<br />Termite Specifications:
<br />
<br />Structural Notes:
<br />
<br />General Notes:
<br />
<br />1. A PERMANENT SIGN WHICH IDENTIFIES THE TERMITE TREATMENT PROVIDER
<br />AND NEED FOR RE-INSPECTION AND TREATMENT CONTRACT RENEWAL SHAll
<br />BE PROVIDED. Tl1E SIGN SHAll BE POSTED NEAR THE WATER HEATER OR
<br />ELECTRIC PANEl.(FBC 104.2.6)
<br />
<br />FOUNDATIONS
<br />SOIL TO BE COMPACTED TO AT lEAST 95%
<br />OF MAX. DRY DENSIlY AS DETERMINED BY
<br />ASTM - 1557 ( MODIFIED PROCTOR)
<br />FOUNDATION INSPECTIONS
<br />A FOUNDATION SURVEY SHAll BE PERFORMED AND A
<br />COpy OF Tl1E SURVEY SHAll BE ON SITE FOR THE BUILDING
<br />INSPECTORS USE, OR ALL PROPERlY MARKERS SHAll BE
<br />EXPOSED AND A STRING STRECHED FROM MARKER TO
<br />MARKER TO VERIFY REQUIRED SETBACKS.
<br />CAST IN PLACE CONCRETE
<br />1. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE
<br />STRENGTH AT 28 DAYS OF 2500 PSI, A SLUMP OF 6"
<br />PLUS OR MINUS 1", AND HAVE 2 TO 5% AIR ENTRAINMENT,
<br />AND A MAXIMUM WATER/CEMENT RATIO OF 0.63
<br />2. ALL REINFORCING STEEL SHALL BE NEW DOMESTIC
<br />DEFORMED BILLET STEEL CONFORMING TO ASTM A-615
<br />GRADE 40.
<br />3. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185.
<br />WWF SHALL BE LAPPED AT LEAST 6" AND CONTAIN AT
<br />LEAST ONE CROSS WIRE WITHIN THE 6".
<br />4. HOOKS SHALL BE PROVIDED AT DISCONTINUOUS ENDS OF
<br />ALL TOP BARS OF BEAMS.
<br />5. HORIZONTAL FOOTING BARS SHALL BE BENT 1'-0"
<br />AROUND CORNERS OR CORNER BARS WITH A 2'-0"
<br />LAP PROVIDED
<br />6. MINIMUM LAP SPUCES ON ALL REINFORCING BAR
<br />SPUCES SHALL BE 40 BAR DIAMETERS lYP.
<br />7. CONCRETE COVER MIN. 3" WHEN EXPOSED TO EARTH OR
<br />1 1/2" TO FORM
<br />MASONRY WALL CONST.
<br />1. HOLLOW LOAD BEARING UNITS SHALL BE NORMAL
<br />WEIGHT, GRADE N, lYPE 2, CONFORMING TO ASTM C90,
<br />WITH A MINIMUM NET COMPRESSIVE STRENGTH OF
<br />1900 PSI ( fm = 1500 PSI )
<br />2. MORTAR SHALL BE lYPE "M" OR "S", CONFORMING TO
<br />ASTM C270.
<br />3. COARSE GROUT SHALL CONFORM TO ASTM C476 WITH A
<br />MAXIMUM AGGREGATE SIZE OF 3/8" AND A MINIMUM
<br />COMPRESSIVE STRENGTH OF 3000 PSI SLUMP 8" TO 11".
<br />4. VERTICAL REINFORCEMENT SHALL BE AS NOTED ON Tl1E
<br />DRAWINGS WITH THE CELLS FILLED WITH COARSE GROUT.
<br />5. VERTICAL REINFORCEMENT SHALL BE HELD IN POSITION
<br />AT THE TOP AND BOTTOM AND AT A MAXIMUM SPACING
<br />OF 192 BAR DIAMETERS. REINFORCEMENT SHALL BE PLACED
<br />IN Tl1E CENTER OF THE MASONRY CELL lYPICAL UNLESS
<br />OTHERWISE NOTED.
<br />6. REINFORCING STEEL SHALL BE LAPPED A MINIMUM OF 40 BAR
<br />DIAMETERS, UNLESS OTHERWISE NOTED ON THE DRAWINGS
<br />7. DUR-O-WALL SHALL BE PROVIDED @ EVERY OTHER
<br />COARSE OR 16" O/C
<br />WOOD CONSTRUCTION
<br />1. WOOD CONSTRUCTION SHALL CONFORM TO THE NFPA
<br />"NATIONAL DESIGN SPECIFICATION FOR WOOD
<br />CONSTRUCTION", 2001 EDmON.
