<br />TERMITE SPECIFICATIONS: <br /> <br />1, A PERMANENT SIGN WHICH IDENTIFIES THE TERMITE TREATMENT PROVIDER <br />AND NEED FOR RE-INSPECTION AND TREATMENT CONTRACT RENEWAL SHALL <br />BE PROVIDED. THE SIGN SHALL BE POSTED NEAR THE WATER HEATER OR <br />ELECTRIC PANEL.(FBC 104.2,6) <br /> <br />2, CONDENSATE AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1'-0" <br />AWAY FROM BUILDING SIDE WALKS.(FBC 1503.4.4) <br /> <br />3. IRRIGATION/SPRINKLER SYSTEMS INCLUDING ALL RISERS AND SPRAY HEADS <br />SHALL NOT BE INSTALLED WITHIN 1'0" OF THE BUILDING SIDE WALLS,(FBC 1503.4.4) <br /> <br />4. TO PROVIDE FOR INSPECTION FOR TERMITE INFESTATION, BETWEEN WALL <br />COVERING AND FINAL EARTH GRADE SHALL NOT BE LESS THAT 6 II\CHES. <br /> <br />EXCEPTION: PAINT OR DECORATIVE CEMENTATIOUS FII\ISH LESS THAN 5/8" <br />THICK ADHERED DIRECTLY TO THE FOUNDATION WALL,(FBC 1403.1,6) <br /> <br />5. INITIAL TREATMENT SHALL BE DONE AFTER ALL EXCAVATION AND BACKFILL <br />IS COMPLETE,(FBC 1816.1.1) <br /> <br />6, SOIL DISTURBED AFTER THE INITIAL TREATMENT SHALL BE RETREATED <br />INCLUDING SPACES BOXED AND FORMED.(FBC 1816.1,2) <br /> <br />7. BOXED AREAS IN CONCRETE FLOORS FOR SUBSEQUENT INSTALLATION OF TRAPS, <br />ETC., SHALL BE MADE WITH PERMANENT METAL OR PLASTIC FORMS. PERMANENT <br />FORMS MUST BE OF A SIZE AND DEPTH THAT WILL ELIMINATE THE DISTURBANCE OF <br />SOIL AFTER THE INITIAL TREATMENT.(FBC 1816.1.3) <br /> <br />8, MINIMUM 6 MIL VAPOR RETARDER MUST BE INSTALLED TO PROTECT AGAINST RAINFALL <br />DILUTION. IF RAINFALL OCCURS BEFORE VAPOR RETARDER PLACEMENT, RETREATMENT IS <br />REQUIRED,(FBC 1816.1.4) <br /> <br />9, CONCRETE OVERPOUR AND MORTAR ALOI\G THE FOUNDATION PERIMETER MUST BE <br />REMOVED BEFORE EXTERIOR SOIL TREATMENT,(FBC 1816.1.5) <br /> <br />10. SOIL TREATMENT MUST BE APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE <br />WITHIN 1'-0" OF THE STRUCTURE SIDEWALLS.(FBC 1816.1.6) <br /> <br />11. AN EXTERIOR VERTICAL CHEMICAL BARRIER MUST BE INSTALLED AFTER CONSTRUCTION <br />IS COMPLETE INCLUDING LAI\DSCAPING AND IRRIGATION. ANY SOIL DISTURBED AFTER <br />THE VERTICAL BARRIER is APPLIED, SHALL BE RETREATED,(FBC 1816.1.6) <br /> <br />12. ALL BUILDINGS ARE REQUIRED TO HAVE PRE-CO~STRUCTION TREATMENT.(FBC 1816.1.7) <br /> <br />13. A CERTIFICATE OF COMPLIANCE MUST BE ISSUED TO THE BUILDING DEPARTMENT <br />BY A LICENSED PEST CONTROL COMPANY BEFORE A CERTIFICATE OF OCCUPANCY <br />WILL BE ISSUED, THE CERTIFICATE OF COMPLIANCE SHALL STATE: "THE BUILDING <br />HAS RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN <br />TERMITES. THE TREATMENT is IN ACCORDANCE WITH THE RULES AND LAWS OF THE <br />FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER SERVICES,"(FBC 1816.1.7) <br /> <br />14. AFTER ALL WORK IS COMPLETED, LOOSE WOOD AND FILL MUST BE REMOVED FROM <br />BELOW AND WITHIN 1'-0" OF THE BUILDING, THIS II\CLUDES ALL GRADE STAKES, <br />TUB TRAY BOXES, FORMS, SHORING OR OTHER CELLULOSE CONTAINING MATERIAL. <br />(FBC 2303.1,3) <br /> <br />15.1\0 WOOD, VEGETATION, STUMPS, CARDBOARD, TRASH, ETC., SHALL BE BURIED <br />WITHIN 15'-0": OF ANY BUILDING OR PROPOSED BUILDING.