<br />TERMITE SPECIFICATIONS:
<br />
<br />1. A PERMANENT SIGN WHICH IDENTIFIES THE TERMITE TREATMENT PROVIDER
<br />AND NEED FOR RE-INSPECTION AND TREATMENT CONTRACT RENEWAL SHALL
<br />BE PROVIDED. THE SIGN SHALL BE POSTED NEAR THE WATER HEATER OR
<br />ELECTRIC PANEL.(FBC 104.2.6)
<br />
<br />2. CONDENSATE AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1'-0"
<br />AWAY FROM BUILDING SIDE WALKS.(FBC 1503.4.4)
<br />
<br />3. IRRIGATION/SPRINKLER SYSTEMS INCLUDING ALL RISERS AND SPRAY HEADS
<br />SHALL NOT BE INSTALLED WITHIN 1'-0" OF THE BUILDING SIDE WALLS.(FBC 1503.4.4)
<br />
<br />4. TO PROVIDE FOR INSPECTION FOR TERMITE INFESTATION, BETWEEN WALL
<br />COVERING AND FINAL EARTH GRADE SHALL NOT BE LESS THAT 6 II\CHES.
<br />
<br />EXCEPTION: PAINT OR DECORATIVE CEMENTATIOUS FINISH LESS THAN 5/8"
<br />THICK ADHERED DIRECTLY TO THE FOUNDATION WALL.(FBC 1403.1.6)
<br />
<br />5. INITIAL TREATMENT SHALL BE DONE AFTER ALL EXCAVATION AND BACKFILL
<br />IS COMPLETE.(FBC 1816.1.1)
<br />
<br />6. SOIL DISTURBED AFTER THE INITIAL TREATMENT SHALL BE RETREATED
<br />INCLUDING SPACES BOXED AND FORMED.(FBC 1816.1.2)
<br />
<br />7. BOXED AREAS IN CONCRETE FLOORS FOR SUBSEQUENT INSTALLATION OF TRAPS,
<br />ETC., SHALL BE MADE WITH PERMANENT METAL OR PLASTIC FORMS. PERMANENT
<br />FORMS MUST BE OF A SIZE AND DEPTH THAT WILL ELIMINATE THE DISTURBANCE OF
<br />SOIL AFTER THE INITIAL TREATMENT.(FBC 1816.1.3)
<br />
<br />8. MINIMUM 6 MIL VAPOR RETARDER MUST BE INSTALLED TO PROTECT AGAINST RAINFALL
<br />DILUTION. IF RAINFALL OCCURS BEFORE VAPOR RETARDER PLACEMENT, RETREATMENT IS
<br />REQUIRED.(FBC 1816.1.4)
<br />
<br />9. CONCRETE OVERPOUR AND MORTAR ALONG THE FOUNDATION PERIMETER MUST BE
<br />REMOVED BEFORE EXTERIOR SOIL TREATMENT.(FBC 1816.1.5)
<br />
<br />10. SOIL TREATMENT MUST BE APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE
<br />WITHIN 1'-0" OF THE STRUCTURE SIDEWALLS.(FBC 1816.1.6)
<br />
<br />~1. AN EXTERIOR VERTICAL CHEMICAL BARRIER MUST BE INSTALLED AFTER CONSTRUCTION
<br />IS COMPLETE INCLUDING LANDSCAPING AND IRRIGATION. ANY SOIL DISTURBED AFTER
<br />THE VERTICAL BARRIER IS APPLIED, SHALL BE RETREATED.(FBC 1816.1.6)
<br />
<br />12. ALL BUILDINGS ARE REQUIRED TO HAVE PRE-CONSTRUCTION TREATMENT.(FBC 1816.1.7)
<br />
<br />13. A CERTIFICATE OF COMPLIANCE MUST BE ISSUED TO THE BUILDING DEPARTMENT
<br />BY A LICENSED PEST CONTROL COMPANY BEFORE A CERTIFICATE OF OCCUPANCY
<br />WILL BE ISSUED. THE CERTIFICATE OF COMPLIANCE SHALL STATE: "THE BUILDING
<br />HAS RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN
<br />TERMITES. THE TREATMENT IS IN ACCORDANCE WITH THE RULES AND LAWS OF THE
<br />FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER SERVICES."(FBC 1816.1.7)
<br />
<br />14. AFTER ALL WORK IS COMPLETED, LOOSE WOOD AND FILL MUST BE REMOVED FROM
<br />BELOW AND WITHIN 1'-0" OF THE BUILDING. THIS II\CLUDES ALL GRADE STAKES,
<br />TUB TRAY BOXES, FORMS, SHORING OR OTHER CELLULOSE CONTAINING MATERIAL.
