<br />Zephyrhills Fire Rescue <br />6907 Dairy Road, Zephyrhills, FL 33542 <br /> <br />Fire Marshal <br />Kerry Barnett <br /> <br />Bus (813) 780-0041 <br />Fax (813) 780-0044 <br /> <br />November 15,2007 <br /> <br />Plan Review Comments <br /> <br />I have reviewed and approved the plans for a commercial hood located at 7825 Gall Blvd. <br />under the following conditions. My comments have been placed below. Please contact <br />me if you have any questions with regards to my comments. <br /> <br />1. Hood and duct shall comply with all current standards ofNFPA 96. <br />2, Rooftop fan shall be hinged and have a grease cup. <br />3. Hood duct shall be wrapped with fire rated insulating blanket <br />4, From the hood down to the floor and width of hood exposure protection shall be <br />provided on wall. Stainless steel or tile will be acceptable. <br /> <br />Inspections required: <br /> <br />1, Light test on hood and duct. Duct shall be tested before being installed; hood shall <br />be tested prior to being installed. After hood and duct has been installed a light <br />test shall be conducted at the connection seam. <br />2. Test and balance required on hood (3rd party) with copy supplied to Fire Marshal <br />at final test. <br />3. Hood final will be conducted during acceptance test on suppression system. <br />