(FBC 2303,1.4) <br /> <br />A.B. <br />Abv, <br />A/C <br />Adj, <br />A.F,F. <br />A.H,U. <br />AU, <br />B.C, <br />B,F. <br />Bk Sh <br />Bm, <br />BOT. <br />~. B,P. <br />Brg. <br />Cir. <br />Clg, <br />Col. <br />Comp, <br />C.T. <br />D <br />Dec. <br />Ded, <br />Dbl, <br />Dia, <br />Disp. <br />Dist. <br />D.S, <br />D.V. <br />DW, <br />Ea. <br />EW. <br />Elec. <br />Elev, <br />Ext. <br />Exp, <br /> <br />ABBREVIA TIONS <br /> <br />Anchor Bolt <br />Above <br />Air-Conditioner <br />Adjustable <br />Above Finished Floor <br />Air Handler Unit <br />Alternate <br />Base Cabinet <br />Bifold Door <br />Book Shelf <br />Beam <br />Bottom <br />Bypass door <br />Bearing <br />Circle <br />Ceiling <br />Column <br />A/C Compressor <br />Ceramic Tile <br />Dryer <br />Decorative <br />Dedicated Outlet <br />Double <br />Diameter <br />Disposal <br />Distance <br />Drawer Stack <br />Dryer Vent <br />Dishwasher <br />Each <br />Each Way <br />Electrical <br />Elevation <br />Exterior <br />Expansion <br /> <br />F,B.C. <br />Fin. Fir. <br />F.G. <br />Fir, <br />Fdn. <br />FIr. Sys, <br />F,PI. <br />Ft. <br />Ftg. <br />FX <br />Galv. <br />G,C. <br />G,F.1. <br />G.T. <br />Hdr. <br />Hgt. <br />HB <br />Int. <br />K/Wall <br />K.S. <br />Laun. <br />Lav. <br />L.F, <br />L.T, <br />Mas. <br />Max <br />M.C. <br />Mfgr. <br />Micro, <br />Min <br />M.L. <br />Mir, <br />Mono <br />N,T.S. <br /> <br />Florida Bldg. Code <br />Finished Floor <br />Fixed Glass <br />Floor <br />Foundation <br />Floor System <br />Fireplace <br />Foot / Feet <br />Footing <br />Fixed <br />Galvanized <br />General Contractor <br />Ground Fault Interrupter <br />Girder Truss <br />Header <br />Height <br />Hose Bibb <br />Interior <br />Kneewall <br />Knee Space <br />Laundry <br />Lavatory <br />Li near Ft. <br />Laundry Tub <br />Masonry <br />Maximum <br />Medicine Cabinet <br />Manufacturer <br />Microwave <br />Minimum <br />Microlam <br />Mirror <br />Monolithic <br />Not to Scale <br /> <br />Opn'g. <br />Opt. <br />Pc. <br />Ped. <br />P,L. <br />PLF <br />PIt. Ht. <br />Pit Sh, <br />PSF <br />P,T, <br />Pwd. <br />Rad. <br />Ref, <br />Req'd. <br />Rm, <br />Rnd. <br />R/SH <br />SD, <br />S.F, <br />Sh, <br />SHT <br />S,L. <br />S.P.F. <br />Sq, <br />S.Y,P. <br />Temp. <br />Thik'n. <br />T,O.B. <br />T.O"VI. <br />T,O.P. <br />Trans. <br />Typ, <br />UCL <br />U.N.O. <br />VB <br />Vert. <br />V.L. <br />VTR <br />W <br />W/ <br />W/C <br />W.A, <br />Wd <br />WP <br /> <br />MASTER REVISIONS <br /> <br />DATE <br /> <br />DESCRIPTION <br /> <br />Openirg <br />Optional <br />P;ece <br />Pedestal <br />Parallam <br />Pounds per linear foot <br />Plate Height <br />Plant Shelf <br />Pounds per square foot <br />PressLire Treated <br />Powder Room <br />Radius <br />Refrigerator <br />Required <br />Room <br />Round <br />Rod and Shelf <br />Smoke Detector <br />Square Ft. <br />Shelves <br />Sheet <br />Side Lights <br />Spruce Pine Fir <br />Square <br />Southern Yellow Pine <br />Tempered <br />Thicken <br />Top of Block <br />Top of Masonry <br />Top of Plate <br />Transom Window <br />Typical <br />Under Cabinet Lighting <br />Unless Noted Otherwise <br />Vanity Base <br />Vertical <br />Versalam <br />Vent through Roof <br />Washer <br />With <br />Water Closet <br />Wedge Anchor <br />Wood <br />Water Proof <br /> <br />STRUCTURAL NOTES: <br /> <br />STRUCTURAL DESIGN CRITERIA <br /> <br />FOUNDATIONS <br /> <br />3. ANY WOOD FRAVlE INTERIOR BEARING WALL STUDS THAT <br />HAVE HOLES IN THE CENTER OF THE STUD UP TO 1" DIA. <br />SHALL HAVE STUD PROTECTION <br />SHIELDS FOR ALL HOLES OVER 1" IN DIA. <br />FOR PLUMBING LINES, ETC, SHALL BE REPAIRED WITH <br />SIMPSON HSS2 STUD SHOES,TYP., U,N.O, <br /> <br />CODES: <br /> <br />FLORIDA BUILDING CODE, 2001 EDITION WITH 2003 REVISIONS <br />BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE (ACI 318-02) <br />SPECIFICATIONS FOR STRUCTURAL CONCRETE BUILDINGS (ACI 301-02) <br />BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES (ACI 530-02) <br />NATIONAL DESIGN SPECIFICATION FOR WOOD COI\;STRUCTION, 2001 EDITION <br />APA PLYWOOD DESIGN SPECIFICATION <br /> <br />SOIL TO BE COMPACTED TO AT LEAST 95% <br />OF MAX, DRY DENSITY AS DETERMINED BY <br />ASTM - 1557 ( MODIFIED PROCTOR) <br /> <br />FOUNDATION INSPECTIONS <br /> <br />A FOUNDATION SURVEY SHALL BE PERFORMED AND A <br />COpy OF THE SURVEY SHALL BE ON SITE FOR THE BUILDING <br />INSPECTORS USE, OR ALL PROPERTY MARKERS SHALL BE <br />EXPOSED AND A STRING STRETCHED FROM MARKER TO <br />MARKER TO VERIFY REQUIRED SETBACKS, <br />CAST IN PLACE CONCRETE <br />1. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE <br />STRENGTH AT 28 DAYS OF 3000 PSI, A SLUMP OF 6" <br />PLUS OR MINUS 1", AI\D HAVE 2 TO 5% AIR ENTRAINMENT, <br />AND A MAXIMUM WATER/CEMENT RATIO OF 0,63 <br />2. ALL REINFORCING STEEL SHALL BE NEW DOMESTIC <br />DEFORMED BILLET STEEL CONFORMING TO ASTM A-615 <br />GRADE 40, <br />3, WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185. <br />WWF SHALL BE LAPPED AT LEAST 6" AND CONTAIN AT <br />LEAST ONE CROSS WIRE WITHIN THE 6". <br />4, HOOKS SHALL BE PROVIDED AT DiSCONTINUOUS ENDS OF <br />ALL TOP BARS OF BEAMS. <br />5, HORIZONTAL FOOTING BARS SHALL BE BENT 1'-0" <br />AROUND CORNERS OR CORI\ER BARS WITH A 2'-0" <br />LAP PROVIDED <br />6. MINIMUM LAP SPLICES ON ALL REINFORCING BAR <br />SPLICES SHALL BE 40 BAR DIAMETERS TYP, <br />7, CONCRETE COVER MIN. 3" WHEN EXPOSED TO EARTH OR <br />1 1/2" TO FORM <br /> <br />WOOD FRAMING INSPECTION <br /> <br />LIVE LOADS: <br /> <br />ROOF <br />RESIDENTIAL FLOOR, UNLESS OTHERWISE INDICATED <br />BALCONIES <br />ST AI RS <br />LIGHT PARTITIONS (DEAD LOAD), U,N,O, <br /> <br />WIND LOADS BASED ON FBC, SECTION 1606.2. <br />WIND VELOCITY: 123 M.P,H" USE FACTOR: 1.0 <br /> <br />20 PSF (REDUCIBLE) <br />40 PSF <br />40 PSF <br />40 PSF <br />20 PSF <br />10 PSF ATTIC L.L, <br /> <br />ALL PLUMBING, ELECTRICAL, AND MECHANICAL <br />ROUGH-INS MUST BE COMPLETE, INSPECTED <br />AND APPROVED BEFORE REQUESTII'\G FRAMING <br />INSPECTION. <br /> <br />PREFABRICATED WOOD TRUSSES <br /> <br />1. ALL PREFABRICATED WOOD