<br />The MS-5012 provides regulated power for operating the fire alarm control panel, operating external devices, and <br />operating the standby battery. The power for operating external devices is limited. Use Table A-1 (standby or <br />nonalarm) and Table A-2 (alarm) to determine if external loading is within the capabilities of the power supply. <br /> <br />Table A-1: Regulated Load in Standby @12VDC <br /> <br />Device Type # of Devices Current Total Current <br /> (Amps) (Amps) <br />Main Circuit Board 1 X 0.074 = 0.074 <br />ADM-12 (1 max.) X 0.012 = <br />RZA-5F (1 max.) X 0.012 = <br />2-wire Detector Heads [ ] X [ ] = <br />4-wire Detector Heads [ l ] X [ ] = , I(JO .l. .;-. <br />Power Supervision 2 [ ] X 0.025 = <br />Relays <br />Auxiliary Outputs: <br />TB3-4 Alarm (1 max.) X 0 = <br />TB3-5 Trouble (1 max.) X o.04d = <br />TB3-6 Supervisory (1 max.) X 0 = <br />TB3-7 Comm. Fail (1 max.) X 0 = <br />Additional Current <br />Draw from TB-3 = <br />(non alarm) <br /> Sum Column for Standby Load = . ()7 5" Amps <br /> <br />Note: <br /> <br />1. Current draw only if End-of-Line relay is installed between TB3-3 and TB3-5. Current shown is maximum <br />available from TB3 Terminal 5. <br />2. Use compatible listed power supervision relay only. <br />3. Refer to Device Compatibility Document for 2-wire smoke detector standby current. <br /> <br />60 <br /> <br />15465 Rev F 512197 PIN 15465:F <br />