Laserfiche WebLink
<br />Zephyrhills Fire Rescue <br />6907 Dairy Road, ZephyrhilIs, FL 33542 <br /> <br />Fire Marshal <br />Kerry Barnett <br /> <br />Bus (813) 780-0041 <br />Fax (813) 780-0044 <br /> <br />July 27,2007 <br /> <br />Plan Review Comments <br /> <br />I have reviewed and disapproved the plans for a gas line installation located at 7050 Gall <br />Blvd. (Florida Hospital) for a kitchen range and fryer. My comments have been placed <br />below. Please contact me if you have any questions with regards to my comments. <br /> <br />1. Drawing is not ledge able. Drawing shall be schematic/architectural in nature <br />showing all connections, anchoring locations, pipe size and type, etc... <br />2. No mention of this being a propane or natural gas installation. <br />3. Details and specs shall be submitted with drawing on gas valve, LP tank (if one), <br />gas appliances and all other components, along with a scope of work. <br />4. Ballard protection shall be needed if it is in a vehicular area or an area that has <br />lawn mowing taking place. <br />5. To ensure correct operation of other systems (exhaust hood, suppression system) a <br />letter shall be submitted to verify that the suppression system in the hood is <br />compliant with the gas range and stove and a test and balance is with in normal <br />limits for the kitchen exhaust hood. <br />6. A carbon monoxide detector shall be installed in the kitchen area for the gas <br />installation. <br /> <br />\" <br />~WO:i\ <br />. .,','J'\" ...,' \ ,. r\b(Jo~ <br />u, ,\\,s",,, '.\ (,.:\'0\'( ~ \,0.1)...' <br />vt.. rl'I1h\V'c ~\O~ll".:\\\s <br />t"'e ,;\tt' ,,-.,\,,1\\'. '\\\~h" <br />~J1.: \>1;~.,.. 'I ~ ; ;; .;:"':o),~ -' <br />'f{e;,." ..'", <br />\,\Ol\oa \ ~\Y:" .<-. <br />_r'cr,\ 1\ <br />Nt'Vn. <br /> <br /> <br />