TRUSSES SHALL BE SECURELY <br />FASTENED TO THEIR SUPPORTING WALLS OR BEAMS WITH <br />HURRICANE CLIPS OR ANCHORS. <br />2, PREFABRICATE WOOD TRUSSES SHALL BE DESIGNED IN <br />ACCORDANCE WITH THE LATEST EDITION OF THE "NATIONAL <br />DESIGN SPECIFICATION FOR STRESS-GRADE LUMBER AND <br />ITS FASTENERS" AS RECOMMENDED BY THE NATIONAL <br />FOREST PRODUCTS ASSOCIATION. <br />3, TRUSS MEMBERS AND CONNECTIONS SHALL BE PROPOR- <br />TIONED ( WITH A MAXIMUM ALLOWABLE STRESS INCREASE <br />FOR LOAD DURATION OF 25%) TO WITHSTAND THE LIVE <br />LOADS GIVEN IN THE NOTES AND TOTAL DEAD LOAD. <br />4, BRIDGING FOR PRE-ENGINEERED TRUSSES SHALL BE AS <br />REQUIRED BY THE TRUSS MANUFACTURER UNLESS <br />NOTED ON THE PLANS. <br />5, TRUSS ELEVATIONS AND SECTIONS ARE FOR GENERAL <br />CONFIGURATION OF TRUSSES ONLY. WEB MEMBERS ARE <br />NOT SHOWN, BUT SHALL BE DESIGNED BY THE TRUSS <br />MANUFACTURER IN ACCORDANCE WITH THE FOLLOWING <br />DESIGN LOADS: <br />6. DESIGN SPECIFICATIONS FOR LIGHT WEIGHT METAL <br />PLATE CONNECTED WOOD TRUSSES PER THE TRUSS <br />PLATE INSTITUTE TPI LATEST EDITION. <br />7. PRE-ENGINEERED WOOD TRUSSES SHALL BE DESIGNED BY <br />THE MANUFACTURER IN ACCORDANCE WITH SPECIFIED LOADS <br />AND GOVERNING CODES. SUBMITTALS SHALL INCLUDE TRUSS <br />FRAMING PLANS AND DETAILS SHOWING MEMBER SIZES, <br />BRACING, ANCHORAGE, CONNECTIONS, TRUSS LOCATIONS, AND <br />AND PERMANENT BRACING AND/OR BRIDGING AS REQUIRED <br />FOR ERECTION AND FOR THE PERMAI'\ENT STRUCTURE, EACH <br />SUBMITTAL SHALL BE SIGNED AND SEALED BY A FLORIDA <br />REGISTERED STRUCTURAL ENGINEER. SUBMIT 3 COPIES FOR <br />REVIEW AND APPROVAL PRIOR TO FABRICATION. <br />8. THE TRUSS MANUFACTURER SHALL DETERMINE ALL SPANS <br />WORKING POINTS, BEARING POINTS, AND SIMILAR CONDITIONS, <br />TRUSS SHOP DRAWINGS SHALL SHOW ALL TRUSSES, ALL <br />BRACING MEMBERS, AND ALL TRUSS TO TRUSS HANGERS, <br /> <br />WIND LOADS: <br />(F. B.C.) <br /> <br />CONCRETE <br />STRENGTH <br />@ 28 DAYS <br /> <br />ALL CONCRETE UNLESS OTHERWISE INDICATED <br />PEA GRAVEL CONCRETE FOR MASONRY CELLS ONLY <br />(DO NOT USE FOR CONCRETE COLUMNS OR TIE BEAMS) <br /> <br />3000 PSI <br />3000 PSI <br /> <br />REINFORCING: <br /> <br />WELDED WIRE FABRIC SHALL CONFORM TO <br />ALL REINFORCII'\G BARS <br />ALL STIRRUPS AND TIES <br /> <br />ASTM A185 <br />ASTM A615-40 40,000 PSI <br />ASTM A615-40 40,000 PSI <br /> <br />CONCRETE <br />MASONRY <br />UNITS: <br /> <br />ASTM C90-99b, STANDARD WEIGHT UNITS, fm==1500 PSI <br />MORTAR TYPE "S" 1800 PSI <br />CONCRETE GROUT 3000 PSI <br />CONTINUOUS MASONRY INSPECTION IS REQUIRED DURING CONSTRUCTION <br /> <br />ALL STRUCTURAL AND MISCELLAI\EOUS STEEL A36 36,000 PSI, U,N.O <br />SHOP AND FIELD WELDS: E70XX ELECTRODES <br />ALL BOLTS CAST IN CONCRETE: ASTM A36 OR ASTM A-307 <br /> <br />BEAMS, RAFTERS, JOIST, PLATES, ETC, U.N.O. <br />NO.2 SOUTHERN YELLOW PINE (19% M.C.) <br />ROOF DECK: PLYWOOD C-C/C-D, EXTERIOR, or OSB <br />FLOOR SHEATHING: T&G A-C GROUP 1 APA RATED (48/24) <br />WALL SHEATHING: PLYWOOD C-C/C-D, EXTERIOR OR OSS <br />VERSA LAM BEAM Fb == 2900 PSI (2.0E) <br />WOOD