<br />Termite Specifications:
<br />
<br />Structural Notes:
<br />
<br />1. A PERMANENT SIGN WHICH IDENTIFIES THE TERMITE TREATMENT PROVIDER
<br />AND NEED FOR RE-INSPECTION AND TREATMENT CONTRACT RENEVv'AL SHALL
<br />BE PROVIDED. THE SIGN SHALL BE POSTED NEAR THE WATER HEATER OR
<br />ELECTRIC PANEL.(FBC 104.2.6)
<br />
<br />FOUNDATIONS
<br />SOIL TO BE COMPACTED TO AT LEAST 95%
<br />OF MAX. DRY DENSITY AS DETERMINED BY
<br />ASTM - 1557 ( MODIFIED PROCTOR)
<br />FOUNDATION INSPECTIONS
<br />A FOUNDATION SURVEY SHALL BE PERFORMED AND A
<br />COpy OF THE SURVEY SHALL BE ON SITE FOR THE BUILDING
<br />INSPECTORS USE, OR ALL PROPERTY MARKERS SHALL BE
<br />EXPOSED AND A STRING STRECHED FROM MARKER TO
<br />MARKER TO VERIFY REQUIRED SETBACKS.
<br />CAST IN PLACE CONCRETE
<br />1. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE
<br />STRENGTH AT 28 DAYS OF 2500 PSI, A SLUMP OF 6"
<br />PLUS OR MINUS 1", AND HAVE 2 TO 5% AIR ENTRAINMENT,
<br />AND A MAXIMUM WATER/CEMENT RATIO OF 0.63
<br />2. ALL REINFORCING STEEL SHALL BE NEW DOMESTIC
<br />DEFORMED BILLET STEEL CONFORMING TO ASTM A-615
<br />GRADE 40.
<br />3. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185.
<br />YfflF SHALL BE LAPPED AT LEAST 6" AND CONTAIN AT
<br />LEAST ONE CROSS WIRE WITHIN THE 6".
<br />4. HOOKS SHALL BE PROVIDED AT DISCONTINUOUS ENDS OF
<br />ALL TOP BARS OF BEAMS.
<br />5. HORIZONTAL FOOTING BARS SHALL BE BENT 1'-0"
<br />AROUND CORNERS OR CORNER BARS WITH A 2'-0"
<br />LAP PROVIDED
<br />6. MINIMUM LAP SPLICES ON ALL REINFORCING BAR
<br />SPLICES SHALL BE 40 BAR DIAMETERS TYP.
<br />7. CONCRETE COVER MIN. 3" WHEN EXPOSED TO EARTH OR
<br />1 1/2" TO FORM
<br />MASONRY WALL CONST.
<br />1. HOLLOW LOAD BEARING UNITS SHALL BE NORMAL
<br />WEIGHT, GRADE N, TYPE 2, CONFORMING TO ASTM C90,
<br />WITH A MINIMUM NET COMPRESSIVE STRENGTH OF
<br />1900 PSI (fm = 1500 PSI)
<br />2. MORTAR SHALL BE TYPE "1'1" OR "S", CONFORMING TO
<br />ASTM C270.
<br />3. COARSE GROUT SHALL CONFORM TO ASTM C476 WITH A
<br />MAXIMUM AGGREGATE SIZE OF 3/8" AND A MINIMUM
<br />COMPRESSIVE STRENGTH OF 3000 PSI SLUMP 8" TO 11".
<br />4. VERTICAL REINFORCEMENT SHALL BE AS NOTED ON THE
<br />DRAWINGS WITH THE CELLS FILLED WITH COARSE GROUT.
<br />5. VERTICAL REINFORCEMENT SHALL BE HELD IN POSITION
<br />AT THE TOP AND BOTTOM AND AT A MAXIMUM SPACING
<br />OF 192 BAR DIAMETERS. REINFORCEMENT SHALL BE PLACED
<br />IN THE CENTER OF THE MASONRY CELL TYPICAL UNLESS
<br />OTHERWISE NOTED.
<br />6. REINFORCING STEEL SHALL BE LAPPED A MINIMUM OF 40 BAR
<br />DIAMETERS, UNLESS OTHERWISE NOTED ON THE DRAWINGS
<br />7. DUR-O-WALL SHALL BE PROVIDED @ EVERY OTHER
<br />COARSE OR 16" o/c
<br />WOOD CONSTRUCTION
<br />1. WOOD CONSTRUCTION SHALL CONFORM TO THE NFPA
<br />"NATIONAL DESIGN SPECIFICATION FOR WOOD
<br />CONSTRUCTION", 2001 EDITION.