<br />(FBC 2303.1.3)
<br />
<br />15. NO WOOD, VEGETATION, STUMPS, CARDBOARD, TRASH, ETC., SHALL BE BURIED
<br />WITHIN 15'-0": OF ANY BUILDING OR PROPOSED BUILDING,(FBC 2303.1.4)
<br />
<br />A.B.
<br />Abv.
<br />A/C
<br />Adj.
<br />A.F.F.
<br />A.H.U.
<br />ALT.
<br />B.C.
<br />B.F.
<br />Bk Sh
<br />Bm.
<br />BOT.
<br />B.P.
<br />Brg.
<br />Cir.
<br />Clg.
<br />Col.
<br />Compo
<br />C.T.
<br />D
<br />Dec.
<br />Ded.
<br />Dbl.
<br />Dia.
<br />Disp.
<br />Dist.
<br />D.S.
<br />D.V.
<br />DW.
<br />Ea.
<br />EW.
<br />Elec.
<br />Elev.
<br />Ext.
<br />Exp.
<br />
<br />ABBREVIA TIONS
<br />
<br />Anchor Bolt
<br />Above
<br />Air-Conditioner
<br />Adjustable
<br />Above Finished Floor
<br />Air Handler Unit
<br />Alternate
<br />Base Cabinet
<br />Blfold Door
<br />Book Shelf
<br />Beam
<br />Bottom
<br />Bypass door
<br />Bearing
<br />Circle
<br />Ceiling
<br />Column
<br />A/C Compressor
<br />Ceramic Tile
<br />Dryer
<br />Decorative
<br />Dedicated Outlet
<br />Double
<br />Diameter
<br />Disposal
<br />Distance
<br />Drawer Stack
<br />Dryer Vent
<br />Dishwasher
<br />Each
<br />Each Way
<br />Electrical
<br />Elevation
<br />Exterior
<br />Expansion
<br />
<br />F.B.C.
<br />Fin. Fir.
<br />F.G.
<br />Fir.
<br />Fdn.
<br />Fir. Sys.
<br />F.P!.
<br />Ft.
<br />Ftg.
<br />FX
<br />Galv.
<br />G.C.
<br />G.F.!.
<br />G.T.
<br />Hdr.
<br />Hgt.
<br />HB
<br />Int.
<br />K/Wall
<br />K.S.
<br />Laun.
<br />Lav.
<br />L.F.
<br />L.T.
<br />Mas.
<br />Max
<br />M.C.
<br />Mfgr.
<br />Micro.
<br />Min
<br />M.L.
<br />Mir.
<br />Mono
<br />N.T.S.
<br />
<br />Florida Bldg. Code
<br />Finished Floor
<br />Fixed Glass
<br />Floor
<br />Foundation
<br />Floor System
<br />Fireplace
<br />Foot / Feet
<br />Footing
<br />Fixed
<br />Galvanized
<br />General Contractor
<br />Ground Fault Interrupter
<br />Girder Truss
<br />Header
<br />Height
<br />Hose Bibb
<br />Interior
<br />Kneewall
<br />Knee Space
<br />Laundry
<br />Lavatory
<br />Linear Ft.
<br />Laundry Tub
<br />Masonry
<br />Maximum
<br />Medicine Cabinet
<br />Manufacturer
<br />Microwave
<br />Minimum
<br />Microlam
<br />Mirror
<br />Monolithic
<br />Not to Scale
<br />
<br />Opn'g.
