RADUS ELBOWS.
<br />2 TRAPS SHALL BE SfoG..E PECE, WR<XJGHT COPPER.
<br />3. NSllATE SUCTk)N LNE Willi ~" ARMAflEX NSllATk:lN
<br />FLlL LENGTH 00 NOT SPLIT Mt-JG NSTALLATION. SEAL
<br />BUTT JONTS Willi ARMAFLEX SEALANT, 00 APPLY ARMAflEX
<br />PRESERVATIVE ON ALL NSllA Tk)N ABOVE ltE ROOF If.E
<br />PROVDE FIRE -RA TED ARMAflEX NSllA Tk)N N ALL RETI.ffl
<br />AR PlEN.J.4S.
<br />4. ROUTNG OFF ALL REfRIGERANT PFNG SHAlL BE PllM3. 00
<br />SHAlL ~ TRU:: Willi Tl-E BULONe L~S. .-mlONT AL RI...NS
<br />OF SUCTlON L~S OVER 2S' SHALL BE PlTa-ED -ot-l: -fiAlF"
<br />BWBLE TOWARD 1lE cotvf>RE5SOO, m OL REnRi
<br />SlPPCRT OF ALL PANG AT COWREssm5, CotaNSERS, 00
<br />AR HAt-I)U.JG LNTS SHALL BE AS SHOWN ABOVE. Sl..PPmT
<br />OF PPNG N BETWEEN ltE LNTS SHALL BE WIlli STRAP
<br />MA TERlAL, USNG ARMAFlEX NSllA TlON AS SADDlES. NO
<br />~TAL TO t-f:TAL CONTACT.
<br />6. awa FL TER-nRER COOES AFTER 30 DAYS OF <HRA OON.
<br />
<br />~
<br />~~
<br />
<br />.....
<br />~:7
<br />~.
<br />
<br />IIr'-"--
<br />
<br />5.
<br />
<br />"CElf\G DfFU$ER
<br />
<br />WRAP NSllA TION ABOVE
<br />CElNG DFFUSER
<br />
<br />DUCT DETAIL
<br />N.T.s.
<br />
<br />RPT
<br />
<br />NOTE:
<br />t HANGER ~TS SHAll BE AS NOTED }.OOVE F<R OOCTS lP TO 24., AN.) WITH TRAPEZE Jwa:RS F<R OOCTS
<br />25- AN.) ABOVE.
<br />2 <X=FSETS SHAll NOT EXCEED .30 DEGREE ANGlE, laW SHAlL NOT REOOCE 1lE FREE f.Rf.A <X= 1lE OOCT.
<br />3. TRANSlOONS SHAll NOT EXCEED tJ RAID (4- TRANSlmN PER FOOT SNGlE soo) TRANSlT"'0-4. laW 8" PER
<br />FOOT OOl8..E SOO) TRANSlTK)4~
<br />4. RECT AN<U.AR BRANCH cot-.N:C~ SHAll BE 45 DEGREE ENTRY TYPE. WITH ~T Ii. SLEEVE &c a.N:H LOCK
<br />CaH:C'BJN. ENTRY lENGlli SHAll BE 25% ~ 8RANCH OOCT WDlli.
<br />5. ROlN) ffiANCH OOCT ~C~ SHAlL BE WITH "FlEXMASTER" FLOE SPN-N FITTNGS.
<br />Willi SCOCP, DAt.JlER AN.) J.W.IX..E.
<br />6. FLEXRE ROlN) OOCT SHAll t.OJ..re I-flIX COl FLEXRE OOCOO, A 1-1/2" ElI..AN<ET
<br />NSU.ATK)4 Willi t-N.W 6.0 R VAl~ laW A AlWNJ.f FOL ooTER V~ ~ laW BE Ll-181 APPROVED,
<br />25 <R LESS FLME SPREAD laW 50 OR LESS SMOKE OEVUCflED. EQUAl TO "FLEXMASTER" TYPE 3M.
<br />
<br />V MES SHALL BE SECWlEY
<br />FASTThEO TO~.
<br />
<br />MN. 24
<br />Go.
<br />VNES
<br />
<br />I
<br />
<br />~:~~ I
<br />Y/l~' ~ 31/4"
<br />, 0 "<V) \\LJ
<br />~ ~
<br />\ --2 1/4"----2 1/4"--- /
<br />> I ~/
<br />~ I ~\\."
<br />~~; 1)4"R'lJf'
<br />\ \ 4 1/2"R /
<br />
<br />MN. 26
<br />Go.
<br />VNE.S
<br />
<br />_I-..