<br />2. ALL EXTERIOR WOOD STUD WALLS, BEARING WALLS, SHEAR
<br />WALLS AND MISC. STRUCTURAL WOOD FRAMING MEMBERS,
<br />( I.E. BLOCKING OR GABLE END BRACING) SHALL BE EITHER
<br />SOUTHERN PINE, OR S.P.F. NUMBER 2 GRADE SHALL BE
<br />USED REGARDLESS OF SPECIES.
<br />3. ANY WOOD FRAME BEARING WALL STUDS THAT ARE CUT
<br />FOR PLUMBING LINES, ETe. SHALL BE REPAIRED WITH
<br />SIMPSON HSS2 STUD SHOES,TYP., U.N.O.
<br />4. ALL STUCCO FINISH OVER EXTERIOR FRAME MUST BE 7/8" THICK
<br />PER ASTM e. 926-APPLY 3 LAYERS WITH TOTAL THICKNESS 7/8"
<br />OVER METAL LATH.
<br />FIRST 2 LAYERS 3/8" THICK EACH. 3RD LAYER 1/8" THICK.
<br />5. ALL EXPOSED WOOD OR WOOD IN CONTACT WITH
<br />EARTH OR CONCRETE TO BE PRESSURE TREATED.
<br />
<br />*ATTENTION: CHEMICAL CHANGES IN PRESSURE TREATED WOODS
<br />AS OF DECEMBER 31ST, 2003, CHROMATED COPPER ARSENATE
<br />(CCA-C) WILL NO LONGER BE PRODUCED FOR RESIDENTIAL OR
<br />GENERAL CONSUMER USE. SEVERAL NEW PRESSURE TREATED
<br />WOOD ALTERNATIVES HAVE BEEN CREATED TO REPLACE CCA-e.
<br />MANY OF THE NEW PRESSURE TREATED WOODS USE CHEMICALS
<br />THAT ARE CORROSIVE TO STEEL. IT IS THE CONTRACTOR'S
<br />RESPONSIBILITY TO VERIFY THE TYPE OF WOOD TREATMENT AND TO
<br />SELECT APPROPRIATE CONNECTORS THAT RESIST CORROSION.
<br />FOR EXAMPLE, ACQ-C, ACQ-D, CBA-A, OR CA-B REQUIRE HOT-DIPPED
<br />GALVANIZED OR STAINLESS STEEL FASTENERS.
<br />DOT SODIUM BORATE (SBX) DOES NOT.
<br />
<br />SOIL BEARING
<br />V ALU E:
<br />
<br />CODES:
<br />
<br />PREFABRICATED WOOD TRUSSES
<br />
<br />3. IRRIGATION/SPRINKLER SYSTEMS INCLUDING ALL RISERS AND SPRAY HEADS
<br />SHALL NOT BE INSTALLED WITHIN 1'-0" OF THE BUILDING SIDE WALLS.(FBC 1503.4.4)
<br />
<br />1. ALL PREFABRICATED WOOD TRUSSES SHALL BE SECURELY
<br />FASTENED TO THEIR SUPPORTING WALLS OR BEAMS WITH
<br />HURRICANE CLIPS OR ANCHORS.
<br />2. PREFABRICATE WOOD TRUSSES SHALL BE DESIGNED IN
<br />ACCORDANCE WITH THE LATEST EDITION OF THE "NATIONAL
<br />DESIGN SPECIFICATION FOR STRESS-GRADE LUMBER AND
<br />ITS FASTENERS" AS RECOMMENDED BY THE NATIONAL
<br />FOREST PRODUCTS ASSOCIATION.
<br />3. TRUSS MEMBERS AND CONNECTIONS SHALL BE PROPOR-
<br />TIONED ( WITH A MAXIMUM ALLOWABLE STRESS INCREASE
<br />FOR LOAD DURATION OF 25%) TO WITHSTAND THE LIVE
<br />LOADS GIVEN IN THE NOTES AND TOTAL DEAD LOAD.
<br />4. BRIDGING FOR PRE-ENGINEERED TRUSSES SHALL BE AS
<br />REQUIRED BY THE TRUSS MANUFACTURER UNLESS
<br />NOTED ON THE PLANS.
<br />5. TRUSS ELEVATIONS AND SECTIONS ARE FOR GENERAL
<br />CONFIGURATION OF TRUSSES ONLY. WEB MEMBERS ARE
<br />NOT SHOWN, BUT SHALL BE DESIGNED BY THE TRUSS
<br />MANUFACTURER IN ACCORDANCE WITH THE DESIGN
<br />LOADS AS LISTED ON THE STRUCTURAL DESIGN CRITERIA
<br />6. DESIGN SPECIFICATIONS FOR LIGHT WEIGHT METAL
<br />PLATE CONNECTED WOOD TRUSSES PER THE TRUSS
<br />PLATE INSTITUTE TPI LATEST EDITION.