COLS, PARALLAM 2.0E U,N.O, <br /> <br />DESIGN LOADS: <br />TOP CHORD LIVE LOAD: 20 PSF <br />TOP CHORD DEAD LOAD: 10 PSF <br /> <br />STRUCTURAL <br />STEEL: <br /> <br />REINFORCING STEEL <br /> <br />ALL REINFORCING STEEL SHALL BE NEW DEFORMED BARS <br />FREE FROM RUST, SCALE & OIL & SHALL VlEET ASTM A-615 <br />REIr--.FORCING FOR FOOTING SHALL BE SUPPORTED ON PRE- <br />CAST CONCRETE PADS, TOP REINFORCING SHALL BE <br />POSITIVELY SUPPORTED BY TEMPORARY STRIr--.GERS. <br />DOWELS FOR COLUMI\JS & FILLED CELLS SHALL BE SECURED <br />IN PLACE BY USING ADDITIONAL CROSS- REINFORCING TIED <br />TO FOOTING REINFORCING. SPLICES IN REIr--.FORC1NG WHERE <br />PERMITTED SHALL BE THE FOLLOWING MINIMUM, UNLESS <br />OTHERWISE INDICATED ON THE DRAWII\GS: <br /> <br />FTGS, WALLS, COLUMNS, BEAMS, SLABS: 36 DIA. OR 2'-0" MIN., WHICHEVER IS MORE. <br />FILLED CELL REINFORCING: 40 DIA, OR 2'-0" MIN" WHICHEVER is MORE. <br />TEMPERATURE REINFORCING: 20 DIA, OR 1'-0" MIN" WHICHEVER IS MORE. <br />WELDED WIRE MESH: 8" LAP <br /> <br />WOOD FRAMING: <br /> <br />WOOD ROOF <br />TRUSSES: <br /> <br />BOTTOM CHORD DEAD LOAD: <br /> <br />10 PSF <br />40 PSF <br /> <br />10 PSF <br /> <br />BOTTOM CHORD ATTIC LIVE LOAD: <br /> <br />SEE DRAWINGS FOR SPECIAL CONCENTRATED LOADS. DESIGN <br />FOR NEW WIND UPLIFT AS PER SPECIFIED CODES, DEDUCTING <br />A MAXIMUM OF 5 P.S.F. DEAD LOAD, BUT NOT EXCEEDING ACTUAL <br />DEAD LOAD. <br /> <br />DESIGN LOADS: <br />DEAD LOAD: <br />LIVE LOAD: <br />TOTAL: <br /> <br />MASONRY WALL CONST. <br />1. HOLLOW LOAD BEARII\G UNITS SHALL BE NORMAL <br />WEIGHT, GRADE N, TYPE 2, CONFORMING TO ASTM C90, <br />WITH A MINIMUM NET COMPRESSIVE STRENGTH OF <br />1900 PSI ( f'm == 1500 PSI) <br />2. MORTAR SHALL BE TYPE "S", CONFORMII\G TO <br />ASTM C270. <br />3. COARSE GROUT SHALL CONFORM TO ASTM C476 WITH A <br />MAXIMUM AGGREGATE SIZE OF 3/8" AND A MINIMUM <br />COMPRESSIVE STRENGTH OF 3000 PSI SLUMP 8" TO 11", <br />4. VERTICAL REINFORCEMENT SHALL BE AS NOTED ON THE <br />DRAWINGS WITH THE CELLS FILLED WITH COARSE GROUT. <br />5. VERTICAL REINFORCEMENT SHALL BE HELD IN POSITION <br />AT THE TOP AND BOTTOM AND AT A MAXIMUM SPACING <br />OF 192 BAR DIAMETERS, REINFORCEMENT SHALL BE PLACED <br />IN THE CENTER OF THE MASONRY CELL TYPICAL UNLESS <br />OTHERWiSE NOTED. <br />6, REINFORCING STEEL SHALL BE LAPPED A MINIMUM OF 40 BAR <br />DIAMETERS, UNLESS OTHERWISE NOTED ON THE DRAWINGS <br />7. GROUT STOPS SHALL BE PROVIDED BELOW BOND BEAM. PLASTIC <br />SCREEN, METAL LATH STRIP OR CAVITY CAPS MAY BE USED TO <br />PREVENT THE FLOW GROUT INTO CELLS BELOW, THE USE OF FELT <br />PAPER AS A STOP IS PROHIBITED, <br /> <br />UPLIFT CONNECTORS <br /> <br />1, UPLIFT CONNECTORS SUCH AS HURRICANE CLIPS, TRUSS <br />ANCHORS AND ANCHOR BOLTS ARE ONLY REQUIRED ON <br />MEMBERS IN WALLS THAT ARE EXPOSED TO UPLIFT FORCES. <br />INTERIOR LOAD BEARING WALLS ARE NOT ALWAYS EXPOSED <br />TO UPLIFT FORCES, THE MEMBERS OF THESE WALLS WOULD <br />NOT NEED TO HAVE CONNECTORS APPLIED. PLEASE CONSULT <br />THE TRUSS ENGINEERING FOR THE LOCATION OF THESE WALLS. <br /> <br />WOOD FLOOR <br />TRUSSES: <br /> <br />15 PSF <br />50 PSF <br />65 PSF <br /> <br />ASSUMED ALLOWABLE SOIL BEARING PRESSURE AFTER COMPACTION: 2000 PSF <br />SEE SOILS REPORT AND SPECIFICATIONS FOR COMPACTION REQUIREMENTS <br />IF SOIL CONDITIONS IN THE PROJECT DO NOT MEET OR EXCEED THE CAPACITY <br />THE GENERAL CONTRACTOR SHALL CONTACT THE ENGINEER PRIOR TO <br />FOUI\DATION POUR FOR VERIFICATION OF FOUNDATION DESIGN. <br /> <br />SOIL BEARING <br />VALUE: <br /> <br />BUILDING DATA <br /> <br />CONSTRUCTION TYPE - TYPE VI UNPROTECTED <br />(SECTION 608 - FBC 2001) <br />MEAN ROOF 15 FT. HIGH <br />TYPICAL FOR SINGLE HOMES <br /> <br />WIND SPEED 123 MPH (3 SEC. GUST) <br />WIND IMPORTANCE FACTOR - (Iw) == 1,0 <br />WIND EXPOSURE -- "B" (FBC 1606.1.8) <br />INTERNAL PRESSURE COEFFICIENT == +/- 0.55 (PARTIALLY <br />ENCLOSED BLDG) <br /> <br />WOOD CONSTRUCTION <br /> <br />1, WOOD CONSTRUCTION SHALL CONFORVI TO THE NFPA <br />"NATIONAL DESIGN SPECIFICATION FOR WOOD <br />CONSTRUCTION", LATEST EDITION. <br />2. ALL EXTERIOR WOOD STUD WALLS, BEARING WALLS, SHEAR <br />WALLS AND MISC. STRUCTURAL WOOD FRAMING MEMBERS, <br />( I.E. BLOCKING OR GABLE END BRACING) SHALL BE EITHER <br />SOUTHERN PINE, OR S,P,F. NUMBER 2 GRADE SHALL BE <br />USED REGARDLESS OF SPECIES, <br /> <br />DESIGN WIND PRESSURE: <br /> <br />(COMPONENT AND CLADDING) WORST CASE (10 SF - END ZONE) <br />WINDOWS AND DOORS <br />123 MPH + 38 PSF / - 40 PSF <br /> <br />GARAGE DOORS (V = 123 MPH) <br />SINGLE 9x7 +37.0 PSF / -40.0 PSF <br />DOUBLE 16x7 +37.0 PSF / -41,0 PSF <br /> <br />SEE FLOOR PLAN FOR ACTUAL PRESSURES <br /> <br />ALL \VORK SHALL COMPLY WITH ALL <br />PREVAILING CODES, FLORIDA BUILDn~(j <br />CODE, NATIONAL ELECTRlC CODE AND <br />CrfY OF ZEPHYRHILLS ORDINANCES <br /> <br /> <br />ENGINEERED PLANS <br />ON FILE <br /> <br />REVIEWED <br />MAY 0 9 2005 <br /> <br />~i5~ <br /> <br />WALDEN GRANDE 2003 STEM WALL <br /> <br />GENERAL NOTES: <br /> <br />THE FOLLOWING TECHINCAL CODES <br />SHALL APPLY: <br />2001 FLORIDA BUILDING CODE, <br />WITH 2003 REVISIONS <br />PLUMBING, MECHANICAL, FUEL GAS, <br />ENERGY EFFICIENCY, ACCESSIBILITY, <br />AND NFPA 70-02 NATIONAL ELECTRICAL CODES <br /> <br />l <br />/i' <br /> <br />1. TANK TYPE WATER CLOSET VOLUME <br />1.6 GALLONS <br />2. WALL MOUNT WATER CLOSET VOLUV1E <br />3.5 GALLONS <br />3, WATER, FLOW RATE, <br />PUBLIC FACILITIES 0.5 G.P.M. <br />PRIVATE FACILITIES 2,2 G,P.M, <br />SHOWER HEADS 2.5 G.P.M. <br />4. ALL WATER LINE PLUMBING <br />TO BE PVPC <br />VTR LOCATIONS ARE APPROXIMATE <br />AND MAY CHANGE DUE TO JOBSITE <br />CONDITIONS <br /> <br />THE FOLLOWING SHALL COMPLY <br />WITH THE 2001 FBC. <br /> <br />o PORCHES AND BALCONIES <br />SECTION 1014 <br />o HANDRAILS - SECTION 1007.5 <br />o GUARDRAILS - SECTION 1015, 1019.9 <br />o STAIRS - SECTION 1007 <br />o CHIMNEY & FIREPLACE <br />SECTION 2804-2806 (MFGR) <br />SECTION 2113-2114 (MAS) <br />o EGRESS WINDOWS <br />SECTION 1005.4 <br /> <br />5. ALL OPENII\GS SHALL COMPLY WITH <br />2001 FBC WIND LOADS AS STATED <br />BELOW, ATTACHMENTS OF WINDOWS, <br />DOORS, SLIDING GLASS