Laserfiche WebLink
<br />Zephyrhills Fire Rescue <br />6907 Dairy Road, Zephyrhills, FI 33542 <br /> <br />Fire .\farshal <br />Ker-:;! Barnett <br /> <br />Bus 313 78l:-,.~C4 <br />Fax 813'1 730-,:;C'44 <br /> <br />Plan Review Comments <br /> <br />I have reviewed the plans for the hood/duct system at Pinchasers (6816 Gall) and my <br />comments have been placed below. Please contact me ifthere are any questions with <br />regards to my comments. <br /> <br />1. Install grease cup on up-blast fan. <br />2. Up-blast fan shall be hinged. <br />3. Protection shall be provided on wall from bottom of hood to floor. <br />4. Hood and duct shall meet all required clearances. <br />5. Access panels shall be provided if duct changes direction. <br />6. If duct passes through any fIre rating the duct itself shall be enclosed with a fIre <br />rated enclosure. <br />7. If no fire barrier, duct shall be wrapped in a fire rated batt material. <br />8. System shall comply with the applicable code ofNFP A 96. <br /> <br />Inspections required: <br /> <br />1. Light test on hood and duct. <br />2. Test and balance required for the room of operation ( can be provided on <br />suppression final). <br />