<br />7. PRE-ENGINEERED WOOD TRUSSES SHALL BE DESIGNED BY
<br />THE MANUFACTURER IN ACCORDANCE WITH SPECIFIED LOADS
<br />AND GOVERNING CODES. SUBMmALS SHALL INCLUDE TRUSS
<br />FRAMING PLANS AND DETAILS SHOWING MEMBER SIZES,
<br />BRACING, ANCHORAGE, CONNECTIONS, TRUSS LOCATIONS, AND
<br />AND PERMANENT BRACING AND/OR BRIDGING AS REQUIRED
<br />FOR ERECTION AND FOR THE PERMANENT STRUCTURE. EACH
<br />SUBMITTAL SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />REGISTERED STRUCTURAL ENGINEER. SUBMIT 3 COPIES FOR
<br />REVIEW AND APPROVAL PRIOR TO FABRICATION.
<br />8. THE TRUSS MANUFACTURER SHALL DETERMINE ALL SPANS
<br />WORKING POINTS, BEARING POINTS, AND SIMILAR CONDITIONS.
<br />TRUSS SHOP DRAWINGS SHALL SHOW ALL TRUSSES, ALL
<br />BRACING MEMBERS, AND ALL TRUSS TO TRUSS HANGERS.
<br />
<br />WOOD FRAMING:
<br />
<br />2. CONDENSATE AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1'-0"
<br />AWAY FROM BUILDING SIDE WALKS.(FBC 1503.4.4)
<br />
<br />LIVE LOADS:
<br />
<br />4. TO PROVIDE FOR INSPECTION FOR TERMITE INFESTATION, BETWEEN WALL
<br />COVERING AND FINAL EARTH GRADE SHALL NOT BE LESS THAT 6 INCHES.
<br />
<br />DEAD LOADS:
<br />
<br />EXCEPTION: PAINT OR DECORATIVE CEMENTATlOUS FINISH LESS THAN 5/8"
<br />THICK ADHERED DIRECTLY TO THE FOUNDATION WALL.(FBC 1403.1.6)
<br />
<br />5. INITIAL TREATMENT SHALL BE DONE AFTER ALL EXCAVATION AND BACKFILL
<br />IS COMPLETE.(FBC 1816.1.1)
<br />
<br />WIND LOADS:
<br />(F.B.C.)
<br />CONCRETE
<br />STRENGTH
<br />@ 28 DAYS
<br />
<br />6. SOIL DISTURBED AFTER THE INITIAL TREATMENT SHALL BE RETREATED
<br />INCLUDING SPACES BOXED AND FORMED.(FBC 1816.1.2)
<br />
<br />7. BOXED AREAS IN CONCRETE FLOORS FOR SUBSEQUENT INSTALLATION OF TRAPS,
<br />ETC., SHALL BE MADE WITH PERMANENT METAL OR PLASTIC FORMS. PERMANENT
<br />FORMS MUST BE OF A SIZE AND DEPTH THAT WILL ELIMINATE THE DISTURBANCE OF
<br />SOIL AFTER THE INITIAL TREATMENT.(FBC 1816.1.3)
<br />
<br />REINFORCING:
<br />
<br />8. MINIMUM 6 MIL VAPOR RETARDER MUST BE INSTALLED TO PROTECT AGAINST RAINFALL
<br />DILUTION. IF RAINFALL OCCURS BEFORE VAPOR RETARDER PLACEMENT, RETREATMENT IS
<br />REQUIRED.(FBC 1816.1.4)
<br />
<br />CONCRETE
<br />MASONRY
<br />UNITS:
<br />
<br />9. CONCRETE OVERPOUR AND MORTAR ALONG THE FOUNDATION PERIMETER MUST BE
<br />REMOVED BEFORE EXTERIOR SOIL TREATMENT.(FBC 1816.1.5)
<br />
<br />STRUCTURAL
<br />STEEL:
<br />
<br />10. SOIL TREATMENT MUST BE APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE
<br />WITHIN 1'-0" OF THE STRUCTURE SIDEWALLS.(FBC 1816.1.6)
<br />
<br />11. AN EXTERIOR VERTICAL CHEMICAL BARRIER MUST BE INSTALLED AFTER CONSTRUCTION
<br />IS COMPLETE INCLUDING LANDSCAPING AND IRRIGATION. ANY SOIL DISTURBED AFTER
<br />THE VERTICAL BARRIER IS APPLIED, SHALL BE RETREATED.(FBC 1816.1.6)
<br />
<br />12. ALL BUILDINGS ARE REQUIRED TO HAVE PRE-CONSTRUCTION TREATMENT.(FBC 1816.1.7)
<br />
<br />UPLIFT CONNECTORS
<br />
<br />WOOD ROOF
<br />TRUSSES:
<br />
<br />13. A CERTIFICATE OF COMPLIANCE MUST BE ISSUED TO THE BUILDING DEPARTMENT
<br />BY A LICENSED PEST CONTROL COMPANY BEFORE A CERTIFICATE OF OCCUPANCY
<br />WILL BE ISSUED. THE CERTIFICATE OF COMPLIANCE SHALL STATE: "THE BUILDING
<br />HAS RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN
<br />TERMITES. THE TREATMENT IS IN ACCORDANCE WITH THE RULES AND LAWS OF THE
<br />FLORIDA DEPARMENT OF AGRICULTURE AND CONSUMER SERVICES. "(FBC 1816.1. 7)
<br />
<br />1. UPLIFT CONNECTORS SUCH AS HURRICANE CLIPS, TRUSS
<br />ANCHORS AND ANCHOR BOLTS ARE ONLY REQUIRED ON
<br />MEMBERS IN WALLS THAT ARE EXPOSED TO UPLIFT FORCES.
