My WebLink
|
Help
|
About
|
Sign Out
Browse
Search
07-6953
Zephyrhills
>
Building Department
>
Permits
>
2007
>
07-6953
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
3/6/2009 4:33:32 PM
Creation date
1/10/2008 11:01:51 AM
Metadata
Fields
Template:
Building Department
Building Department - Doc Type
Permit
Permit #
07-6953
Building Department - Name
ZEPHYR PALMS
Address
4645 AIRPORT RD
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
31
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
<br />Multiplex Photoelectric Smoke Detectors <br /> <br />07050 Series <br />Specifications <br /> <br />Features <br /> <br />. Connects 10 a two-wire Mutliplex Bus <br />. Superior Dust Invnunity <br />. Exclusive Chamber Check Self Diagnostics <br />. Automatic Sensitivity Test Features <br />. 135"F (57"C) Heat Sensor (D7050TH) <br />. Easy Disassembly for Cleaning <br />. 07050 and D7050TH Require a D7050-B6 Base <br />. D7050DH Requires a 0343 Duct Smoke Detector Housing <br />. UL, ULC, CSFM UstecI <br /> <br />Description <br /> <br />The 07050 and D7050TH are low profile, Multiplexing, <br />Pholoelectric System type smoke detectors for the 07024 <br />Series Fire Alarm Control/Communicalors using a 07039 <br />Multiplex Expansion Module. The D7050DH is designed for <br />use with the 0343 Duct Smoke Detector Housing. The pa1ented <br />chamber design provides superior inmunity 10 false alanns <br />caused by dust. The detector is designed for use with <br />commercial and household fire warning systems. An LED <br />indicalDr flashes 10 verify that the detector has power and the <br />smoke sampling circuitry is fu1ctioning. <br /> <br />Vllhen property installed using the D7050-B6 base or the D343 <br />Smoke Detector Housing, tamper protection is provided by <br />multiplex wiring. This causes the control panel to initiate a <br />trouble signal when a detector is removed from its base. <br /> <br />Application <br /> <br />The 07050 Series smoke detectors are intended for de1ection <br />circuils inslalled in areas where personnel are present Heat <br />detectors are appropriate for circuits that supervise property. <br />The 07050 Series Pho1DeIec:tric Smoke Det8clDrs are designed <br />lD delect large smoke particles. <br />The D7050TH whidl has an added fixed temperature sensor, <br />expands the detector application 10 confined areas where a <br />fire increases air temperature slowly and where there is a <br />substantial inaease in air 18mperatlJre before the fire breaks <br />confinement, such as furnace rooms, closets, and other <br />confined areas. <br />The D7050DH Pho1DeIec.iric Smoke Detector is designed 10 <br />detect smoke particles in air duels when used with the 0343 <br />Duct Smoke Detector Housing. <br /> <br /> <br />07050 Series Smoke Detectors <br />Installation <br /> <br />Radionics smoke and heat detectors are compound devices. <br />The detec:for base installs over a back box and contains all the <br />wiring. The detBdDr head attaches lD the base by aligning theahead with the base and tuming it clockwise. No tools are <br />requinld for installation other than the hex key used lD tighten <br />the ~ screw. <br />InstaU, test and maintain these devices according lD their <br />Installation Guides, NFPA 72, Local Codes and the Authority <br />Having Jwisdiction. Failure 10 follow these procedures may <br />result in faiur8 of the device 10 operate properly. Radionics is <br />not responsible for devices that are irT1)fOperty installed, tested <br />and maintained. <br /> <br />07050-86 Multiplex Smoke Detector <br />Base <br /> <br />The D7~B6 Smoke De1Bc1Dr Base is designed for use with <br />the 07050 and D7050TH Multiplex Photoelectric Smoke <br />DetecloIs. This easy-4D-insta1l base can be attached to single <br />gang or 3.5 in. octagonal box, surface mounted, or mounted <br />to a 4 in. square electrical gang box using the supplied adaptor <br />plate. <br /> <br />Features <br /> <br />. Easy lD instaU <br />. Compact low profile design <br />. Stainless steel contacts <br /> <br />".,-~ <br />" <br /> <br />..,.... <br />,.~.I~ <br /> <br />~.,.. <br />~'.....,.~.'" <br /> <br />$ radionics <br /> <br />A member of the <br />Bosch Group <br />
The URL can be used to link to this page
Your browser does not support the video tag.