Laserfiche WebLink
<br />Zephyrhills Fire Rescue <br />6907 Dairy Road, Zephyrhills, FL 33542 <br /> <br />Fire Marshal <br />Kerry Barnett <br /> <br />Bus (813) 780-0041 <br />Fax (813) 780-0044 <br /> <br />March 12,2008 <br /> <br />Plan Review Comments <br /> <br />I have reviewed and approved the 2nd revised plans for an interior remodel located at <br />38449 - 38453 CR 54E under the following conditions. My comments have been placed <br />below. Please contact me if you have any questions with regards to my comments. <br /> <br />1. One may not exit through a storage related room. The storage room will have to <br />have a wall separating itself from the egress corridor. See plans. <br />2. All penetrations in firewall shall be properly sleeved and fire caulked with an UL <br />approved material. Wall shall be caulked at roof deck and it shall also be labeled <br />"FIREWALL - DO NOT PENETRATE" <br />3. Add exit light above door entering the egress corridor. <br />4. All previous comments from original review (September 24th, 2007) still apply. <br /> <br />Inspections Required: <br /> <br />1. Firewall shall be inspected. Each layer shall have a screw inspection and then an <br />over all final. <br />2. Building Final. <br />