<br />INTERIOR LOAD BEARING WALLS ARE NOT ALWAYS EXPOSED
<br />TO UPLIFT FORCES. THE MEMBERS OF THESE WALLS WOULD
<br />NOT NEED TO HAVE CONNECTORS APPLIED. PLEASE CONSULT
<br />THE TRUSS ENGINEERING FOR THE LOCATION OF THESE WALLS.
<br />
<br />14. AFTER ALL WORK IS COMPLETED, LOOSE WOOD AND FILL MUST BE REMOVED FROM
<br />BELOW AND WITHIN 1'-0" OF THE BUILDING. THIS INCLUDES ALL GRADE STAKES,
<br />TUB TRAY BOXES, FORMS, SHORING OR OTHER CELLULOSE CONTAINING MATERIAL
<br />(FBC 2303.1.3)
<br />
<br />15. NO WOOD, VEGETATION, STUMPS, CARDBOARD, TRASH, ETC., SHALL BE BURIED
<br />WITHIN 15'-0": OF ANY BUILDING OR PROPOSED BUILDING.(FBC 2303.1.4)
<br />
<br />FIELD REPAIR NOTES
<br />
<br />WOOD FLOOR
<br />TRUSSES:
<br />
<br />WOOD FRAMING INSPECTION
<br />ALL PLUMBING, ELECTRICAL, AND MECHANICAL
<br />ROUGH-INS MUST BE COMPLETE, INSPECTED
<br />AND APPROVED BEFORE REQUESTING FRAMING
<br />INSPECTION.
<br />
<br />1. MISSED LINTEL STRAPS FOR MASONRY CONSTRUCTION MAY
<br />BE SUBSTITUTED W/ (1) "SIMPSON MTSM16 TWIST STRAP W/
<br />(4) 1/4" X 2 1/4" DIA. TITENS TO THE BOND BEAM BLOCK
<br />AND (7) lad TO THE TRUSS FOR UPLIFTS OF 1000 LBS. OR
<br />LESS. USE (2) FOR 2000 LBS. OR LESS. OTHERS MAY BE
<br />SUBSTITUTED ON A CASE BY CASE BASIS.
<br />2. MISSED "J" BOLTS FOR WOOD BEARING WALLS MAY BE SUB-
<br />STITUTED W/ 1/2" DIA. ANCHOR BOLTS SET IN 3/4" DIA. X 6"
<br />DEEP UNITEX "PROPOXY" 300 ADHESIVE BINDER FOLLOWING
<br />ALL MANUFACTURERS RECOMMENDATIONS ( OR 1/2" X 6"
<br />RAWL STUD EXPANSION ANCHORS. )
<br />
<br />3. REGARDING MISSED REBAR IN VERTICAL FILLED CELLS:
<br />DRILL A 3/4" DIAMETER HOLE 6" DEEP AT THE LOCATION OF
<br />THE OMmED REBAR, AND INSTALL A 32" LONG #5 BAR INTO
<br />THE EPOXY FILLED HOLE. USE A TWO PART EMBEDDEMENT
<br />EPOXY ( SIMPSON "EPOXY TIE SEr', OR HIL TI " 2 PARr'
<br />EMBEDDMENT EPOXY ), MIXED PER MANUFACTURER'S
<br />INSTRUCTIONS. ASSURE THAT ALL DUST AND DEBRIS FROM
<br />DRILLING ARE REMOVED FROM THE HOLE BY BRUSHING AND
<br />AND USING COMPRESSED AIR PRIOR TO APPLYING THE EPOXY.