<br />2. ALL EXTERIOR WOOD STUD WALLS, BEARING WALLS, SHEAR
<br />WALLS AND MISe. STRUCTURAL WOOD FRAMING MEMBERS,
<br />( I.E. BLOCKING OR GABLE END BRACING) SHALL BE EITHER
<br />SOUTHERN PINE, OR S.P.F. NUMBER 2 GRADE SHALL BE
<br />USED REGARDLESS OF SPECIES.
<br />3. ANY WOOD FRAME BEARING WALL STUDS THAT ARE CUT
<br />FOR PLUMBING UNES, ETC. SHALL BE REPAIRED WITH
<br />SIMPSON HSS2 STUD SHOES,lYP., U.N.O.
<br />4. ALL STUCCO FINISH OVER EXTERIOR FRAME MUST BE 7/8" Tl1ICK
<br />PER ASTM e. 926-APPLY 3 LAYERS WITH TOTAL Tl1ICKNESS 7/8"
<br />OVER METAL LATH.
<br />FIRST 2 LAYERS 3/8" Tl1ICK EACH. 3RD LAYER 1/8" Tl1ICK.
<br />5. ALL EXPOSED WOOD OR WOOD IN CONTACT WITH
<br />EARTH OR CONCRETE TO BE PRESSURE TREATED.
<br />
<br />*ATTENTION: CHEMICAL CHANGES IN PRESSURE TREATED WOODS
<br />AS OF DECEMBER 31ST, 2003, CHROMATED COPPER ARSENATE
<br />(CCA-C) WILL NO LONGER BE PRODUCED FOR RESIDENTIAL OR
<br />GENERAL CONSUMER USE. SEVERAL NEW PRESSURE TREATED
<br />WOOD ALTERNATIVES HAVE BEEN CREATED TO REPLACE CCA-e.
<br />MANY OF THE NEW PRESSURE TREATED WOODS USE CHEMICALS
<br />THAT ARE CORROSIVE TO STEEL. IT IS THE CONTRACTOR'S
<br />RESPONSIBIUlY TO VERIFY THE lYPE OF WOOD TREATMENT AND TO
<br />SELECT APPROPRIATE CONNECTORS THAT RESIST CORROSION.
<br />FOR EXAMPLE, ACQ-C, ACQ-D, CBA-A. OR CA-B REQUIRE HOT-DIPPED
<br />GALVANIZED OR STAINLESS STEEL FASTENERS.
<br />DOT SODIUM BORATE (SBX) DOES NOT.
<br />
<br />2. CONDENSATE AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1'-0"
<br />AWAY FROM BUILDING SIDE WALKS.(FBC 1503.4.4)
<br />
<br />3. IRRIGATION/SPRINKLER SYSTEMS INCLUDING ALL RISERS AND SPRAY HEADS
<br />SHALL NOT BE INSTALLED WITHIN 1'-0" OF THE BUILDING SIDE WALLS.(FBC 1503.4.4)
<br />
<br />4. TO PROVIDE FOR INSPECTION FOR TERMITE INFESTATION, BETWEEN WALL
<br />COVERING AND FINAL EARTH GRADE SHALL NOT BE LESS THAT 6 INCHES.
<br />
<br />EXCEPTION: PAINT OR DECORATIVE CEMENTATIOUS FINISH LESS THAN 5/8"
<br />THICK ADHERED DIRECTLY TO THE FOUNDATION WALl.(FBC 1403,1.6)
<br />
<br />5. INITIAL TREATMENT SHALL BE DONE AFTER ALL EXCAVATION AND BACKFILL
<br />IS COMPLETE.(FBC 1816.1.1)
<br />
<br />6. SOIL DISTURBED AFTER Tl1E INITIAL TREATMENT SHALL BE RETREATED
<br />INCLUDING SPACES BOXED AND FORMED,(FBC 1816.1.2)
<br />
<br />7. BOXED AREAS IN CONCRETE FLOORS FOR SUBSEQUENT INSTALLATION OF TRAPS,
<br />ETC., SHALL BE MADE WITH PERMANENT METAL OR PLASTIC FORMS. PERMANENT
<br />FORMS MUST BE OF A SIZE AND DEPTH THAT WILL EUMINATE THE DISTURBANCE OF
<br />SOIL AFTER THE INITIAL TREATM ENT. (FBC 1816.1.3)
<br />
<br />8. MINIMUM 6 MIL VAPOR RETARDER MUST BE INSTALLED TO PROTECT AGAINST RAINFALL
<br />DILUTION. IF RAINFALL OCCURS BEFORE VAPOR RETARDER PLACEMENT, RETREAH1ENT IS
<br />REQUIRED.(FBC 1816.1.4)
<br />
<br />9. CONCRETE OVERPOUR AND MORTAR ALONG THE FOUNDATION PERIMETER MUST BE
<br />REMOVED BEFORE EXTERIOR SOIL TREATMENT.(FBC 1816,1.5)
<br />
