<br />TERMITE SPECIFICATIONS: <br /> <br />1. A PERMANENT SIGN WHICH IDENTIFIES THE TERMITE TREATMENT PROVIDER <br />AND NEED FOR RE-INSPECTION AND TREATMENT CONTRACT RENEWAL SHALL <br />BE PROVIDED. THE SIGN SHALL BE POSTED NEAR THE WATER HEATER OR <br />ELECTRIC PANEL.(FBC 104.2.6) <br /> <br />2. CONDENSATE AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1'-0" <br />AWAY FROM BUILDING SIDE WALKS.(FBC 1503.4.4) <br /> <br />3. IRRIGATION/SPRINKLER SYSTEMS INCLUDING ALL RISERS AND SPRAY HEADS <br />SHALL NOT BE INSTALLED WITHIN 1'-0" OF THE BUILDING SIDE WALLS.(FBC 1503.4.4) <br /> <br />4. TO PROVIDE FOR INSPECTION FOR TERMITE INFESTATION, BETWEEN WALL <br />COVERING AND FINAL EARTH GRADE SHALL NOT BE LESS THAT 6 Ii\CHES. <br /> <br />EXCEPTION: PAINT OR DECORATIVE CEMENTATIOUS FINISH LESS THAN 5/8" <br />THICK ADHERED DIRECTLY TO THE FOUNDATION WALL.(FBC 1403.1.6) <br /> <br />5. INITIAL TREATMENT SHALL BE DONE AFTER ALL EXCAVATION AND BACKFILL <br />is COMPLETE.(FBC 1816.1.1) <br /> <br />6. SOIL DISTURBED AFTER THE INITIAL TREATMENT SHALL BE RETREATED <br />INCLUDING SPACES BOXED AND FORMED.(FBC 1816.1.2) <br /> <br />7. BOXED AREAS IN CONCRETE FLOORS FOR SUBSEQUENT INSTALLATION OF TRAPS, <br />ETC., SHALL BE MADE WITH PERMANENT METAL OR PLASTIC FORMS. PERMANENT <br />FORMS MUST BE OF A SIZE AND DEPTH THAT WILL ELIMINATE THE DISTURBANCE OF <br />SOIL AFTER THE INITIAL TREATMENT.(FBC 1816.1.3) <br /> <br />8. MINIMUM 6 MIL VAPOR RETARDER MUST BE INSTALLED TO PROTECT AGAINST RAIf\FALL <br />DILUTION. IF RAINFALL OCCURS BEFORE VAPOR RETARDER PLACEMENT, RETREATMENT is <br />REQUIRED.(FBC 1816.1.4) <br /> <br />9. CONCRETE OVERPOUR AND MORTAR ALONG THE FOUNDATION PERIMETER MUST BE <br />REMOVED BEFORE EXTERIOR SOIL TREATMENT.(FBC 1816.1.5) <br /> <br />10. SOIL TREATMENT MUST BE APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE <br />WITHIN 1'-0" OF THE STRUCTURE SIDEWALLS.(FBC 1816.1.6) <br /> <br />'i:: <br /> <br />11. AN EXTERIOR VERTICAL CHEMICAL BARRIER MUST BE INSTALLED AFTER CONSTRUCTION <br />IS COMPLETE INCLUDING LANDSCAPING AND IRRIGATION. AIW SOIL DISTURBED AFTER <br />THE VERTICAL BARRIER is APPLIED, SHALL BE RETREATED.(FBC 1816.1.6) <br /> <br />12. ALL BUILDINGS ARE REQUIRED TO HAVE PRE-CONSTRUCTION TREATMENT.(FBC 1816.1.7) <br /> <br />13. A CERTIFICATE OF COMPLIANCE MUST BE ISSUED TO THE BUILDII\G DEPARTMENT <br />BY A L1CE,'JSED PEST CO'JTROL COMPANY BEFORE A CERTIFICATE OF OCCUPAi\CY <br />WILL BE iSSUED. THE CERTIFICATE OF COMPLIANCE SHALL STATE: "THE BUILDING <br />HAS RECEIVED A CO~PLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN <br />TERMITES. THE TREATMENT IS IN ACCORDANCE WITH THE RULES AND LAWS OF THE <br />FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER SERVICES."