<br />
<br />450 I 450
<br />
<br />22 Go. ~
<br />
<br />. MAXU..\4 ~TRED
<br />V ftJ-E. LOOlli
<br />SMALL DOUBLE
<br />V~ 60 0
<br />lARGE DOUa.E
<br />Tv ftJ-E. 72 0
<br />
<br />NSTALL VNE.S N SECTIONS
<br />· OR USE TE RODS TO
<br />1 lldT ltE lH3AO<ED
<br />--L- V~ LENGTH
<br />
<br />~
<br />~
<br />
<br />SCREW EVERY
<br />6 TH V ftJ-E.
<br />
<br />Q:~
<br />~
<br />
<br />AR FLOW _ _ 3::
<br />
<br />r:AR TIGHT GASKET TO
<br />RUN ARO(,N) EDGE OF
<br />\ ACCESS PANEL
<br />\ rf"' .---:;:;~CAM LATCH
<br />~~
<br />Q.1f X ~~ -~
<br />1// " I
<br />IL___~
<br />
<br />, ^
<br />~
<br />
<br />DUCT OPENING
<br />
<br />MAlE TYPE DRAN P<RT
<br />TIf<EAm) CJP
<br />(ClEAN ooT)
<br />
<br />sa. T, SCREW, OR -
<br />WElD TO DUCT
<br />
<br />OO'a.'NSATE SIZE EWAL
<br />TO FtlL SIZE rF 00. ~4j
<br />SUFE TO oo.N. ~ 1/8-:f)
<br />
<br />. NSU..A TE PFE & TRAP Willi 3/4"
<br />ARMAFLEX (TYPCAI..)
<br />
<br />I". ~ I". ~J --
<br />L./ J L./ -./
<br />
<br />c
<br />
<br />T
<br />
<br />4 1/2"
<br />OR
<br />7"
<br />
<br />DUCT SIZE
<br />
<br />ACCESS PANEL
<br />SIZE
<br />1010 W X (DM'PER DEPTH-2") D
<br />1210 W X (DMPER DEPTH-2j 0
<br />1810 W X (DM'PER DEPTH-2j 0
<br />
<br />TURNING VANES
<br />
<br />N. T.S.
<br />
<br />ACCESS PANEL SIZE SCHEDU.E
<br />
<br />610 TO 15"
<br />15" TO 2(
<br />
<br />21' AN) ABOVE
<br />
<br />~
<br />- r--
<br />1 1/t'
<br />
<br />ALL OTI-ER ACCESS PANELS TO BE A MNMUM OF 15" x 15" 'M-ERE DUCT SIZE
<br />ALLOWS. USE FOUR CAM LATa-ES ON PANELS LARGER THAN 18" X 1810 SIZE.
<br />
<br />ENERGY RECOVERY VENTILATOR
<br />
<br />SPLIT SYSTEM UNIT SCHEDULE
<br />
<br />DESIGN C()t.I)ITIONS
<br />SlM.4ER: OO~ 93 DB, 79 we
<br />NXX>RS 76 DB, 50 m-t
<br />
<br />WNTER: OOTOOORS 36 DB
<br />NXX>RS 70 DB
<br />
<br />NOTES:
<br />t TRAP C~TE DRAN AT LNT (FLlL SIZE OF Cf'ENNG) MN. 2" WATER SEAL 00
<br />EXTOO AS SHOWN.
<br />2. ~T C()t{)ENSW LNT ON PITa-! ROO=' c;l.m.
<br />3 ALL LNTS SHALL BE SU'PlED Willi COWlETE TEM'ERA 1WE CONTROLS 00
<br />. AUTOMATe CHANGEOVER.
<br />4. ALL CAPAOTES AT AR.l CQt.011ONS.
<br />5. ElECTRICAL STARTERS ARE TO BE PROVOED BY Tl-E MECHANICAL CONTRACTOR
<br />N ACCOOOANCE WITH I)VJSI()N 16 00 NSTALlED BY Tl-E ElECTRICAL CONTRACTOR.
<br />6. PROVDE SEACOST CONSTRUCTION. ALL EXTERIOR Sl.HACES SHALL BE COATED
<br />00 SHALL tvlET OR EXCEED 3600 HOUR SALT SPRAY TEST PER ASm Bm 97.
<br />7. PROVDE Willi WEC 7.5 !-EATER 00 AtEOO1) PRtMRY HORIZONTAL DRAN PAN.