<br />10. SOIL TREATMENT MUST BE APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE
<br />WITHIN 1'-0" OF THE STRUCTURE SIDEWALLS.(FBC 1816.1.6)
<br />
<br />11. AN EXTERIOR VERTICAL CHEMICAL BARRIER MUST BE INSTALLED AFTER CONSTRUCTION
<br />IS COMPLETE INCLUDING LANDSCAPING AND IRRIGATION. ANY SOIL DISTURBED AFTER
<br />Tl1E VERTICAL BARRIER IS APPUED, SHALL BE RETREATED.(FBC 1816.1.6)
<br />
<br />12. ALL BUILDINGS ARE REQUIRED TO HAVE PRE-CONSTRUCTION TREATMENT.(FBC 1816.1.7)
<br />
<br />13. A CERTIFICATE OF COMPUANCE MUST BE ISSUED TO THE BUILDING DEPARTMENT
<br />BY A LICENSED PEST CONTROL COMPANY BEFORE A CERTIFICATE OF OCCUPANCY
<br />WILL BE ISSUED. THE CERTIFICATE OF COMPLIANCE SHALL STATE: "Tl1E BUILDING
<br />HAS RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN
<br />TERMITES. THE TREATMENT IS IN ACCORDANCE WITH THE RULES AND LAWS OF THE
<br />FLORIDA DEPARMENT OF AGRICULTURE AND CONSUMER SERVICES."(FBC 1816.1.7)
<br />
<br />14. AFTER ALL WORK IS COMPLETED, LOOSE WOOD AND FILL MUST BE REMOVED FROM
<br />BELOW AND WITHIN 1'.0" OF THE BUILDING. Tl1IS INCLUDES ALL GRADE STAKES,
<br />TUB TRAY BOXES, FORMS, SHORING OR OTHER CELLULOSE CONTAINING MATERIAL.
<br />(FBC 2303.1.3)
<br />
<br />15. NO WOOD, VEGETATION, STUMPS, CARDBOARD, TRASH, ETC., SHALL BE BURIED
<br />WITHIN 15'-0": OF ANY BUILDING OR PROPOSED BUILDING.(FBC 2303.1.4)
<br />
<br />WOOD FRAMING INSPECTION
<br />ALL PLUMBING, ELECTRICAL, AND MECHANICAL
<br />ROUGH-INS MUST BE COMPLETE, INSPECTED
<br />AND APPROVED BEFORE REQUESTING FRAMING
<br />INSPECTION.
<br />
<br />Master Revisions:
<br />
<br />DATE
<br />
<br />DESCRIPTION
<br />
<br />ALL WORK SHALL COMPLY WlTHALL
<br />PREVAILING CODES, FLORlDA BUILDll\G
<br />CODE, NATIONAL ELECTRIC CODE AND
<br />CITY OF ZEPHYRHILLS ORDINANCES
<br />
<br />....
<br />;..;
<br />
<br />J
<br />~
<br />1i\
<br />"-
<br />'"
<br />;..;
<br />....
<br />~
<br />"
<br />~
<br />"
<br />""
<br />~
<br />~
<br />J
<br />~
<br />c3
<br />..:
<br />~
<br />f
<br />~
<br />/'
<br />.&,
<br />iil
<br />!
<br />~
<br />~
<br />l
<br />i
<br />]
<br />t
<br />$l
<br />/'
<br />/'
<br />
<br />REVIEWED
<br />NAY 09 Z005
<br />
<br />~bWr
<br />
<br />Structural Design Criteria:
<br />
<br />
<br />
<br />CODES:
<br />
<br />FLORIDA BUILDING CODE, 2001 EDmON
<br />BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE (ACI 318-02)
<br />SPECIFICATIONS FOR STRUCTURAL CONCRETE BUILDINGS (ACI 301-89)
<br />BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES (ACI 530-02)
<br />NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION, 2001 EDmON
<br />APA PLYWOOD DESIGN SPECIFICATION
<br />
<br />2001 FLORIDA BUILDING CODE,
<br />PLUMBING, MECHANICAL, FUEL GAS,
<br />ENERGY EFFICIENCY, ACCESSIBILIlY,
<br />AND 2002 NATIONAL ELECTRICAL CODES
<br />
<br /> ~ w\
<br /> cw~
<br /> !aj:
<br />d ;h ~
<br />z ~~9 ~
<br />~ ~~ ~~ ~
<br />z ~8~ ;~ ~
<br />~ ~~I~
<br />W ~ g1B~
<br />w z ~.