(FBC 1816.1.7) <br /> <br />14. AFTER ALL WORK IS COMPLETED, LOOSE WOOD AND FILL MUST BE REMOVED FROM <br />BELOW AND WITHIN 1'-0" OF THE BUILDING. THIS INCLUDES ALL GRADE STAKES, <br />TUB TRAY BOXES, FORMS, SHORING OR OTHER CELLULOSE CONTAINING MATERIAL. <br />(FBC 2303.1.3) <br /> <br />15. NO WOOD, VEGETATION, STUMPS, CARDBOARD, TRASH, ETC., SHALL BE BURIED <br />WITHIN 15'-0": OF ANY BUILDING OR PROPOSED BUILDING,(FBC 2303.1.4) <br /> <br />A.B. <br />Abv. <br />A/C <br />Adj. <br />A.F.F. <br />A.H.U. <br />ALT. <br />B.C. <br />B.F. <br />Bk Sh <br />Bm. <br />BOT. <br />B.P. <br />Brg. <br />Cir. <br />clg. <br />Col. <br />,. Compo <br />C.T. <br />D <br />Dec. <br />Ded. <br />Dbl. <br />Dia. <br />Disp. <br />Dist. <br />D.S. <br />D.V. <br />DW. <br />Ea. <br />EW. <br />Elec. <br />Elev. <br />Ext. <br />Exp. <br /> <br />ABBREVIA TIONS <br /> <br />Anchor Bolt <br />Above <br />Air-Conditioner <br />Adjustable <br />Above Finished Floor <br />Air Handler Unit <br />Alternate <br />Base Cabinet <br />Blfold Door <br />Book Shelf <br />Beam <br />Bottom <br />Bypass door <br />Bearing <br />Circle <br />Ceiling <br />Column <br />A/C Compressor <br />Ceramic Tile <br />Dryer <br />Decorative <br />Dedicated Outlet <br />Double <br />Diameter <br />Disposal <br />Distance <br />Drawer Stack <br />Dryer Vent <br />Dishwasher <br />Each <br />Each Way <br />Electrical <br />Elevation <br />Exterior <br />Expansion <br /> <br />F.B.C. <br />Fin. Fir. <br />F.G. <br />Fir. <br />Fdn. <br />Fir. Sys. <br />F.PI. <br />Ft. <br />Ftg. <br />FX <br />Galv. <br />G.C. <br />G.F.I. <br />G.T. <br />Hdr. <br />Hgt. <br />HB <br />Int. <br />K/Wall <br />K.S. <br />Laun. <br />Lav. <br />L.F. <br />L.T. <br />Mas. <br />Max <br />M.C. <br />Mfgr. <br />Micro. <br />Min <br />M.L. <br />Mir. <br />Mono <br />N.T.S. <br /> <br />Florida Bldg. Code <br />Finished Floor <br />Fixed Glass <br />Floor <br />Foundation <br />Floor System <br />Fireplace <br />Foot / Feet <br />Footing <br />Fixed <br />Galvanized <br />General Contractor <br />Ground Fault Interrupter <br />Girder Truss <br />Header <br />Height <br />Hose Bibb <br />Interior <br />Kneewall <br />Knee Space <br />Laundry <br />Lavatory <br />Li near Ft. <br />Laundry Tub <br />Masonry <br />Maximum <br />Medicine Cabinet <br />Manufacturer <br />Microwave <br />Minimum <br />Microlam <br />Mirror <br />Monolithic <br />Not to Scale <br /> <br />Opn'g. <br />Opt. <br />Pc. <br />Ped. <br />P.L. <br />PLF <br />PIt. Ht. <br />Pit Sh. <br />PSF <br />P.T. <br />Pwd. <br />Rad. <br />Ref. <br />Req'd. <br />Rm. <br />Rnd. <br />R/SH <br />SD. <br />S.F. <br />Sh. <br />SHT <br />S.L. <br />S.P.F. <br />Sq. <br />S.Y.P. <br />Temp. <br />Thik'n. <br />T.O.B. <br />T.O.M. <br />T.O.P. <br />Trans. <br />Typ. <br />UCL <br />U.N.O. <br />VB <br />Vert. <br />V.L. <br />VTR <br />W <br />W/ <br />W/C <br />W.A. <br />Wd <br />WP <br /> <br />MASTER REVISIONS <br /> <br />DATE <br /> <br />DESCRIPTION <br /> <br />Opening <br />Optional <br />Piece <br />Pedestal <br />Parallam <br />Pounds per linear foot <br />Plate Height <br />Plant Shelf <br />Pounds per square foot <br />Pressure Treated <br />Powder Room <br />Radius <br />Refrigerator <br />Required <br />Room <br />Round <br />Rod and Shelf <br />Smoke Detector <br />Square Ft. <br />Shelves <br />Sheet <br />Side Lights <br />Spruce P:ne Fir <br />Square <br />Southern Yellow Pine <br />Tempered <br />Thicken <br />Top of Block <br />Top of Masonry <br />Top of Plate <br />Transom Window <br />Typical <br />Under Cabinet Lighting <br />Unless Noted Otherwise <br />Vanity Base <br />Vertical <br />Versalam <br />Vent through Roof <br />Washer <br />With <br />Water Closet <br />Wedge Anchor <br />Wood <br />Water Proof <br /> <br />STRUCTURAL NOTES: <br /> <br />STRUCTURAL DESIGN CRITERIA <br /> <br />FOUNDATIONS <br /> <br />3. ANY WOOD FRAME INTERIOR BEARING WALL STUDS THAT <br />HAVE HOLES IN THE CENTER OF THE STUD UP TO 1" DIA. <br />SHALL HAVE STUD PROTECTION <br />SHIELDS FOR ALL HOLES OVER 1" IN DIA. <br />FOR PLUMBING LINES, ETC. SHALL BE REPAIRED WITH <br />SIMPSON HSS2 STUD SHOES,TYP., U.N.O. <br /> <br />CODES: <br /> <br />FLORIDA BUILDING CODE, 2001 EDITION WITH 2003 REVISIONS <br />BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE (ACI 318-02) <br />SPECIFICATIONS FOR STRUCTURAL CONCRETE BUILDINGS (ACI 301-02) <br />BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES (ACI 530-02) <br />NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION, 2001 EDITION <br />APA PLYWOOD DESIGN SPECIFICATION <br /> <br />SOIL TO BE COMPACTED TO AT LEAST 95% <br />OF MAX. DRY DENSITY AS DETERMINED BY <br />ASTM - 1557 ( MODIFIED PROCTOR) <br /> <br />FOUNDATION INSPECTIONS <br /> <br />A FOUNDATION SURVEY SHALL BE PERFORMED AND A <br />COpy OF THE SURVEY SHALL BE ON SITE FOR THE BUILDING <br />INSPECTORS USE, OR ALL PROPERTY MARKERS SHALL BE <br />EXPOSED AND A STRING STRETCHED FROM MARKER TO <br />MARKER TO VERIFY REQUIRED SETBACKS. <br />CAST IN PLACE CONCRETE <br />1. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE <br />STRENGTH AT 28 DAYS OF 3000 PSI, A SLUMP OF 6" <br />PLUS OR MINUS 1", AND HAVE 2 TO 5% AIR ENTRAINMENT, <br />AND A MAXIMUM WATER/CEMENT RATIO OF 0.63 <br />2. ALL REINFORCING STEEL SHALL BE NEW DOMESTIC <br />DEFORMED BILLET STEEL CONFORMING TO ASTM A-615 <br />GRADE 40. <br />3. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185. <br />WWF SHALL BE LAPPED AT LEAST 6" AND CONTAIN AT <br />LEAST ONE CROSS WIRE WITHIN THE 6". <br />4. HOOKS SHALL BE PROVIDED AT DiSCONTINUOUS ENDS OF <br />ALL TOP BARS OF BEAMS. <br />5. HORIZONTAL FOOTING BARS SHALL BE BENT 1'-0" <br />AROUND CORNERS OR CORNER BARS WITH A 2'-0" <br />LAP PROVIDED <br />6. MINIMUM LAP SPLICES ON ALL REINFORCING BAR <br />SPLICES SHALL BE 40 BAR DIAMETERS TYP. <br />7. CONCRETE COVER MIN. 3" WHEN EXPOSED TO EARTH OR <br />11/2" TO FORM <br /> <br />WOOD FRAMING INSPECTION <br /> <br />LIVE LOADS: <br /> <br />ROOF <br />RESIDENTIAL FLOOR, UNLESS OTHERWISE INDICATED <br />BALCONIES <br />STAIRS <br />LIGHT PARTITIONS (DEAD LOAD), U.N.O. <br /> <br />WIND LOADS BASED ON FBC, SECTION 1606.2. <br />WIND VELOCITY: 123 M.P.H., USE FACTOR: 1.0 <br /> <br />20 PSF (REDUCIBLE) <br />40 PSF <br />40 PS F <br />40 PSF <br />20 PSF <br />10 PSF ATTIC L.L. <br /> <br />ALL PLUMBING, ELECTRICAL, AND MECHANICAL <br />ROUGH-INS MUST BE COMPLETE, INSPECTED <br />AND APPROVED BEFORE REQUESTlI\G FRAMING <br />INSPECTION. <br /> <br />PREFABRICATED WOOD TRUSSES <br /> <br />1. ALL PREFABRICATED WOOD TRUSSES SHALL BE SECURELY <br />FASTENED TO THEIR SUPPORTING WALLS OR BEAMS WITH <br />HURRICANE CLIPS OR ANCHORS. <br />2. PREFABRICATE WOOD TRUSSES SHALL BE DESIGNED IN <br />ACCORDANCE WITH THE LATEST EDITION OF THE "NATIONAL <br />DESIGN SPECIFICATION FOR STRESS-GRADE LUMBER AND <br />ITS FASTENERS" AS RECOMMENDED BY THE NATIONAL <br />FOREST PRODUCTS ASSOCIATION. <br />3. TRUSS MEMBERS AND CONNECTIONS SHALL BE PROPOR- <br />TIONED ( WITH A MAXIMUM ALLOWABLE STRESS INCREASE <br />FOR LOAD DURATION OF 25%) TO WITHSTAND THE LIVE <br />LOADS GIVEN IN THE NOTES AND TOTAL DEAD LOAD. <br />4. BRIDGING FOR PRE-ENGINEERED TRUSSES SHALL BE AS <br />REQUIRED BY THE TRUSS MANUFACTURER UNLESS <br />NOTED ON THE PLANS. <br />5. TRUSS ELEVATIONS AND SECTIONS ARE FOR GENERAL <br />CONFIGURATION OF TRUSSES ONLY. WEB MEMBERS ARE <br />NOT SHOWN, BUT SHALL BE DESIGNED BY THE TRUSS <br />MANUFACTURER IN ACCORDANCE WITH THE FOLLOWING <br />DESIGN LOADS: <br />6. DESIGN SPECIFICATIONS FOR LIGHT WEIGHT METAL <br />PLATE CONNECTED WOOD TRUSSES PER THE TRUSS <br />PLATE INSTITUTE TPI LATEST EDITION. <br />7. PRE-ENGINEERED WOOD TRUSSES SHALL BE DESIGNED BY <br />THE MANUFACTURER IN ACCORDAI\CE WITH SPECIFIED LOADS <br />AND GOVERNING CODES. SUBMITTALS SHALL INCLUDE TRUSS <br />FRAMING PLANS AND DETAILS SHOWING MEMBER SIZES, <br />BRACII\G, ANCHORAGE, CONNECTIONS, TRUSS LOCATIONS, AND <br />AND PERMANENT BRACING AND/OR BRIDGING AS REQUIRED <br />FOR ERECTION AND FOR THE PERMANENT STRUCTURE. EACH <br />SUBMITTAL SHALL BE SIGNED AND SEALED BY A FLORIDA <br />REGISTERED STRUCTURAL ENGINEER. SUBMIT 3 COPIES FOR <br />REVIEW AND APPROVAL PRIOR TO FABRICATION. <br />8. THE TRUSS MANUFACTURER SHALL DETERMINE ALL SPANS <br />WORKII\G POINTS, BEARING POINTS, AND SIMILAR CONDITIONS. <br />TRUSS SHOP DRAWINGS SHALL SHOW ALL TRUSSES, ALL <br />BRACING MEMBERS, AND ALL TRUSS TO TRUSS HANGERS. <br /> <br />WIND LOADS: <br />(F.B.C.) <br /> <br />CONCRETE <br />STRENGTH <br />@ 28 DAYS <br /> <br />ALL CONCRETE UNLESS OTHERWISE INDICATED <br />PEA GRAVEL CONCRETE FOR MASONRY CELLS ONLY <br />(DO NOT USE FOR CONCRETE COLUMNS OR TIE BEAMS) <br /> <br />3000 PSI <br />3000 PSI <br /> <br />REINFORCING: <br /> <br />WELDED WIRE FABRIC SHALL CONFORM TO <br />ALL REINFORCING BARS <br />ALL STIRRUPS AND TIES <br /> <br />ASTM A185 <br />ASTM A615-40 40,000 PSI <br />ASTM A615AO 40,000 PSI <br /> <br />CONCRETE <br />MASONRY <br />UNITS: <br /> <br />ASTM C90-99b, STANDARD WEIGHT UNITS, fm=1500 PSI <br />MORTAR TYPE "S" 1800 PSI <br />CONCRETE GROUT 3000 PSI <br />CONTINUOUS MASONRY INSPECTION IS REQUIRED DURING CONSTRUCTION <br /> <br />ALL STRUCTURAL AND MISCELLANEOUS STEEL A36 36,000 PSI, U.N.O <br />SHOP AND FIELD WELDS: E70XX ELECTRODES <br />ALL BOLTS CAST IN CONCRETE: ASTM A36 OR ASTM A-307 <br /> <br />BEAMS, RAFTERS, jOiST, PLATES, ETC. U.N.O. <br />1\0. 