<br />ALLOW THE EPOXY TO CURE TO MANUFACTURER'S SPECIFICATIONS,
<br />THEN FILL THE CELL IN THE NORMAL WAY DURING BOND BEAM
<br />POUR.
<br />4. HURRICANE STRAPS MAY BE SUBSTITUTED WITH A STRAP OF
<br />GREATER HOLDOWN VALUE OR GREATER UPLIFT VALUE IN THE
<br />FIELD WITHOUT VERIFICATION, PROVIDED ALL MANUFACTURERS
<br />INSTALLATION INSTRUCTIONS ARE FOLLOWED.
<br />5. FOR MORTAR JOINTS LESS THAN 1/4", PROVIDE (1) #5 VERT.
<br />IN CONe. FILLED CELL EACH SIDE OF THE JOINT ( BAR DOES
<br />NOT HAVE TO BE CONT. TO FOOTING)
<br />
<br />Structural Design Criteria:
<br />
<br />General Notes:
<br />
<br />
<br />FLORIDA BUILDING CODE, 2001 EDITION
<br />BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE (ACI 318-02)
<br />SPECIFICATIONS FOR STRUCTURAL CONCRETE BUILDINGS (ACI 301-89)
<br />BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES (ACI 530-02)
<br />NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION, 2001 EDITION
<br />APA PLYWOOD DESIGN SPECIFICATION
<br />
<br />THE FOLLOWING TECHINCAL CODES
<br />SHALL APPLY:
<br />
<br />u
<br />z
<br />
<br />2001 FLORIDA BUILDING CODE,
<br />PLUMBING, MECHANICAL, FUEL GAS,
<br />ENERGY EFFICIENCY, ACCESSIBILITY,
<br />AND 2002 NATIONAL ELECTRICAL CODES
<br />
<br />Nco
<br />~ ~~
<br />ffi ~~~~~
<br />W ~ O)N
<br />~ ~ lir;),....1O
<br />......" co CQ~rd
<br />Z 'l'-!-...;;r,eLJ
<br />WOS"
<br />a:...JV"
<br />-:::1 ex
<br />ii! ~~
<br />c." n.
<br />W
<br />I-
<br />Z
<br />
<br />ROOF
<br />TOP CHORD
<br />BOTTOM CHORD (W /0 STORAGE)
<br />RESIDENTIAL FLOOR, UNLESS OTHERWISE INDICATED
<br />BALCONIES
<br />STAIRS
<br />
<br />ROOF
<br />FLOOR
<br />
<br />20 PSF
<br />10 PSF
<br />40 PSF
<br />40 PSF
<br />40 PSF
<br />
<br />17 PSF (SHINGLE)
<br />15 PSF
<br />
<br />ORDINANCE 92-19 - APPENDIX "J"
<br />TO FBC PLUMBING 2001 CODE.
<br />1. TANK TYPE WATER CLOSET VOLUME
<br />1.6 GALLONS
<br />2. WALL MOUNT WATER CLOSET VOLUME
<br />3.5 GALLONS
<br />3. WATER - FLOW RATE.
<br />PUBLIC FACILITIES 0.5 G.P.M.
<br />PRIVATE FACILITIES 2.2 G.P.M.
<br />SHOWER HEADS 2.5 G.P.M.
<br />4. ALL PLUMBING WATER LINES
<br />TO BE PVPC
<br />
<br />
<br />WIND LOADS BASED ON FBC, SECTION 1606.2.
<br />WIND VELOCITY: 123 M.P.H., USE FACTOR: 1.0
<br />
<br />ALL CONCRETE UNLESS OTHERWISE INDICATED
<br />PEA GRAVEL CONCRETE FOR MASONRY CELLS ONLY
<br />(DO NOT USE FOR CONCRETE COLUMNS OR TIE BEAMS)
<br />
<br />2500 PSI
<br />3000 PSI
<br />
<br />WELDED WIRE FABRIC SHALL CONFORM TO
<br />ALL REINFORCING BARS
<br />ALL STIRRUPS AND TIES
<br />
<br />ASTM A185
<br />ASTM A615-4O 40,000 PSI
<br />ASTM A615-40 40,000 PSI
<br />
<br />VTR LOCATIONS ARE APPROXIMATE
<br />AND MAY CHANGE DUE TO JOBSITE
<br />CONDITIONS
<br />
<br />ASTM C90 OR C129, STANDARD WEIGHT UNITS, fm=1500 PSI
<br />MORTAR TYPE "S" 1900 PSI
<br />CONCRETE GROUT 3000 PSI
<br />CONTINUOUS MASONRY INSPECTION IS REQUIRED DURING CONSTRUCTION
<br />
<br />ALL STRUCTURAL AND MISCELLANEOUS STEEL A36 36,000 PSI, U.N.O
<br />SHOP AND FIELD WELDS: E70XX ELECTRODES
<br />ALL BOLTS CAST IN CONCRETE: ASTM A36 OR ASTM A-307
<br />
<br />THE FOLLOWING SHALL COMPLY
<br />WITH THE 2001 FBC.