<br />
<br />LNT M.U3ER
<br />
<br />ERV-1
<br />
<br />\ L
<br />\ /
<br />\ /
<br />\ /
<br />\ /
<br />\ /
<br />\ 1
<br />V
<br />1\
<br />/ \
<br />/ \
<br />/ \
<br />/ \
<br />/ \
<br />1 \
<br />/ \
<br />
<br />AR HAN:l.ER
<br />TONS
<br />AREA SERVED
<br />
<br />EV AKF.A TOR:
<br />TOTAL CAPAOTY
<br />SENSI3lE CN>AOTY
<br />SLPPl Y
<br />OUTSVE AR
<br />EXT. STATIC PRE~
<br />MOTOR
<br />ElECTRIC
<br />ENTERNG AR
<br />LEA VNG AR
<br />ElECTRIC ~A T
<br />ElECTRIC
<br />MeA I MOCP
<br />WEGiT
<br />MM\.F ACTlHR
<br />MOClEl
<br />
<br />OO'VENSNG LNT:
<br />SEER/Ern
<br />ElECTRIC
<br />MCA/WlXP
<br />WEIGHT
<br />MAN.f'AC~
<br />MOCn
<br />
<br />/7 ~ t
<br />\ '/~ ~:\
<br />'K '~ 2 1/8"
<br />rt~ ~ ~~
<br />e\ ~va---'~ 1~- ~ I
<br />.... /
<br />
<br />~ ~x
<br />e gj/fR 0/
<br />\ 2"R /
<br />450145 V
<br />
<br />Rt..N-.ER TYPES
<br />
<br />STAPLE 2- flANGE llI:N
<br />TAPE OVER Tl-E ..lOtH 00
<br />STAPLE TO PROVDE
<br />VAPm-TGiT SEAL
<br />
<br />CFM
<br />IN. Hi>
<br />CFM
<br />IN. Hi>
<br />
<br />EXHAUST/OA
<br />650
<br />0.5
<br />550
<br />0.5
<br />73.0
<br />87.S
<br />1/3
<br />1/3
<br />20.9/25
<br />115/1/60
<br />OOP
<br />1625
<br />GREm-ECK
<br />MNV-750
<br />1.2.3.4.5.6.7.8
<br />
<br />::::.
<br />
<br />SE:R\n:
<br />OO~ V<X..LU::
<br />EXT. STATe PREss.
<br />EXHAUST V<X..lA€
<br />EXHAUST SP
<br />su:>PL Y EFF.
<br />EXHAUST EFF.
<br />OOTDOOR SIZE
<br />EXHAUST SIZE
<br />tIl;A/JItXP
<br />VOLTAGE
<br />ENCLO~
<br />SPEED
<br />MAtU' ACTLRER
<br />MODEL
<br />NOTES
<br />NOTES:
<br />t PROVDE WITH DUCT FLANGE.
<br />2. PROVDE WITH AIR INTAKE DMPER, MOTOOZED WD-220.
<br />3. PROVDE WITH EXHAUST AR NT AKE DAtftR, MOTORIZED WD-220.
<br />4. PROVDE WITH DOUBlE WALL CONSTRUCTION. 20 GA. GALVANZED
<br />NTERIOR LNER.
<br />5. PROVDE WITH REMOTE PANEL W/U/E. ClOCK.
<br />6. PROIVOE WITH OUTDOOR/EXHAUST AR FL TER, ( PlEA TED
<br />(30% EFFICENT).
<br />7. PROVDE WITH SOlD STATE SPEED CONTROlLER MOUNTED ON
<br />EXTERIOR OF FAN HOUSING. TO BE USED N SETTING PROPER
<br />CfM NOT AS AN ON/OFF SWITCH.
<br />8. NTERlOCK WITH RESPECTIVE AR HANDLER/S FOR AUTOMATIC
<br />ON/OFF OPERATION WITH AN HMClERS OPERATION.
<br />
<br />If>
<br />If>
<br />Mf>S
<br />V/tlHZ
<br />
<br />RPM
<br />
<br />OUTSIDE AIR CALCULATION
<br />FOR ASHRAE 62-89
<br />
<br />MJMBER OF PEOPLE (DESIGN) 86
<br />CfM PER PERSON REOURED 15
<br />[)(vERSlTY FACTOR (%) 50%
<br />TOTAL CFM OUTSDE AR REQURED 645
<br />. TOTAL CfM EXHAUST AR REOUREO 550
<br />SPECFED OOTSDE AR CFM 650
<br />
<br />AIR DEVICE SCHEDULE
<br />
<br />MARK TYPE
<br />
<br />MATERIAl FNSH MAtU' AC~ & MOOO.