<br />Opt.
<br />Pc.
<br />Ped.
<br />P.L.
<br />PLF
<br />PIt. Ht.
<br />Pit Sh.
<br />PSF
<br />P.T.
<br />Pwd.
<br />Rad.
<br />Ref.
<br />Req'd.
<br />Rm.
<br />Rnd.
<br />R/SH
<br />SD.
<br />S.F.
<br />Sh.
<br />SHT
<br />S.L.
<br />S.P.F.
<br />Sq.
<br />S.Y.P.
<br />Temp.
<br />Thik'n.
<br />T.O.B.
<br />T.O.M.
<br />T.O.P.
<br />Trans.
<br />Typ.
<br />UCL
<br />U.N.O.
<br />VB
<br />Vert.
<br />V.L.
<br />VTR
<br />W
<br />W/
<br />W/C
<br />W.A.
<br />Wd
<br />WP
<br />
<br />N1ASTER REVISIONS
<br />
<br />DATE
<br />
<br />DESCRIPTION
<br />
<br />Opening
<br />Optional
<br />Piece
<br />Pedestal
<br />Parallam
<br />Pounds per linear foot
<br />Plate Height
<br />Plant Shelf
<br />Pounds per square foot
<br />Pressure Treated
<br />Powder Room
<br />Radius
<br />Refrigerator
<br />Required
<br />Room
<br />Round
<br />Rod and Shelf
<br />Smoke Detector
<br />Square Ft.
<br />Shelves
<br />Sheet
<br />Side lights
<br />Spruce Pine Fir
<br />Square
<br />Southern Yellow Pine
<br />Tempered
<br />Thicken
<br />Top of Block
<br />Top of Masonry
<br />Top of Plate
<br />Transom Window
<br />Typical
<br />Under Cabinet Lighting
<br />Unless Noted Otherwise
<br />Vanity Base
<br />Vertical
<br />Versalam
<br />Vent through Roof
<br />Washer
<br />With
<br />Water Closet
<br />Wedge Anchor
<br />Wood
<br />Water Proof
<br />
<br />STRUCTURAL NOTES:
<br />
<br />STRUCTURAL DESIGN CRITERIA
<br />
<br />FOUNDATIONS
<br />
<br />3. ANY WOOD FRAME INTERIOR BEARING WALL STUDS THAT
<br />HAVE HOLES IN THE CENTER OF THE STUD UP TO 1" DIA.
<br />SHALL HAVE STUD PROTECTION
<br />SHIELDS FOR ALL HOLES OVER 1" IN DIA.
<br />FOR PLUMBING LINES, ETC. SHALL BE REPAIRED WITH
<br />SIMPSON HSS2 STUD SHOES,TYP., U.N.O.
<br />
<br />CODES:
<br />
<br />FLORIDA BUILDING CODE, 2001 EDITION WITH 2003 REVISIONS
<br />BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE (ACI 318-02)
<br />SPECIFICATIONS FOR STRUCTURAL CONCRETE BUILDINGS (ACI 301-02)
<br />BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES (ACI 530-02)
<br />NATIONAL DESIGN SPECIFICATION FOR WOOD COI'.STRUCTION, 2001 EDITION
<br />APA PLYWOOD DESIGN SPECIFICATION
<br />
<br />SOIL TO BE COMPACTED TO AT LEAST 95%
<br />OF MAX. DRY DENSITY AS DETERMINED BY
<br />ASTM - 1557 ( MODIFIED PROCTOR)
<br />
<br />FOUNDATION INSPECTIONS
<br />
<br />A FOUNDATION SURVEY SHALL BE PERFORMED AND A
<br />COPY OF THE SURVEY SHALL BE ON SITE FOR THE BUILDING
<br />INSPECTORS USE, OR ALL PROPERTY MARKERS SHALL BE
<br />EXPOSED AND A STRING STRETCHED FROM MARKER TO
<br />MARKER TO VERIFY REQUIRED SETBACKS.