2 SOUTHERN YELLOW PINE (19% M.C.) <br />ROOF DECK: PLYWOOD C-C/C-D, EXTERIOR, or OSB <br />FLOOR SHEATHING: T&G A-C GROUP 1 APA RATED (48/24) <br />WALL SHEATHING: PLYWOOD C-C/C-D, EXTERIOR OR OSB <br />VERSA LAM BEAM Fb = 2900 PSI (2.0E) <br />WOOD COLS. PARALLAM 2.0E U.N.O. <br /> <br />DESIGN LOADS: <br />TOP CHORD LIVE LOAD: 20 PSF <br />TOP CHORD DEAD LOAD: 10 PSF <br /> <br />STRUCTURAL <br />STEEL: <br /> <br />REINFORCING STEEL <br /> <br />ALL REINFORCING STEEL SHALL BE NEW DEFORMED BARS <br />FREE FROM RUST, SCALE & OIL & SHALL MEET ASTM A-615 <br />REIr-..FORCING FOR FOOTING SHALL BE SUPPORTED ON PRE- <br />CAST CONCRETE PADS, TOP REINFORCING SHALL BE <br />POSITIVELY SUPPORTED BY TEMPORARY STRINGERS. <br />DOWELS FOR COLUMNS & FILLED CELLS SHALL BE SECURED <br />IN PLACE BY USING ADDITIONAL CROSS- REINFORCING TIED <br />TO FOOTING REINFORCING. SPLICES IN REIMORCING WHERE <br />PERMITTED SHALL BE THE FOLLOWING MINIMUM, UNLESS <br />OTHERWiSE INDICATED ON THE DRAWII\GS: <br /> <br />FTGS, WALLS, COLUMNS, BEAMS, SLABS: 36 DIA. OR 2'-0" MIN., WHICHEVER is MORE. <br />FILLED CELL REINFORCING: 40 DIA. OR 2'-0" MIN., WHICHEVER is MORE. <br />TEMPERATURE REINFORCING: 20 DIA. OR 1'-0" MIN., WHICHEVER IS MORE. <br />WELDED WIRE MESH: 8" LAP <br /> <br />WOOD FRAMING: <br /> <br />WOOD ROOF <br />TRUSSES: <br /> <br />BOTTOM CHORD DEAD LOAD: <br /> <br />10 PSF <br />40 PS F <br /> <br />10 PSF <br /> <br />BOTTOM CHORD ATTIC LIVE LOAD: <br /> <br />SEE DRAWINGS FOR SPECIAL CONCENTRATED LOADS. DESIGN <br />FOR NEW WIND UPLIFT AS PER SPECIFIED CODES, DEDUCTING <br />A MAXIMUM OF 5 P.S.F. DEAD LOAD, BUT NOT EXCEEDING ACTUAL <br />DEAD LOAD. <br /> <br />DESIGN LOADS: <br />DEAD LOAD: <br />LIVE LOAD: <br />TOTAL: <br /> <br />MASONRY WALL CONST. <br />1. HOLLOW LOAD BEARING UNITS SHALL BE NORMAL <br />WEIGHT, GRADE N, TYPE 2, CONFORMING TO ASTM C90, <br />WITH A MINIMUM NET COMPRESSIVE STRENGTH OF <br />1900 PSI ( f'm = 1500 PSI) <br />2. MORTAR SHALL BE TYPE "S", CONFORMING TO <br />ASTM C270. <br />3. COARSE GROUT SHALL CONFORM TO ASTM C476 WITH A <br />MAXIMUM AGGREGATE SIZE OF 3/8" AND A MINIMUM <br />COMPRESSIVE STRENGTH OF 3000 PSI SLUMP 8" TO 11". <br />4. VERTICAL REIr-..FORCEMENT SHALL BE AS NOTED ON THE <br />DRAWINGS WITH THE CELLS FillED WITH COARSE GROUT. <br />5. VERTICAL REINFORCEMENT SHALL BE HELD IN POSITION <br />AT THE TOP AND BOTTOM AND AT A MAXIMUM SPACING <br />OF 192 BAR DIAMETERS. REINFORCEMENT SHALL BE PLACED <br />IN THE CENTER OF THE MASONRY CELL TYPICAL UNLESS <br />OTHERWiSE! NOTED. <br />6. REINFORCING STEEL SHALL BE LAPPED A MINIMUM OF 40 BAR <br />DIAMETERS, Ui\LESS OTHERWiSE NOTED ON THE DRAWINGS <br />7. GROUT STOPS SHALL BE PROVIDED BELOW BOND BEAM. PLASTIC <br />SCREEN, METAL LATH STRIP OR CAVITY CAPS MAY BE USED TO <br />PREVENT THE FLOW GROUT INTO CELLS BELOW. THE USE OF FELT <br />PAPER AS A STOP IS PROHIBITED. <br /> <br />UPLIFT CONNECTORS <br /> <br />1. UPLIFT CONNECTORS SUCH AS HURRICANE CLIPS, TRUSS <br />ANCHORS AND ANCHOR BOLTS ARE ONLY REQUIRED ON <br />MEMBERS IN WALLS THAT ARE EXPOSED TO UPLIFT FORCES. <br />INTERIOR LOAD BEARING WALLS ARE NOT ALWAYS EXPOSED <br />TO UPLIFT FORCES. THE MEMBERS OF THESE WALLS WOULD <br />NOT NEED TO HAVE