DOORS <br />AND O,H. GARAGE DOORS ARE TO DELEGATED <br />THE MANUFACTURER OF THESE ITEMS, THE <br />MANUFACTURER OF THESE ITEMS <br />SHALL SUBMIT ATTACHMENTS FOR <br />SITE INSTALLATION. <br /> <br />SEE ATTACHED SPECIFICATION SHEETS FOR <br />MANUFACTURERS DESIGN CRITERIA AND <br />INSTALLATION METHODS FOR WINDOWS, <br />DOORS, SLIDING GLASS DOORS, OVERHEAD <br />GARAGE DOORS, AND ROOFING. <br /> <br />6. Ai..L DOORS INTERIOR & EXTERIOR ARE <br />6'-8" UNLESS OTHERWISE NOTED <br />ALL SHOWER EI\CLOSURES TO BE <br />TEMPERED GLASS <br />7. ALL WINDOWS WITHIN 24" OF DOORS <br />(INTERIOR & EXTERIOR) Ar--.D WITHIN <br />18" OF FLR TO BE TEMPERED GLASS. <br />(SECTION 2405,2) <br /> <br />SHT NO: <br />1 <br />2 <br />2A <br />3 <br />4 <br />5 <br />6 <br />S-1 <br />S-2 <br />S-3 <br />S-4 <br />S-5 <br />S-6 <br />S-7 <br /> <br />S-8 <br />S-9 <br />S-10 <br />S-11 <br />S-12 <br />S-13 <br />S-14 <br />S-15 <br />S-16 <br />S-17 <br />S-18 <br /> <br />INDEX OF DRAWINGS <br /> <br />TITLE <br />COVER SHEET <br />FLOOR PLAN <br />DIMENSION PLAN <br />FOUNDATION PLAN <br />ELECTRICAL PLAN/ INT. ELEV. <br />ELEVATIONS <br />TRUSS LAYOUT <br />MASONRY DETAILS <br />LINTEL PLAN AND DETAILS <br />DETAILS <br />DET AI LS <br />DETAILS <br />DETAILS <br />STRUC. NOTES & <br />HANGER INFORMATION <br />DETAILS <br />DETAILS <br />ROOFING DETAILS <br />DETAILS <br />DETAILS <br />PRODUCT APPROVAL <br />WINDOW DETAILS <br />WINDOW DETAILS <br />DET AI LS <br />DET AI LS <br />DETAILS <br /> <br />NOTICE TO BUILDER <br /> <br />IT IS THE INTENT OF THIS DESIGNER THAT <br />THESE PLANS ARE ACCURATE AND ARE <br />CLEAR ENOUGH FOR THE LICENSED PROFESS- <br />ONAL TO CONSTRUCT THIS PROJECT, <br />IN THE EVENT THAT SOMETHING IS UNCLEAR <br />OR NEEDS CLARIFICATION..STOP..AND CALL <br />THE DESIGNER LISTED IN THIS TITLE PAGE, IT <br />IS THE RESPONSIBILITY OF THE LICENSED <br />PROFESSIONAL THAT IS CONSTRUCTING THIS <br />PROJECT TO FULLY REVIEW THESE DOCUMENTS <br />BEFORE CONSTRUCTION BEGINS AND ANY AND <br />ALL CORRECTIOI\JS, IF NEEDED, TO BE MADE <br />BEFORE ANY WORK IS DONE. <br /> <br />l.LJ <br />() <br />f- <br />a <br />z <br />w <br />~ <br />~ <br />a <br />a <br />L.l.. <br />l.LJ <br />0:: <br />~ <br />::) <br />o <br />C/) <br /> <br />w <br />~ <br />LL.<l:0:: <br />'00::0 <br />W LL.LL. <br />~W"",f- <br />O..,:::;Z <br />~-O::) <br />X~O::O <br />o::)LL.u <br />O::OZU <br />a.."",w<l: <br />a....,:::;~,-- <br /><l:O<l:Q <br />wO::f-z <br />o::LL.w <br /><l:zo::o <br />ow<l:O <br />W~(/)o <br />f-<l:zz <br />of-o<l: <br />::)w-w <br />oo::(/)~ <br />'" <l: Z . <br />W(/)W<l:z <br />,-,z~B:Q <br /><l:000f- <br />5cnO::f-() <br />o~o~:J <br />LL."",o::ua.. <br />w..,:::;wOa.. <br />O::Of-CiS<l: <br /><l:...JZ ...J <br />::) ...J -. 0:: ...J <br />R <l: (/) 0 <l:~ <br />VI 0:: ...J "'- <br />...Jw...JO <br />...J>~ZO:: <br /><l:0:><l:0 <br /> <br />(/) <br />Q,)Q)...J <br />cn1a~ <br />Q,)._ 0 <br />Q,)(,)(/) <br />~ ~ ~ <br />I (/)0 <br />cncu[ <br />Q,)c8 <br />- 'OJ) u: <br />ca.- - <br />..