<br />Z x~~~~ ~-L..l 00 ~ C'1
<br />~j:;i~ ~
<br />~ ~ ...-1"). ~~~ ~f3 ~~ cr:::
<br />Z cQ...-lD c:1:
<br />W . ~"'V'euJ ~
<br />o .. ii; I~ ~!
<br /> a: ..
<br />....J ...JD
<br />~ ex
<br />~~
<br />C) a..
<br />W :~~ ~~ ~~
<br />I-
<br />Z
<br /> . . .
<br />
<br />PREFABRICATED WOOD TRUSSES
<br />
<br />1. ALL PREFABRICATED WOOD TRUSSES SHALL BE SECURELY
<br />FASTENED TO THEIR SUPPORTING WALLS OR BEAMS WITH
<br />HURRICANE CUPS OR ANCHORS.
<br />2. PREFABRICATE WOOD TRUSSES SHALL BE DESIGNED IN
<br />ACCORDANCE WITH THE LATEST EDITION OF Tl1E "NATIONAL
<br />DESIGN SPECIFICATION FOR STRESS-GRADE LUMBER AND
<br />ITS FASTENERS" AS RECOMMENDED BY THE NATIONAL
<br />FOREST PRODUCTS ASSOCIATION.
<br />3. TRUSS MEMBERS AND CONNECTIONS SHALL BE PROPOR-
<br />TIONED (WITH A MAXIMUM ALLOWABLE STRESS INCREASE
<br />FOR LOAD DURATION OF 25%) TO WITHSTAND THE UVE
<br />LOADS GIVEN IN THE NOTES AND TOTAL DEAD LOAD.
<br />4. BRIDGING FOR PRE-ENGINEERED TRUSSES SHALL BE AS
<br />REQUIRED BY Tl1E TRUSS MANUFACTURER UNLESS
<br />NOTED ON THE PLANS.
<br />5. TRUSS ELEVATIONS AND SECTIONS ARE FOR GENERAL
<br />CONFIGURATION OF TRUSSES ONLY. WEB MEMBERS ARE
<br />NOT SHOWN, BUT SHALL BE DESIGNED BY THE TRUSS
<br />MANUFACTURER IN ACCORDANCE WITH THE DESIGN
<br />LOADS AS LISTED ON THE STRUCTURAL DESIGN CRITERIA
<br />6. DESIGN SPECIFICATIONS FOR UGHT WEIGHT METAL
<br />PLATE CONNECTED WOOD TRUSSES PER Tl1E TRUSS
<br />PLATE INSTITUTE TPI LATEST EDITION.
<br />7. PRE-ENGINEERED WOOD TRUSSES SHALL BE DESIGNED BY
<br />Tl1E MANUFACTURER IN ACCORDANCE WITH SPECIFIED LOADS
<br />AND GOVERNING CODES. SUBMITTALS SHALL INCLUDE TRUSS
<br />FRAMING PLANS AND DETAILS SHOWING MEMBER SIZES,
<br />BRACING, ANCHORAGE, CONNECTIONS, TRUSS LOCATIONS, AND
<br />AND PERMANENT BRACING AND/OR BRIDGING AS REQUIRED
<br />FOR ERECTION AND FOR THE PERMANENT STRUCTURE. EACH
<br />SUBMmAL SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />REGISTERED STRUCTURAL ENGINEER. SUBMIT 3 COPIES FOR
<br />REVIEW AND APPROVAL PRIOR TO FABRICATION.
<br />8. Tl1E TRUSS MANUFACTURER SHALL DETERMINE ALL SPANS
<br />WORKING POINTS, BEARING POINTS, AND SIMILAR CONDITIONS.
<br />TRUSS SHOP DRAWINGS SHALL SHOW ALL TRUSSES, ALL
<br />BRACING MEMBERS, AND ALL TRUSS TO TRUSS HANGERS.
<br />
<br />THE FOLLOWING TECHINCAL CODES
<br />SHALL APPLY:
<br />
<br />LIVE LOADS:
<br />
<br />ROOF
<br />TOP CHORD
<br />BOTTOM CHORD (W/O STORAGE)
<br />RESIDENTIAL FLOOR, UNLESS OTHERWISE INDICATED
<br />BALCONIES
<br />STAIRS
<br />
<br />ROOF
<br />FLOOR
<br />
<br />ORDINANCE 92-19 - APPENDIX "J"
<br />TO FBC PLUMBING 2001 CODE.
<br />1. TANK lYPE WATER CLOSET VOLUME
<br />1.6 GALLONS
<br />2. WALL MOUNT WATER CLOSET VOLUME
<br />3.5 GALLONS
<br />3. WATER - FLOW RATE.
<br />PUBLIC FACIUTIES 0.5 G.P.M.
<br />PRIVATE FACILITIES 2.2 G.P.M.