CONNECTORS APPLIED. PLEASF. CONSULT <br />THE TRUSS ENGINEERING FOR THE LOCATION OF THESE WALLS. <br /> <br />WOOD FLOOR <br />TRUSSES: <br /> <br />15 PSF <br />50 PSF <br />65 PSF <br /> <br />ASSUMED ALLOWABLE SOIL BEARING PRESSURE AFTER COMPACTION: 2000 PSF <br />SEE SOILS REPORT AND SPECIFICATIONS FOR COMPACTION REQUIREMENTS <br />IF SOIL CONDITIONS IN THE PROJECT DO NOT MEET OR EXCEED THE CAPACITY <br />THE GENERAL CONTRACTOR SHALL CONTACT THE ENGINEER PRIOR TO <br />FOUr-..DATION POUR FOR VERIFICATION OF FOUNDATION DESIGN. <br /> <br />SOIL BEARING <br />VALUE: <br /> <br />BUILDING DATA <br /> <br />CONSTRUCTION TYPE - TYPE VI UNPROTECTED <br />(SECTION 608 - FBC 2001) <br />MEAN ROOF 15 FT. HIGH <br />TYPICAL FOR SINGLE HOMES <br /> <br />WIND SPEED 123 MPH (3 SEC. GUST) <br />Wlr\D IMPORTANCE FACTOR - (Iw) = 1.0 <br />WIND EXPOSURE - "B" (FBC 1606.1.8) <br />INTERNAL PRESSURE COEFFICIENT = +/- 0.55 (PARTIALLY <br />ENCLOSED BLDG) <br /> <br />WOOD CONSTRUCTION <br /> <br />1. WOOD CONSTRUCTION SHALL CONFORM TO THE NFPA <br />"NATIONAL DESIGN SPECIFICATION FOR WOOD <br />CONSTRUCTION", LATEST EDITION. <br />2. ALL EXTERIOR WOOD STUD WALLS, BEARING WALLS, SHEAR <br />WALLS AND MiSC. STRUCTURAL WOOD FRAMING MEMBERS, <br />( I.E. BLOCKING OR GABLE END BRACING) SHALL BE EITHER <br />SOUTHERN PINE, OR S.P.F. NUMBER 2 GRADE SHALL BE <br />USED REGARDLESS OF SPECIES. <br /> <br />DESIGN WIND PRESSURE: <br /> <br />(COMPOI\ENT AND CLADDING) WORST CASE (10 SF - END ZONE) <br />WINDOWS AND DOORS <br />123 MPH + 38 PSF / - 40 PSF <br /> <br />GARAGE DOORS (V = 123 MPH) <br />SINGLE 9x7 +37.0 PSF / AO.O PSF <br />DOUBLE 16x7 +37.0 PSF /41.0 PSF <br /> <br />SEE FLOOR PLAN FOR ACTUAL PRESSURES <br /> <br />ALL WORK SHALL COMPLY WITH ALL <br />PREVAILlNG CODES, FLORIDA BUlLDJ}:G <br />CODE, NATIONAL ELECTRIC CODE AND <br />CITY OF ZEPHYRBlLLS ORDINANCES <br /> <br /> <br />ENGINEERED PLANS <br />ON FILE <br /> <br />REVlEWED <br />HA~ 1 0 2005 <br /> <br />~&r <br /> <br />WALDEN GRANDE 2003 STEM WALL <br /> <br />-", <br /> <br />GENERAL NOTES: <br /> <br />THE FOllOWING TECHINCAl CODES <br />SHAll APPLY: <br />2001 FLORIDA BUilDING CODE, <br />WITH 2003 REVISIONS <br />PLUMBING, MECHANICAL, FUEL GAS, <br />ENERGY EFFICIENCY, ACCESSIBILITY, <br />AND NFPA 70-02 NATIONAL ELECTRICAL CODES <br /> <br />1. TANK TYPE WATER CLOSET VOLUME <br />1.6 GALLONS <br />2. WALL MOUNT WATER CLOSET VOLUME <br />3.5 GALLONS <br />3. WATER - FLOW RATE. <br />PUBLIC FACILITIES 0.5 G.P.M. <br />PRIVATE FACILITIES 2.2 G.P.M. <br />SHOWER HEADS 2.5 G.P.M. <br />4. ALL WATER L1r-..E PLUMBING <br />TO BE PVPC <br />VTR LOCATIONS ARE APPROXIMATE <br />AND MAY CHANGE DUE TO JOBSITE <br />CONDITIONS <br /> <br />THE FOLLOWING SHALL COMPLY <br />WITH THE 2001 FBC. <br /> <br />D PORCHES AND BALCONIES <br />SECTION 1014 <br />D HANDRAILS - SECTION 1007.5 <br />D GUARDRAILS - SECTION 1015, 1019.9 <br />D STAIRS - SECTION 1007 <br />D CHIMNEY & FIREPLACE <br />SECTION 2804-2806 (MFGR) <br />SECTION 2113-2114 (MAS) <br />D EGRESS WINDOWS <br />SECTION 1005.4 <br /> <br />5. ALL OPEr-..INGS