<br />
<br />CAST IN PLACE CONCRETE
<br />
<br />1. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE
<br />STRENGTH AT 28 DAYS OF 3000 PSI, A SLUMP OF 6"
<br />PLUS OR MINUS 1", AND HAVE 2 TO 5% AIR ENTRAINMENT,
<br />AND A MAXIMUM WATER/CEMENT RATIO OF 0.63
<br />2. ALL REINFORCING STEEL SHALL BE NEW DOMESTIC
<br />DEFORMED BILLET STEEL CONFORMING TO ASTM A-615
<br />GRADE 40.
<br />3. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185.
<br />WWF SHALL BE LAPPED AT LEAST 6" AND CONTAIN AT
<br />LEAST ONE CROSS WIRE WITHIN THE 6".
<br />4. HOOKS SHALL BE PROVIDED AT DISCONTINUOUS ENDS OF
<br />ALL TOP BARS OF BEAMS.
<br />5. HORIZONTAL FOOTING BARS SHALL BE BENT 1'-0"
<br />AROUND CORNERS OR CORNER BARS WITH A 2'-0"
<br />LAP PROVIDED
<br />6. MINIMUM LAP SPLICES ON ALL REINFORCING BAR
<br />SPLICES SHALL BE 40 BAR DIAMETERS TYP.
<br />7. CONCRETE COVER MIN. 3" WHEN EXPOSED TO EARTH OR
<br />11/2" TO FORM
<br />
<br />REINFORCING STEEL
<br />
<br />ALL REINFORCING STEEL SHALL BE NEW DEFORMED BARS
<br />FREE FROM RUST, SCALE & OIL & SHALL MEET ASTM A-615
<br />REINFORCING FOR FOOTING SHALL BE SUPPORTED ON PRE-
<br />CAST CONCRETE PADS, TOP REINFORCING SHALL BE
<br />POSITIVELY SUPPORTED BY TEMPORARY STRINGERS.
<br />DOWELS FOR COLUMNS & FILLED CELLS SHALL BE SECURED
<br />IN PLACE BY USING ADDITIONAL CROSS- REINFORCING TIED
<br />TO FOOTING REINFORCING. SPLICES IN REINFORCING WHERE
<br />PERMITTED SHALL BE THE FOLLOWING MINIMUM, UNLESS
<br />OTHERWISE INDICATED ON THE DRAWINGS:
<br />
<br />FTGS, WALLS, COLUMNS, BEAMS, SLABS: 36 DIA. OR 2'-0" MIN., WHICHEVER IS MORE.
<br />FILLED CELL REINFORCING: 40 DIA. OR 2'-0" MIN., WHICHEVER IS MORE.
<br />TEMPERATURE REINFORCING: 20 DIA. OR 1'-0" MIN., WHICHEVER IS MORE.
<br />WELDED WIRE MESH: 8" LAP
<br />
<br />WOOD FRAMING INSPECTION
<br />
<br />LIVE LOADS:
<br />
<br />ROOF
<br />RESIDENTIAL FLOOR, UNLESS OTHERWISE INDICATED
<br />BALCONIES
<br />STAIRS
<br />LIGHT PARTITIONS (DEAD LOAD), U.N.O.
<br />
<br />WIND LOADS BASED ON FBC, SECTION 1606.2.
<br />WIND VELOCITY: 123 M.P.H., USE FACTOR: 1.0
<br />
<br />20 PSF (REDUCIBLE)
<br />40 PSF
<br />40 PSF
<br />40 PSF
<br />20 PSF
<br />10 PSF ATTIC L.L.
<br />
<br />ALL PLUMBING, ELECTRICAL, AND MECHANICAL
<br />ROUGH-INS MUST BE COMPLETE, INSPECTED
<br />AND APPROVED BEFORE REQUESTING FRAMING
<br />INSPECTION.