(/)b:: <br />oQ)w <br />e'au <br /> <br /> <br />. <br />w '-' 000 <br />:r: ~ N Z <br />f-. (/) 3: <D <br />,-,Zw <l:<D~ <br />(/)~Qo O::N<D u) <br />. of-O O~'*I: Z <br />ffiz()u w~~Li 0 <br />w~u:'-' :r::r:'*I:. ~ <br />~(/)-z f-f-...ILLI :J <br />'-'0::&30 0::LL.L&.Q. ..J <br />ZWa.....J 00.. 0 <br />WO(/)-(/)LL.ZLLlZ (I) <br />z::) Q.LL1 <br />W (/)a::lZOO Q Z <br />:r:::)zwQ::Ji=zo: <br />f-0:s:r:(/)<l:0::3:) ~ <br />6za..f->w~oa:l Vi <br /><l: :r: w (/) 0:' IJJ <br />f-w...Jf-O::o...JQ3.... C <br />~g~~MZ~...:u:l <br />a::lw::) O<l:::)....c:c < <br />w...Jf-~~Of-...I:c C <br />:r:>Ua.. wUO:O ;::;:; <br />f-:>::)~IZ::)c:c- ... <br />o~~ot::~~o:E 0 <br />f- ~ (/) u 3: (/) (/)DD Li <br /> <br /> <br />~~ <br />1Q c:::::J 0 <br />~ <X: CO <br /> <br />(/) <br />w <br />o <br />'-' <br />z <br />o <br />...J <br />::) <br />co <br /> <br />...J <br />~ <br />0:: <br />f- <br />~ <br />o <br />(/) <br />(/) w <br />o U <br />...J M u: >< <br />co 0 LL. <l: <br />w r-- 0 LL. <br />'-' N M <;j" <br />zM MO <br /><l: ...J M M <br />0:: LL. ~ ~ <br />o . 00 <br />'~oooo <br />(/) a.. 00 00 <br />Lfl 0 r-:. r-:. <br /><;j" a.. 00 <br />(j) <l: <;j" <;j" <br /> <br /> <br />~ <br />E <br />o <br />(/) <br />(/) LL. ' <br />.2MLflt3..- <br />COONZ <br />~~ ~ w 6 <br />eM' ...J w <br />~...J~~f- <br />OLL.oo::)<l:M <br />. (iir-:..f-~(!) <br />(/)~OU!:!::M w <br />n. <;j" ::) f- (j) f- <br />MO 0::0::'..... <br />Lfl n.:r: f- w 0 .... <br />(j) <l: a.. (/) U Z 0 <br /> <br />Lfl <br />o <br />o <br />N <br /> <br />o <br />o <br />1.0 <br />W <br />I- <br />- 0 <br />::J q <br />Z Ul .... L" <br />o Q .... L" <br />- > I l\1 <br />Ul ~ (]'I III <br />- [!] 0 I <br />> 1.0 (]'I <br />OWMI.O <br />~ML" <br />~ 0 I <br />D.I~M <br />Ul lL. .... <br />I I- ~ OJ <br />~ Ul !l I <br />I- W .... <br />~ ~ <br />.1- <br />Z <br />o <br />o <br />1.0 <br /> <br />o <br />Z W <br />"cnZ <br />U;I:S:? 0 <br />Wf-cnW:::i <br />oZcn=,<t <br />oO-I:> <br />z::;;;t:=s;cn <br /><tC\iWO::~ <br />"r-I~Oo <br />~O::OoO <br />S;OWWU <br /><tLL. -'f- <br />o::O~~z <br />O:::io::cn~ <br />~;:;~OO:: <br />I: LL.Z::.J <br />f-~<t<tU <br /> <br /> Lfl <br /> C'.J(/) 0 <br /> "'- <br /> M <br /> 'Z U"'- <br /> ~O f-M <br /> <l:a.. <br /> C'.J- (j)0 <br /> ...-j(/) Lfl"'- <br /> > <;j"<l: <br /> MO <br /> W '~ <br /> 0:: ~~ <br />0 llJ-I <br />(j) ~ <br />(J) 0-1 w 0 <br />0 0:: <br /> z<X: () >-LL.Z <br />.....J Zf-O <br />0 <($ <l:Z- <br />.....J f- zw~ <br /> -(/)> <br />I o:::~ 0 OZO <br />C\J - t50<l: <br />:c z ::)UO <br />L() '-9llJ OZo:: <br /> owo <br /> f- o::f-...J <br />I $ Zl- a..t::LL. <br />I'- I wO::...J <br /> llJC/) 0::3:<l: <br /> wwO:: <br />~ lLJ wO(Y) ~ a::lIf- <br />f-f-~ <br /> Of-U <br />~ - ~-IO 0:: z::) . <br />> >-On.. <br />LD ~ <( 0 >- <l:IO:: <br />~t::0 <br />I- Z$ N Q.. z3:u <br />~ :so::w <br />(J) a w~ <br />::5 a..zo <br /> (/)ZI <br />>- llJ Q.. () -<l:(/) <br /> 2=~::) <br />0::: 0::: SHEET NO, a.. <br /> 0:: <br />U 0 <br />0 1 U <br /> w <br />I- 0 ~ <br /> 0 <br /> OF I <br />Z (/) <br />(j) 25 ::) <br /> M <br />W 0 <br />I- 0 <br />> LAST PLOT DATE N <br /> @ <br />0 March 01, 2005 <br />Z <br />.....J COVER SHEET <br />- <br />