SHALL COMPLY WITH <br />2001 FBC WIND LOADS AS STATED <br />BELOW. ATTACHMENTS OF WINDOWS, <br />DOORS, SLIDING GLASS DOORS <br />AND O.H. GARAGE DOORS ARE TO DELEGATED <br />THE MANUFACTURER OF THESE ITEMS. THE <br />MANUFACTURER OF THESE ITEMS <br />SHALL SUBMIT ATTACHMENTS FOR <br />SITE INSTALLATION. <br /> <br />SEE ATTACHED SPECIFICATION SHEETS FOR <br />MANUFACTURERS DESIGN CRITERIA AND <br />INSTAllATION METHODS FOR WINDOWS, <br />DOORS, SLIDING GLASS DOORS, OVERHEAD <br />GARAGE DOORS, AND ROOFING. <br /> <br />6. ALL DOORS INTERIOR & EXTERIOR ARE <br />6'-8" UNLESS OTHERWISE NOTED <br />ALL SHOWER ENCLOSURES TO BE <br />TEMPERED GLASS <br />7. ALL WINDOWS WITHIN 24" OF DOORS <br />(INTERIOR & EXTERIOR) AND WITHIN <br />18" OF FLR TO BE TEMPERED GLASS. <br />(SECTION 2405.2) <br /> <br />SHT'NO: <br />1 <br />2 <br />2A <br />3 <br />4 <br />5 <br />6 <br />S-1 <br />S-2 <br />S-3 <br />S-4 <br />S-5 <br />S-6 <br />S-7 <br /> <br />S-8 <br />S-9 <br />S-10 <br />S-11 <br />S-12 <br />S-13 <br />S-14 <br />S-15 <br />S-16 <br />S-17 <br />S-18 <br /> <br />INDEX OF DRAWINGS <br /> <br />TITLE <br />COVER SHEET <br />FLOOR PLAN <br />DIMENSION PLAN <br />FOUNDATION PLAN <br />ELECTRICAL PLAN/ INT. ELEV. <br />ELEVATIONS <br />TRUSS LAYOUT <br />MASONRY DETAILS <br />LINTEL PLAN AND DETAILS <br />DETAILS <br />DETAILS <br />DETAILS <br />DETAILS <br />STRUC. NOTES & <br />HANGER INFORMATION <br />DETAILS <br />DETAILS <br />ROOFING DETAILS <br />DETAILS <br />DET AI LS <br />PRODUCT APPROVAL <br />WINDOW DETAILS <br />WINDOW DETAILS <br />DETAILS <br />DETAILS <br />DETAILS <br /> <br />NOTICE TO BUILDER <br /> <br />iT IS THE INTENT OF THiS DESIGNER THAT <br />THESE PLANS ARE ACCURATE AND ARE <br />CLEAR ENOUGH FOR THE LICENSED PROFESS- <br />ONAL TO CONSTRUCT THIS PROJECT. <br />IN THE EVENT THAT SOMETHING IS UNCLEAR <br />OR NEEDS CLARIFICATION..STOP..AND CALL <br />THE DESIGNER LISTED IN THIS TITLE PAGE. IT <br />IS THE RESPONSIBILITY OF THE L1CE'JSED <br />PROFESSIONAL THAT IS CONSTRUCTING THIS <br />PROJECT TO FULLY REVIEW THESE DOCUMENTS <br />BEFORE CONSTRUCTION BEGINS AND ANY AND <br />ALL CORRECTIONS, IF NEEDED, TO BE MADE <br />BEFORE ANY WORK IS DONE. <br /> <br />W <br />lJ..~0::: <br />'00:::0 <br />W lJ..lJ.. <br />~W~f- <br />~903 <br />W x~o:::o <br />U o::JlJ..u <br />I- O:::OZU <br />o.."",w<( <br />O o.."",~,- <br /><(0<(0 <br />Z wO:::f-z <br />o:::lJ..w <br />W <(zo:::o <br />rl""i aw<(o <br />\oJ W~(/)o <br /><t: f-;:::zz <br />I- 0 0<( <br />::Jw-w <br />o OO:::(/)~ <br />O (/)<(z . <br />W(/)w<(z <br />LL ~z~EtQ <br />W ;:::Qoof- <br />O(/) 0::: f-(:5 <br />0::: ofjSQ~:J <br /><t: lJ.. o:::Uo.. <br />w~woo.. <br />::) o:::of-CiS<( <br />a <(-lZ -l <br />::J -l -. 0::: -l <br />CJ) ~ <( (/) 0 <(~ <br />VJ 0::: -l '" <br />-lw-lO <br />-l>:;;ZO::: <br /><(0;><(0 <br /> <br />tn <br />(1)Q)-l <br />(J)1a~ <br />(1).- 0 <br />(1)(.)(/) <br />~ ~ ~ <br />I tn 0 <br />(J)~g: <br />(1)c5] <br />- 'OJ) Ci: <br />ca.- - <br />...tnE;:: <br />oQ)w <br />e"Cu <br /> <br /> <br />w ~ 0 <br />I ~ ~ Z <br />f-. (/) $: CD <br />c..:lZw <(CD.