<br />SHOWER HEADS 2,5 G,P.M.
<br />4. ALL PLUMBING WATER LINES
<br />TO BE PVPC
<br />
<br />
<br />20 PSF
<br />10 PSF
<br />40 PSF
<br />40 PSF
<br />40 PSF
<br />
<br />17 PSF (SHINGLE)
<br />15 PSF
<br />
<br />DEAD LOADS:
<br />
<br />WIND LOADS:
<br />(F.B.C.)
<br />CONCRETE
<br />STRENGTH
<br />@ 28 DAYS
<br />
<br />WIND LOADS BASED ON FBC, SECTION 1606.2.
<br />WIND VELOCIlY: 123 M.P.H., USE FACTOR: 1.0
<br />
<br />ALL CONCRETE UNLESS OTl1ERWISE INDICATED
<br />PEA GRAVEL CONCRETE FOR MASONRY CELLS ONLY
<br />(DO NOT USE FOR CONCRETE COLUMNS OR TIE BEAMS)
<br />
<br />2500 PSI
<br />3000 PSI
<br />
<br />VTR LOCATIONS ARE APPROXIMATE
<br />AND MAY CHANGE DUE TO JOBSITE
<br />CONDITIONS
<br />
<br />REINFORCING:
<br />
<br />ASTM A185
<br />ASTM A615-40 40,000 PSI
<br />ASTM A615-40 40,000 PSI
<br />
<br />WELDED WIRE FABRIC SHALL CONFORM TO
<br />ALL REINFORCING BARS
<br />ALL STIRRUPS AND TIES
<br />
<br />THE FOLLOWING SHALL COMPLY
<br />WITH Tl1E 2001 FBC.
<br />
<br />o PORCHES AND BALCONIES
<br />SECTION 1014
<br />o HANDRAILS - SECTION 1007,5
<br />o GUARDRAILS - SECTION 1015, 1019,9
<br />o STAIRS - SECTION 1007
<br />o CHIMNEY & FIREPLACE
<br />SECTION 2804-2806 (MFGR)
<br />SECTION 2113-2114 (MAS)
<br />IXJ EGRESS WINDOWS
<br />SECTION 1005.4
<br />
<br />s
<br />o
<br />u
<br />0\ U
<br />di( Lt) .S
<br />.9 Lt) f;:; ~
<br />"'d (1') ......
<br />E~ .ooo.c
<br />~c2 ~~~ ~~
<br />.8 QJ .8 t--. ~ .~ ~
<br />~~ ~~~.$jo
<br />~(j)t--. ~~~ .g
<br />~~.~~~~ ~~
<br />UN(})UO.d..I.. ~:tt:
<br />
<br />CONCRETE
<br />MASONRY
<br />UNITS:
<br />
<br />ASTM C90 OR C129, STANDARD WEIGHT UNITS, fm=1500 PSI
<br />MORTAR lYPE "S" 1900 PSI
<br />CONCRETE GROUT 3000 PSI
<br />CONTINUOUS MASONRY INSPECTION IS REQUIRED DURING CONSTRUCTION
<br />
<br />ALL STRUCTURAL AND MISCELLANEOUS STEEL A36 36,000 PSI, U.N.O
<br />SHOP AND FIELD WELDS: E70XX ELECTRODES
<br />ALL BOLTS CAST IN CONCRETE: ASTM A36 OR ASTM A-307
<br />
<br />STRUCTURAL
<br />STEEL:
<br />
<br />WOOD FRAMING:
<br />
<br />BEAMS, RAFTERS, JOIST, PLATES, ETC. U.N.O.
<br />NO.2 SOUTHERN YELLOW PINE (19% M.C,)
<br />ROOF DECK: PLYWOOD C-C;C-D, EXTERIOR, or OSB
<br />FLOOR SHEATHING: 3/4" PLYWOOD (5 PUES) OR 3/4" T&G ADVANTECH
<br />WALL SHEATHING: PLYWOOD C-C/C-D, EXTERIOR OR OSB
<br />VERSA LAM BEAM Fb = 2900 PSI (2.0E)
<br />
<br />4. ALL OPENINGS SHALL COMPLY WITH
<br />2001 FBC WIND LOADS AS STATED
<br />BELOW. ATTACHMENTS OF WINDOWS,
<br />DOORS, SUDING GLASS DOORS
<br />AND O.H. GARAGE DOORS ARE TO DELEGATED
<br />Tl1E MANUFACTURER OF THESE ITEMS. THE
<br />MANUFACTURER OF THESE ITEMS
<br />SHALL SUBMIT ATTACHMENTS FOR
<br />SITE INSTALLATION.