<br />AlLM WHTE 0tA.,t
<br />ALLM WHTE TITUS 5a='
<br />
<br />OOTES
<br />1.2.3
<br />1.2.3
<br />
<br />/JD-1 CELNG
<br />/JD-2 EXH/RET /TRANS
<br />OOTES:
<br />1. NOISE CRITERIA NOT TO EXCEED 25.
<br />2. C~TRACTOR TO COOODNATE BORDER Willi CELf\G TYPE (LAY-N m PlASTER).
<br />3. REFER TO flOOR PlAN FOR CfM.
<br />4. AlL AR DEV(:ES ARE 4 WAY TffiOW, IN.ESS NOTED OTI-ERWISE ~ DRAWNG.
<br />5. PROVDE Willi ROlW TO SQUARE ADAPTER.
<br />ACCESSffiES:
<br />1. ALL AR DEVICES TO BE SlPPlED Willi O.BD.
<br />
<br />CUT NSllA Tk)N TO PROPER
<br />LENGlli TO A VOO COMJRESSlON
<br />OF NSllA TlON
<br />
<br />./ ""'" , FI3ER GLASS DUCT WRAP WITH A FACTORY
<br />./, APPlED FOL -SKRIM-KRAFT VAPOR BARRER.
<br />./ ./ , ...... WITH APERto.EANCE OF .02 OR LESS. MNMJM
<br />J< _ :: NST ALLED "R" V ALLIE OF 6. NSULA TION
<br />I .................. ~ MUST BE STORED AN) INSTALLED DRY.
<br />I '.. ~ /
<br />" (~'- IXJCT
<br />"~~:!~ '/ NOTE:
<br />
<br />-- "- SECIoft: NSLlA TOO Willi
<br />......... WEl.DED STICK PNS ON
<br />DUCTWORK 24" 00 LARGER
<br />
<br />SEAL ALL SEAMS
<br />WITH HARDCAST
<br />
<br />TYPICAL DUCT WRAPPING DETAIL
<br />
<br />N.T.S.
<br />
<br />DRAN PAN
<br />
<br />SlANT mAN PAN TOWARDS
<br />/ 1lE DRAN PORT
<br />/' r FLOAT COOTRCt SHJT-oFF
<br />-t. V N.. VE (SHJT LNT OfF N
<br />r ! I OVERFlOW CONlTOOS).
<br />LJ 1- OO'VENSA TE mAN PAN - t'
<br />HGH X t' lARGER 1l-tAN 00.
<br />PAN SHAlL BE 18 GA GN..V.
<br />St-EET. ~ mAcro AS
<br />SEAMS SHAlL BE ~.
<br />
<br />r
<br />
<br />II]
<br />
<br />FL. I
<br />
<br />LtKH
<br />
<br />I < II
<br />
<br />~
<br />t FOR OOAW llR.J LNTS Willi A TOTAL STATe PRE~ OF
<br />2 NOt:S OR LEss. A=t5" AND B=3".
<br />2 FOR ~W llR.J LNTS Willi A TOTAL STATIC PRESSI.n: Cf"
<br />3 NOt:S OR LESS. A=2- 00 B=4".
<br />3. FOR BlOW 1ffiU LNTS Willi A TOTAL STATIC PRE~ OF
<br />2 NOES OR LESS. A=3" 00 B=(.
<br />4. FOR BlOW 1ffiU LNTS Willi A TOTAL STATIC PRE~ OF
<br />3 NOt:S m LEss. A=4- 00 8=(.
<br />S. ELEVATE LNT AS REQ..ftO TO PROVDE TRAP t-miT laW
<br />PROPER OONAGE.
<br />6. llfRE SlW.L NOT BE 00 ST,6U)NG WATER.
<br />7. INSlLA TE PPE & TRAP WITH '4" ARMAfLEX WJ-ERE ltE PPE
<br />IS ~ WI~ ltE I3UlDNG OR WJ-ERE Ca<<NSA TlON MAY
<br />CAUSE DAMAGE.
<br />
<br />ACCESS PANEL DETAIL
<br />
<br />CONDENSATE P-TRAP DETAIL
<br />
<br />N. T.$.
<br />
<br />ACCESS
<br />
<br />N. T.S.