<br />
<br />o PORCHES AND BALCONIES
<br />SECTION 1014
<br />o HANDRAILS - SECTION 1007.5
<br />o GUARDRAILS - SECTION 1015, 1019.9
<br />o STAIRS - SECTION 1007
<br />o CHIMNEY & FIREPLACE
<br />SECTION 2804-2806 (MFGR)
<br />SECTION 2113-2114 (MAS)
<br />00 EGRESS WINDOWS
<br />SECTION 1005.4
<br />
<br />BEAMS, RAFTERS, JOIST, PLATES, ETe. U.N.O.
<br />NO.2 SOUTHERN YELLOW PINE (19% M.C.)
<br />ROOF DECK: PLYWOOD C-C;C-D, EXTERIOR, or OSB
<br />FLOOR SHEATHING: 3/4" PLYWOOD (5 PLIES) OR 3/4" T&G ADVANTECH
<br />WALL SHEATHING: PLYWOOD C-C/C-D, EXTERIOR OR OSB
<br />VERSA LAM BEAM Fb = 2900 PSI (2.0E)
<br />
<br />4. ALL OPENINGS SHALL COMPLY WITH
<br />2001 FBC WIND LOADS AS STATED
<br />BELOW. ATTACHMENTS OF WINDOWS,
<br />DOORS, SLIDING GLASS DOORS
<br />AND O.H. GARAGE DOORS ARE TO DELEGATED
<br />THE MANUFACTURER OF THESE ITEMS. THE
<br />MANUFACTURER OF THESE ITEMS
<br />SHALL SUBMIT ATTACHMENTS FOR
<br />SITE INSTALLATION.
<br />
<br />SEE ATTACHED SPECIFICATION SHEETS FOR
<br />MANUFACTURERS DESIGN CRITERIA AND
<br />INSTALLATION METHODS FOR WINDOWS,
<br />DOORS, SLIDING GLASS DOORS, OVERHEAD
<br />GARAGE DOORS, AND ROOFING.
<br />
<br />www
<br />o::::t.9U
<br />~~~
<br />::>00
<br />5?f2z
<br />
<br />(/) .~ Q ~
<br />@ ~.~ ~ ~ 9 ~ ~ 8 ~ ~
<br />~Q~ffi~?;ffiB:a:~~g
<br />::)c;.x~zu.~zo~::)~
<br />SSb']~o~oo~O"wo~
<br />::l\.:)e:::ll-'~a:~z:;;~i
<br />~~~ ......0 ~(i!~
<br />~Q~w~S~~~Q5
<br />t(~> o~ (i!r-Z~
<br />o ...... U. 0
<br />
<br />DESIGN LOADS:
<br />TOP CHORD LIVE AND DEAD LOAD:
<br />BOTTOM CHORD LIVE AND DEAD LOAD:
<br />TOTAL:
<br />
<br />27 PSF
<br />20 PSF
<br />47 PSF
<br />
<br />NET UPLIFT DESIGN PRESSURE: 20 PSF WITHIN
<br />4 FEET OF RIDGES, HIPS, EAVES AND BUILDING
<br />PERIMETER AND 15 PSF MIN FOR ALL OTHER AREAS.
<br />
<br />SEE DRAWINGS FOR SPECIAL CONCENTRATED LOADS. DESIGN
<br />FOR NEW WIND UPLIFT AS PER SPECIFIED CODES, DEDUCTING
<br />A MAXIMUM OF 10 P.S.F. DEAD LOAD, BUT NOT EXCEEDING ACTUAL
<br />DEAD LOAD.
<br />
<br />
<br />~
<br />oll.l~
<br />~j;8'
<br />Bi~ VI
<br />!~~ !
<br />~~~ ~~ ~
<br />",,;!ill.l 00 ~~
<br />~~j; ~~ ~~
<br />~~~ ~f3 ~
<br />~t:~ ~~ i
<br />~~e !!l! ~~
<br />~~Iii ot: f3~
<br />~~3 ~~ ~~
<br />
<br />. . .
