Laserfiche WebLink
<br />ZephyrhiHs Fire Rescue <br />S90~ Dai:r?~-=ad. Zcphyrhills. PI .3.3 :5..:.': <br /> <br />?~re.\faf3hal <br />Kerry Barnett <br /> <br />3us ;3:~ ""'3C-1:C..J.: <br /> <br />?1~( (-3 -L3 73C-~=C4j. <br /> <br />"----_._------~_.__.,-~--_._----~._----_._._._._-~-~--_...._."'----~"-"'_.__.... <br /> <br />Plan Review Comments <br /> <br />I have reviewed the plans for the interior remodel at 7320 Gall and my comments have <br />been placed below. Please contact me if there are any questions with regards to my <br />comments. <br /> <br />1. Add emergency lights in handicap restroom in north suite and in restroom in <br />south suite. <br />2. Install knox box. <br />3. Firewall needs to have a UL design approved prior to construction. <br />4. Exit lights shall be battery backup. <br />S. Sprinkler changes shall be permitted with plans being turned in and letter <br />submitted from sprinkler contractor stating the system is compliant in that space <br />per NFPA 13, 2007 edition. <br />6. Panic hardware shall be installed on rear exit doors. <br />7. Place address on rear exit doors. <br /> <br />Inspections required: <br /> <br />1. Pressure test at system's working pressure for 2 hours for added or relocated <br />heads. <br />2. Acceptance test. <br />