<br />
<br />SEE ATTACHED SPECIFICATION SHEETS FOR
<br />MANUFACTURERS DESIGN CRITERIA AND
<br />INSTALLATION METHODS FOR WINDOWS,
<br />DOORS, SUDING GLASS DOORS, OVERHEAD
<br />GARAGE DOORS, AND ROOFING.
<br />
<br />o
<br />o
<br />\.0
<br />2
<br />
<br />.- 0
<br />::J~
<br />ZVloMl"'-.
<br />o - oM I"'-.
<br />~"'OIN
<br />Vl>O'\LJ')
<br />~caOI
<br />~QJ~O'\
<br />OL.(V)\.O
<br />I"'-.
<br />,<(0- I
<br />o....cLLM
<br />':E~ro~
<br />~QJ~~
<br />r-5ro
<br />-J-
<br />Z
<br />o
<br />o
<br />\.0
<br />
<br />UPLIFT CONNECTORS
<br />
<br />WOOD ROOF
<br />TRUSSES:
<br />
<br />@~~~~~1S~~~~
<br />~ s< ~ ffi ft :i: 15 fLx: Z ~ ::1
<br />:)Ox~zu.~zO~:)o..
<br />O'Ul~cn:;!OQ~OWOo..
<br />UlWo.. ~w ~ ~U~
<br />:j~~:::jf'-9f5f'-~ ~-I
<br />~f'- ~W~Ci2WW f'-::t
<br />Q~LU~:)UJ~~~o~
<br />~~> o~ r-Zcx:
<br />0...... 0
<br />
<br />DESIGN LOADS:
<br />TOP CHORD UVE AND DEAD LOAD:
<br />BOTTOM CHORD LIVE AND DEAD LOAD:
<br />TOTAL:
<br />
<br />NET UPLIFT DESIGN PRESSURE: 20 PSF WITHIN
<br />4 FEET OF RIDGES, HIPS, EAVES AND BUILDING
<br />PERIMETER AND 15 PSF MIN FOR ALL OTHER AREAS.
<br />
<br />SEE DRAWINGS FOR SPECIAL CONCENTRATED LOADS. DESIGN
<br />FOR NEW WIND UPLIFT AS PER SPECIFIED CODES, DEDUCTING
<br />A MAXIMUM OF 10 P.S.F. DEAD LOAD, BUT NOT EXCEEDING ACTUAL
<br />DEAD LOAD.
<br />
<br />27 PSF
<br />20 PSF
<br />47 PSF
<br />
<br />LULULU
<br />~(9U
<br />~~~
<br />:)00
<br />~~z
<br />
<br />1. UPUFT CONNECTORS SUCH AS HURRICANE CUPS, TRUSS
<br />ANCHORS AND ANCHOR BOLTS ARE ONLY REQUIRED ON
<br />MEMBERS IN WALLS THAT ARE EXPOSED TO UPUFT FORCES.
<br />INTERIOR LOAD BEARING WALLS ARE NOT ALWAYS EXPOSED
<br />TO UPUFT FORCES. Tl1E MEMBERS OF Tl1ESE WALLS WOULD
<br />NOT NEED TO HAVE CONNECTORS APPUED. PLEASE CONSULT
<br />THE TRUSS ENGINEERING FOR THE LOCATION OF THESE WALLS.
<br />
<br />
<br />FIELD REPAIR NOTES
<br />
<br />WOOD FLOOR
<br />TRUSSES:
<br />
<br />DESIGN LOADS:
<br />DEAD LOAD:
<br />LIVE LOAD:
<br />TOTAL:
<br />
<br />15 PSF
<br />40 PSF
<br />55 PSF
<br />
<br />5. ALL DOORS INTERIOR & EXTERIOR ARE
<br />6'-8" UNLESS OTHERWISE NOTED
<br />ALL SHOWER ENCLOSURES TO BE
<br />TEMPERED GLASS
<br />6. ALL WINDOWS WITl1IN 24" OF DOORS
<br />(INTERIOR & EXTERIOR) AND WITHIN
<br />18" OF FLR TO BE TEMPERED GLASS.
<br />(SECTION 2405.2)
<br />
<br />1. MISSED UNTEL STRAPS FOR MASONRY CONSTRUCTION MAY
<br />BE SUBSTITUTED W/ (1) "SIMPSON MTSM16 TWIST STRAP W/
<br />(4) 1/4" X 2 1/4" DIA. mENS TO Tl1E BOND BEAM BLOCK
<br />AND (7) 10d TO THE TRUSS FOR UPUFTS OF 1000 LBS. OR
<br />LESS. USE (2) FOR 2000 LBS. OR LESS. OTl1ERS MAY BE
<br />SUBSTITUTED ON A CASE BY CASE BASIS.