<br />
<br />s
<br />o
<br />u
<br />0\ U
<br />o L() .6
<br />0\ t--. rJl
<br />.9 L() CI') Q)
<br />-0 CI') ......
<br />E~ .0000
<br />~~ ~~~.~~
<br />ro~ roR:R:~o
<br />~~~ ~~~ ~.~
<br />Q) ~'S Q) t; ~ ~
<br />U("Hj)Uo..~ :tl:
<br />
<br />
<br />DESIGN LOADS:
<br />DEAD LOAD:
<br />LIVE LOAD:
<br />TOTAL:
<br />
<br />15 PSF
<br />40 PSF
<br />55 PSF
<br />
<br />5. ALL DOORS INTERIOR & EXTERIOR ARE
<br />6'-8" UNLESS OTHERWISE NOTED
<br />ALL SHOWER ENCLOSURES TO BE
<br />TEMPERED GLASS
<br />6. ALL WINDOWS WITHIN 24" OF DOORS
<br />(INTERIOR & EXTERIOR) AND WITHIN
<br />18" OF FLR TO BE TEMPERED GLASS.
<br />(SECTION 2405.2)
<br />
<br />CONSTRUCTION TYPE -- TYPE VI UNPROTECTED
<br />(SECTION 608 - FBe 2001)
<br />
<br />WIND BORNE DEBRIS AREAS
<br />
<br />THE METHOD TO SATISFY PROTECTION OF OPENINGS
<br />IN THESE AREAS WILL BE THE SOLE RESPONSIBILITY
<br />OF THE CONTRACTOR.
<br />
<br />ASSUMED ALLOWABLE SOIL BEARING PRESSURE AFTER COMPACTION: 2000 PSF
<br />SEE SOILS REPORT AND SPECIFICATIONS FOR COMPACTION REQUIREMENTS
<br />IF SOIL CONDITIONS IN THE PROJECT DO NOT MEET OR EXCEED THE CAPACITY
<br />THE GENERAL CONTRACTOR SHALL CONTACT THE ENGINEER PRIOR TO
<br />FOUNDATION POUR FOR VERIFICATION OF FOUNDATION DESIGN.
<br />
<br />Building Data:
<br />
<br />Index Of Drawings
<br />SHT NO: ITLE
<br />A COVER SHEET
<br />A1 FLOOR PLAN
<br />A2 FOUNDATION PLAN
<br />A3 ELECTRICAL PLAN
<br />A4.1 ELEVATION I
<br />A4.2 ELEVATION II
<br />A4.3 ELEVATION III
<br />AS.1 ROOF FRAMING ELEV I
<br />AS.2 ROOF FRAMING ELEV II
<br />AS.3 ROOF FRAMING ELEV III
<br />A6 INTERIOR ELEVATIONS <.0
<br /> (/)
<br /> c
<br />S-1 FOUNDATION DETAILS 0) 0
<br />S-2 LINTEL DETAILS '0;
<br />0 '>
<br />S-2A LINTEL PLANS ~
<br />S-3 ROOF FRAMING (I, II, III) 0 ~
<br /> Q)
<br />S-4 BRACING DETAILS I en >
<br /> WALL SECTIONS C\I -
<br />S-6 -
<br /> .-
<br />S-7 STRUCTURAL NOTES & lC) I
<br /> HANGER INFORMATION I 3:
<br />S-8 WINDOW & DOOR DETAILS f'-..
<br />S-9 WINDOW & DOOR DETAILS Q)
<br /> .-
<br />S-lO WINDOW & DOOR DETAILS ~ >
<br /> +-'
<br />S-11 WINDOW & DOOR DETAILS ~ en
<br />S-12 PRODUCT APPROVAL INFO lC) Q)
<br /> L..
<br /> ~ ()
<br />
<br />WIND SPEED 123 MPH
<br />WIND IMPORTANCE FACTOR -- (Iw) = 1.0
<br />WIND EXPOSURE -- "B" (FBC 1606.1.8)
<br />INTERNAL PRESSURE COEFFICIENT = +/- 0.55 (PART. ENCLOSED)
<br />
<br />DESIGN WIND PRESSURE:
<br />
<br />(COMPONENT AND CLADDING) WORST CASE (10 SF - END ZONE)
<br /># END ZONE IS ONLY WITHIN 5'-0"
<br />OF ALL EXTERIOR BUILDING CORNERS
<br />
<br />THEIR OPTIONS ARE AS FOLLOWS:
<br />
<br />WINDOWS AND DOORS
<br />SEE FLOOR PLAN FOR ACTUAL PRESSURES
<br />
<br />A. IMPACT RESISTANT GLAZING
<br />B. APPROVED SHUTTERS
<br />C. SUPPLY WOOD STRUCTURAL PANELS
<br />PER FBC 1606.1.4
<br />
<br />
<br />Master Revisions:
<br />
<br />DATE
<br />
<br />DESCRIPTION
<br />
<br />ALL WORK SHALL COMPLY WITH ALL
<br />PREVAILlNG CODES, FLORlDA BUILDI1~J
<br />CODE, NATIONAL ELECTRIC CODE AND
<br />CITY OF ZEPHYRHlLLS ORDINANCES
<br />
<br />....