-4 <br />(/)~Qa O:::('.ICD (I) <br />. of-O 0.-4~ Z <br />ffiz(:5U w~~ii 0 <br />W<(-c..:l II~ t= <br />~tn~z f-f-....lLU ::J <br />c..:lo:::~o o:::lJ..u.o. ..J <br />ZWo..-l 00.. 0 <br />w9(/)S(/)lJ..z~~ (I) <br />wz(/)COZOO Q <br />I::JzwQ::Ji=zct Z <br />f-05I(/)<(0:::~:J ~ <br />6zo..f-:>uJooD:l (I) <br /><( I W (/) 0.. ct . IJJ <br />tnw<i!t::O:::o<i!a:I: C <br />w~O:::$:('I")zo:::....:1..U .- <br />COw::::J O<(:J....cc - <br />W-lf-~~af-....l::C C <br />I$:Uo.. wUcto _ <br />f-0E2~~0~~:; ~ <br />8 ~ tn 8 ~ (j) tnDO ii <br /> <br /> <br />~Il' <br />~ C=::J 0 <br />~ <( m <br /> <br />(/) <br />W <br />o <br />c..:l <br />z <br />o <br />-l <br />::J <br />co <br /> <br />-l <br /><l: <br />0::: <br />I- <br />~ <br />o <br />(/) <br />(/) W <br />o U <br />-l ('I") Ci: >< <br />COo lJ..<( <br />wr-- OLL <br />c..:lN ('1")0;;;1' <br />z('I") ('1")0 <br /><( -l ('I") ('I") <br />0:::lJ.. ~~ <br />o . 00 <br />.;2 coco <br />(/) 0.. C9 C9 <br />Il) 0 r-- r-- <br />0;;;1' 0- 00 <br />(j)<(0;;;I'0;;;I' <br /> <br />"'~ <br /> <br />(j) <br />o <br />('I") <br />~ \6 <br />00 - <br />00 r.- <br />L ~ <br />f- 0 <br />~ ,::; <br />CI) ~W <br />~ lJ.. _ <br />-('I")1l) <br />COONZ <br />~~c;jwo <br />c ('I") , -l W <br />~-l:;~f- <br />OlJ..oo:J<(M <br />. ro~f-~(!) <br />(/)~OU~M w <br />Q. 0;;;1' ::J f- (j) <br />MOO::: 0::: . ~ <br />Il)Q.If-WOO <br />(j)<(O-(/)UZ <br /> <br /> <br />o <br />o <br />l!l <br />W <br />~ <br />:J 0 <br />~ <br />Z Ul ..... ~ <br />o ci ..... ~ <br />- > I N <br />Ul .J C' U1 <br />> [l] 0 I <br />_ l!l C' <br />OW('I']l!l <br />L! ('I'] ~ <br />A 0 I <br />[l I .J ('I'] <br />~ U1 I.&. ..... <br />A ~ ~ 00 <br />"'" U1 Q. I <br />I- W ..... <br />~ ~ <br />.1- <br />Z <br />o <br />o <br />l!l <br /> <br />o <br />Z ~ <br />S2(J)~ 0 <br />(J):r:- <br />Wf-(J)w:J <br />oz(J)='< <br />O-:r:> <br />~2t:::;=(J) <br /><C'oIWO::~ <br />~M~OO <br />~O::OOO <br />:;=OwwU <br /><U.-:r:-'f- <br />O::Of-;'5Z <br />O:JO::(J)ii! <br />(J);;:Woo:: <br />I (J)C: Z::J <br />f-_<<U <br /> <br /> Il) <br /> 0 <br /> NU) '" <br /> M <br /> -z U""'" <br /> ~O f-('I") <br /> <(0- <br /> N- 0;;;1'0 <br /> ..,U) Il) '" <br /> > <:t<( <br /> MO <br /> W '~ <br /> 0::: ~~ <br />0 (f) W-' <br />~ ~ <br />~ --I 0--1 W 0 <br /> 0::: <br />--I z<( U >-lJ..z <br /> Zf-O <br />0 <($ <(Z- <br />- ZW~ <br />I :r: I- -(/)> <br /> O:::~ 0 Oz(3 <br />C\J t3C<( <br /> Z ::JUO <br />LO $ 0W OZo:: <br /> owo <br /> Zl- I- 0:::f::......J <br />I 0--lJ.. <br />('..... 1J.J I wO:::-l <br /> wU) 0:::$:<( <br /> WWO::: <br />~ - C!J COIf- <br />> wO(Y) f-f-6J <br /> Of-U <br />~ ~--IO 0::: Z::J . <br />I- >-00- <br />LO ~<( 0 >- <(I 0::: <br />(j) ~t::0 <br />z$ N 0... $:U <br />50:::w <br />~ 1J.J 0 w~ <br /><t: o..zo <br /> -.J (/)ZI <br />>- 0:: 0.. U -<((/) <br /> ~~::J <br />0:: () SHEET NO. 0.. <br /> 0::: <br />0 1 0 <br />0 U <br /> W <br /> ~ <br />I- ~ 0 <br /> OF I <br />Z ~ 25 (/) <br /> ::J <br /> ('I") <br />1J.J 0 <br />I- 0 <br />> LAST PLOT DATE '" <br /> @ <br />0 March 01, 2005 <br />Z <br />--I COVER SHEET <br />- <br />