<br />2, MISSED "J" BOLTS FOR WOOD BEARING WALLS MAY BE SUB-
<br />STITUTED W/ 1/2" DIA. ANCHOR BOLTS SET IN 3/4" DIA. X 6"
<br />DEEP UNITEX "PROPOXY" 300 ADHESIVE BINDER FOLLOWING
<br />ALL MANUFACTURERS RECOMMENDATIONS ( OR 1/2" X 6"
<br />RAWL STUD EXPANSION ANCHORS. )
<br />
<br />3. REGARDING MISSED REBAR IN VERTICAL FILLED CELLS:
<br />DRILL A 3/4" DIAMETER HOLE 6" DEEP AT Tl1E LOCATION OF
<br />THE OMITTED REBAR, AND INSTALL A 32" LONG #5 BAR INTO
<br />THE EPOXY FILLED HOLE. USE A TWO PART EMBEDDEMENT
<br />EPOXY (SIMPSON "EPOXY TIE SET", OR HILT!" 2 PART"
<br />EMBEDDMENT EPOXY ), MIXED PER MANUFACTURER'S
<br />INSTRUCTIONS. ASSURE THAT ALL DUST AND DEBRIS FROM
<br />DRILLING ARE REMOVED FROM THE HOLE BY BRUSHING AND
<br />AND USING COMPRESSED AIR PRIOR TO APPLYING THE EPOXY.
<br />ALLOW THE EPOXY TO CURE TO MANUFACTURER'S SPECIFICATIONS,
<br />THEN FILL THE CelL IN THE NORMAL WAY DURING BOND BEAM
<br />POUR.
<br />4. HURRICANE STRAPS MAY BE SUBSTITUTED WITH A STRAP OF
<br />GREATER HOLDOWN VALUE OR GREATER UPLIFT VALUE IN THE
<br />FIELD WITHOUT VERIFICATION, PROVIDED ALL MANUFACTURERS
<br />INSTALLATION INSTRUCTIONS ARE FOLLOWED.
<br />5. FOR MORTAR JOINTS LESS THAN 1/4", PROVIDE (1) #5 VERT.
<br />IN CONe. FILLED CELL EACH SIDE OF Tl1E JOINT ( BAR DOES
<br />NOT HAVE TO BE CONT. TO FOOTING)
<br />
<br />SOIL BEARING
<br />VALUE:
<br />
<br />ASSUMED ALLOWABLE SOIL BEARING PRESSURE AFTER COMPACTION: 2000 PSF
<br />SEE SOILS REPORT AND SPECIFICATIONS FOR COMPACTION REQUIREMENTS
<br />IF SOIL CONDmONS IN Tl1E PROJECT DO NOT MEET OR EXCEED THE CAPACITY'
<br />THE GENERAL CONTRACTOR SHALL CONTACT THE ENGINEER PRIOR TO
<br />FOUNDATION POUR FOR VERIFICATION OF FOUNDATION DESIGN.
<br />
<br />,t
<br />
<br />Building Data:
<br />
<br />"r
<br />p
<br />
<br />Index Of Drawings
<br />
<br />SHT NO:
<br />
<br />TlE
<br />
<br />CONSTRUCTION lYPE -- lYPE VI UNPROTECTED
<br />(SECTION 608 - FBC 2001)
<br />
<br />WIND SPEED 123 MPH
<br />WIND IMPORTANCE FACTOR -- (Iw) = 1.0
<br />WIND EXPOSURE -- "B" (FBC 1606.1.8)
<br />INTERNAL PRESSURE COEFFICIENT = +/- 0.55 (PART. ENCLOSED)
<br />
<br />~
<br />
<br />A
<br />A1
<br />A2
<br />A3
<br />A4.1
<br />A4.2
<br />A4.3
<br />AS.l
<br />AS.2
<br />AS.3
<br />A6
<br />S-1
<br />S-2
<br />S-2A
<br />S-3
<br />S-4
<br />
<br />S-6
<br />S-7
<br />
<br />>-f-
<br />Zz
<br /><(UJ
<br />Z<n
<br />W.......zz
<br />u98~
<br />~~z~
<br />o8~o
<br />Za::~<(
<br />a..:>c-
<br />~:>~
<br />I-UJUJ~
<br />:r: co I UJ
<br />19f-f-~
<br />Io-o-ot 0 f- 0
<br />0::: Z 5 ::c
<br />>- >- I <n
<br />0.<(1:::)
<br />::E~~
<br />O~a::O
<br />U:)UJct
<br />a..Zu.