<br />.:<
<br />~
<br />}
<br />~
<br />8
<br />~
<br />~
<br />~
<br />......
<br />'"
<br />~
<br />~
<br />l
<br />~
<br />i
<br />
<br />---
<br />:;
<br />~
<br />j
<br />~
<br />1
<br />
<br />---
<br />~
<br />~
<br />o
<br />~
<br />~
<br />i
<br />~
<br />1
<br />2
<br />---
<br />---
<br />
<br />REVIEWED
<br />HAY 0 9 2005
<br />
<br />~~
<br />
<br />CENTRAL FLORIDA DIVISION,
<br />TAMPA, FLORIDA 33609
<br />
<br />w
<br />~
<br />O~
<br />OZ
<br />:5
<br />~a..
<br />U SHEET NO.
<br />o
<br />
<br />-
<br />
<br />al
<br />
<br />ENGINEERED PLANS
<br />ON FILE
<br />
<br />Notice To Builder
<br />
<br />>-
<br />(t:
<br />o
<br />I-
<br />Z
<br />W
<br />>
<br />Z
<br />
<br />600 N. WESTSHORE BLVD. SUITE 600
<br />(813) 769-5277
<br />
<br />IT IS THE INTENT OF THIS DESIGNER THAT
<br />THESE PLANS ARE ACCURATE AND ARE
<br />CLEAR ENOUGH FOR THE LICENSED PROFESS-
<br />ONAL TO CONSTRUCT THIS PROJECT.
<br />IN THE EVENT THAT SOMETHING IS UNCLEAR
<br />OR NEEDS CLARIFlCATION..STOP..AND CALL
<br />THE DESIGNER LISTED IN THIS TITLE PAGE. IT
<br />IS THE RESPONSIBILITY OF THE LICENSED
<br />PROFESSIONAL THAT IS CONSTRUCTING THIS
<br />PROJECT TO FULLY REVIEW THESE DOCUMENTS
<br />BEFORE CONSTRUCTION BEGINS AND ANY AND
<br />ALL CORRECTIONS, IF NEEDED, TO BE MADE
<br />BEFORE ANY WORK IS DONE.
<br />
<br />o
<br />o
<br />\..0
<br />
<br />~O
<br />:J ~t
<br />ZVl,..-ir--.
<br />o .,..-i r--.
<br />t-t""OIN
<br />Vl>O"\Lt')
<br />t-t;::nOI
<br />>L.L..I\!)
<br />t-tQ)MO'\
<br />OL-M\..O
<br />r--.
<br />... <( 0 - I
<br />"a...cLLM
<br />~ II (0 ~
<br />~ U) n I
<br />j::Q)E..-i
<br />$ (0
<br />.1--
<br />Z
<br />o
<br />o
<br />\..0
<br />
<br />Ln
<br />o
<br />o
<br />N
<br />
<br />>-....
<br />~z
<br />UJ
<br />Z(J)
<br />wJ-1zz
<br />Uooo
<br />UJUtJ)
<br />~~z~
<br />08~o
<br />Z~~<{
<br />0.>0..
<br />UJ>:E
<br />J-~UJ<{
<br />::C~~~
<br />(..9 .... .... :E
<br />~o::>o
<br />0:::: Z 0 J:
<br />>- ~ J: (J)
<br />0.. :E ~ ::>
<br />O~~~
<br />U:)UJct
<br />o..Zu.
<br />(J)Z
<br />J-1<{
<br />~:E
<br />
<br />-
<br />-
<br />
<br />L.
<br />(]J
<br />>
<br />o
<br />""0
<br />C
<br /><(
<br />
<br />ro
<br />$
<br />E
<br />2
<br />Vl
<br />
<br />A
<br />
<br />a:
<br />~
<br />o
<br />U
<br />UJ
<br />:E
<br />o
<br />J:
<br />(J)
<br />::>
<br />II)
<br />8
<br />('oj
<br />@
<br />
<br />ANDOVER 2005
<br />
<br />co
<br />(j) LAST PLOT DATE
<br />. 0 Mar. 23, 05
<br />--l COVER SHEET
<br />
<br />-
<br />
|