<br />
<br />,
<br />,
<br />
<br />AH-1
<br />3.5
<br />
<br />AH-2
<br />3.5
<br />
<br />J
<br />J
<br />I
<br />
<br />tBi 4004
<br />tBi 32.0
<br />CFM 1400
<br />CfM 325
<br />N. Hi> 1
<br />If> 1
<br />V / tfHZ 230/1/60
<br />DB/WB 7.5/63
<br />DB/WB 54/53
<br />
<br />KW ISTEP 7/1
<br />V/./HZ "l.30/1/60
<br />AMPS -
<br />LBS. 160
<br />- IDAPST AR
<br />- FCP4200A
<br />
<br />\
<br />\
<br />\
<br />\
<br />\
<br />\
<br />\
<br />
<br />J
<br />
<br />38.9
<br />30.9
<br />1300
<br />325
<br />1
<br />1
<br />230/1/60
<br />75/63
<br />53/52
<br />7/1
<br />l230/1/60
<br />
<br />\
<br />I
<br />
<br />I-
<br />
<br />, \
<br />
<br />160
<br />TaPST AR
<br />FCP4200A
<br />
<br />J
<br />
<br />,
<br />
<br />J
<br />J
<br />I
<br />
<br />J
<br />I
<br />
<br />\
<br />\
<br />\
<br />\
<br />\
<br />\
<br />
<br />ClJ-1
<br />
<br />n.5
<br />V / ./HZ 230/1/60
<br />Mf>S -
<br />LBS. 260
<br />- TEJvPST AR
<br />- NAC042AKA
<br />
<br />CU-1
<br />10.5
<br />230/1/60
<br />
<br />260
<br />TaPST AR
<br />NAC042AKA
<br />
<br />HV AC LEGEND
<br />
<br />UP DOWN
<br />
<br />~~
<br />
<br />UP DOWN
<br />
<br />Fj3Fj3
<br />~[2J
<br />SLm.. Y REnm/
<br />TRANSFER
<br />
<br />Slm.. Y AR DUCT (lP & DOWN)
<br />
<br />RE~ AR OOCT (lP & DOWN)
<br />
<br />CELNG DfFUSER
<br />
<br />~
<br />~
<br />p
<br />~
<br />~
<br />~
<br />f +
<br />
<br />flEX CctHCTOO
<br />
<br />VCltM: DMflER N DUCTWORK
<br />
<br />90- ElBOW WITH ~ VMf:S
<br />DUCT TRANSITION
<br />
<br />DUCT TRANSITION
<br />
<br />RECT ANGLlAR TO ROlW TRANSlTK)4
<br />~ DUCT WORK
<br />
<br />C}I
<br />(f)
<br />
<br />ElECTRCAl DlSCQ'.H:CT
<br />
<br />1lf1M)ST A T
<br />
<br />~
<br />
<br />RE~ AR PATH
<br />
<br />Mj-1 ·
<br />100 CfM ·
<br />aX8 NK ..
<br />
<br />AR DEVK:E IDTFICA 1lON
<br />AR~T
<br />AR DEVICE t-lCl( SIZE
<br />
<br />\ .,~,~
<br />y date 05-29-02
<br />~)~ bes~ grin~r ~~.~ lass piate~
<br />~ \._j!f~ n..:. \ L'~ W
<br />- (T ,,~C.l~' Jlin avei . ft' 0,1 t ~ed NP
<br />- ~- ~. ~~ J ~"\L._~ -_\
<br />~ ~ pe ..ni~ 0 ~ ~
<br />~ ~~ ~ (1~ ,m ~ ~~ revised
<br />O"~ ~ flU ('(27)-3 l~:;M Job no. 02054
<br />
<br />VlI
<br />F I
<br />U~
<br />Ude
<br />C
<br />Is
<br />U~
<br />~~
<br />~
<br />
<br />o
<br />"0
<br />V) "S
<br />'- ~ G:
<br />~ ~
<br />~t
<br />~:
<br />
<br />(I)
<br />
<br />:em
<br />U:!
<br />t:::=:lI ~
<br />(.LJ
<br />
<br />~~
<br />S2l
<br />6~
<br />~~
<br />
<br />&I
<br />
<br />,..
<br />~
<br />~
<br />~
<br />o
<br />::J
<br />
<br />CD
<br />~
<br />~
<br />U
<br />
<br />~
<br />~
<br />I
<br />ct:
<br />>-
<br />I
<br />CL
<br />W
<br />N
<br />
<br />(f)
<br />-.J
<br />-.J
<br />:r:
<br />a:::
<br />>-
<br />:r:
<br />0...
<br />W
<br />N
<br />
<br />PROJECT NO.: 0153
<br />
<br />DATE: 08/25/02
<br />DRAWN BY: DJD /TTM
<br />REVISIONS:
<br />
<br />SHEET TITLE:
<br />
<br />SCHEDULES &
<br />DET AILS
<br />
<br />SHEET NO.:
<br />
<br />M-2
<br />
<br />OF SHEETS
<br />
|