<br /><nZ
<br />.......<(
<br />I::E
<br />f-
<br />
<br />COVER SHEET
<br />FLOOR PLAN
<br />FOUNDATION PLAN
<br />ELECTRICAL PLAN
<br />ELEVATION I
<br />ELEVATION II
<br />ELEVATION III
<br />ROOF FRAMING ELEV I
<br />ROOF FRAMING ELEV II
<br />ROOF FRAMING ELEV III
<br />INTERIOR ELEVATIONS
<br />FOUNDATION DETAILS
<br />LINTEL DETAILS
<br />LINTEL PLANS
<br />ROOF FRAMING (I, II, III)
<br />BRACING DETAILS
<br />WALL SECTIONS
<br />STRUCTURAL NOTES &
<br />HANGER INFORMATION
<br />WINDOW & DOOR DETAILS
<br />WINDOW & DOOR DETAILS
<br />WINDOW & DOOR DETAILS
<br />WINDOW & DOOR DETAILS
<br />PRODUCT APPROVAL INFO
<br />
<br />1-
<br />Q)
<br />>
<br />o
<br />"C
<br />c:
<br /><(
<br />
<br />WIND BORNE DEBRIS AREAS
<br />
<br />DESIGN WIND PRESSURE:
<br />
<br />(COMPONENT AND CLADDING) WORST CASE (10 SF - END ZONE)
<br /># END ZONE IS ONLY WITHIN 5'-0"
<br />OF ALL EXTERIOR BUILDING CORNERS
<br />
<br />THE METHOD TO SATISFY PROTECTION OF OPENINGS
<br />IN THESE AREAS WILL BE THE SOLE RESPONSIBILITY'
<br />OF THE CONTRACTOR.
<br />
<br />WINDOWS AND DOORS
<br />SEE FLOOR PLAN FOR ACTUAL PRESSURES
<br />
<br />THEIR OPTIONS ARE AS FOLLOWS:
<br />
<br />A. IMPACT RESISTANT GLAZING
<br />B. APPROVED SHUTTERS
<br />C. SUPPLY WOOD STRUCTURAL PANELS
<br />PER FBC 1606.1.4
<br />
<br />C\I Vl
<br /> C
<br />~ 0
<br /> '(;;
<br /> '5
<br />~ &
<br />0 ~
<br /> Q)
<br />I (f) >
<br />C\I -
<br />-
<br />--
<br />LO I
<br />I ~
<br />f'... Q)
<br /> --
<br />~ >
<br /> +-'
<br />~ (f)
<br />LO Q)
<br />'-
<br />~ ()
<br />
<br />
<br />Ln
<br />o
<br />o
<br />N
<br />
<br />$-8
<br />S-9
<br />S-10
<br />S-l1
<br />S-12
<br />
<br />-
<br />-
<br />
<br />ENGINEERED PLANS
<br />ON FILB
<br />
<br />ro
<br />$
<br />E
<br />QJ
<br />+J
<br />Vl
<br />
<br />>-
<br />~
<br />o
<br />I-
<br />Z
<br />W
<br />>
<br />Z
<br />
<br />Notice To Builder
<br />
<br />LU
<br />::E
<br />O~
<br />~z
<br />()~
<br />o SHEET NO.
<br />-
<br />
<br />co
<br />
<br />a.:
<br />a::
<br />o
<br />u
<br />UJ
<br />::E
<br />o
<br />I
<br /><n
<br />:)
<br />lI'l
<br />~
<br />@
<br />
<br />CENTRAL FLORIDA DIVISION,
<br />TAMPA, FLORIDA 33609
<br />
<br />600 N. WESTSHORE BLVD. SUITE 600
<br />(813) 769-5277
<br />
<br />A
<br />
<br />IT IS THE INTENT OF Tl1IS DESIGNER THAT
<br />THESE PLANS ARE ACCURATE AND ARE
<br />CLEAR ENOUGH FOR THE LICENSED PROFESS-
<br />ONAL TO CONSTRUCT THIS PROJECT.
<br />IN THE EVENT THAT SOMETHING IS UNCLEAR
<br />OR NEEDS CtARIFlCATION..sTOP..AND CALL
<br />THE DESIGNER USTED IN Tl1IS TITlE PAGE. IT
<br />IS THE RESPONSIBILIlY OF Tl1E LICENSED
<br />PROFESSIONAL THAT IS CONSTRUCTING THIS
<br />PROJECT TO FULLY REVIEW Tl1ESE DOCUMENTS
<br />BEFORE CONSTRUCTION BEGINS AND ANY AND
<br />ALL CORRECTIONS, IF NEEDED, TO BE MADE
<br />BEFORE ANY WORK IS DONE.
<br />
<br />N
<br />~
<br />~
<br />+-I
<br />o
<br />.....I
<br />
<br />ANDOVER 2005
<br />
<br />LAST PLOT DA IT
<br />Mar. 23, 05
<br />
<br />COVER SHEET
<br />
<br />-
<br />
|