<br />
<br />PREFABRICATED WOOD TRUSSES
<br />
<br />1. ALL PREFABRICATED WOOD TRUSSES SHALL BE SECURELY
<br />FASTENED TO THEIR SUPPORTING WALLS OR BEAMS WITH
<br />HURRICANE CLIPS OR ANCHORS.
<br />2. PREFABRICATE WOOD TRUSSES SHALL BE DESIGNED IN
<br />ACCORDANCE WITH THE LATEST EDITION OF THE "NATIONAL
<br />DESIGN SPECIFICATION FOR STRESS-GRADE LUMBER AND
<br />ITS FASTENERS" AS RECOMMENDED BY THE NATIONAL
<br />FOREST PRODUCTS ASSOCIATION.
<br />3. TRUSS MEMBERS AND CONNECTIONS SHALL BE PROPOR-
<br />TIONED ( WITH A MAXIMUM ALLOWABLE STRESS INCREASE
<br />FOR LOAD DURATION OF 25%) TO WITHSTAND THE LIVE
<br />LOADS GIVEN IN THE NOTES AND TOTAL DEAD LOAD.
<br />4. BRIDGING FOR PRE-ENGINEERED TRUSSES SHALL BE AS
<br />REQUIRED BY THE TRUSS MANUFACTURER UNLESS
<br />NOTED ON THE PLANS.
<br />5. TRUSS ELEVATIONS AND SECTIONS ARE FOR GENERAL
<br />CONFIGURATION OF TRUSSES ONLY. WEB MEMBERS ARE
<br />NOT SHOWN, BUT SHALL BE DESIGNED BY THE TRUSS
<br />MANUFACTURER IN ACCORDANCE WITH THE FOLLOWING
<br />DESIGN LOADS:
<br />6. DESIGN SPECIFICATIONS FOR LIGHT WEIGHT METAL
<br />PLATE CONNECTED WOOD TRUSSES PER THE TRUSS
<br />PLATE INSTITUTE TPI LATEST EDITION.
<br />7. PRE-ENGINEERED WOOD TRUSSES SHALL BE DESIGNED BY
<br />THE MANUFACTURER IN ACCORDANCE WITH SPECIFIED LOADS
<br />AND GOVERNING CODES. SUBMITTALS SHALL INCLUDE TRUSS
<br />FRAMING PLANS AND DETAILS SHOWING MEMBER SIZES,
<br />BRACING, ANCHORAGE, CONNECTIONS, TRUSS LOCATIOI'.S, AND
<br />AND PERMANENT BRACING AND/OR BRIDGING AS REQUIRED
<br />FOR ERECTION AND FOR THE PERMANENT STRUCTURE. EACH
<br />SUBMITTAL SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />REGISTERED STRUCTURAL ENGINEER. SUBMIT 3 COPIES FOR
<br />REVIEW AND APPROVAL PRIOR TO FABRICATION.
<br />8. THE TRUSS MANUFACTURER SHALL DETERMINE ALL SPANS
<br />WORKING POINTS, BEARING POINTS, AND SIMILAR CONDITIONS.
<br />TRUSS SHOP DRAWINGS SHALL SHOW ALL TRUSSES, ALL
<br />BRACING MEMBERS, AND ALL TRUSS TO TRUSS HANGERS.
<br />
<br />WIND LOADS:
<br />(F. B.C.)
<br />
<br />CONCRETE
<br />STRENGTH
<br />@ 28 DAYS
<br />
<br />ALL CONCRETE UNLESS OTHERWISE INDICATED
<br />PEA GRAVEL CONCRETE FOR MASONRY CELLS ONLY
<br />(DO NOT USE FOR CONCRETE COLUMNS OR TIE BEAMS)
<br />
<br />3000 PSI
<br />3000 PSI
<br />
<br />REINFORCING:
<br />
<br />WELDED WIRE FABRIC SHALL CONFORM TO
<br />ALL REINFORCING BARS
<br />ALL STIRRUPS AND TIES
<br />
<br />ASTM A185
<br />ASTM A61540 40,000 PSI
<br />ASTM A615-40 40,000 PSI
<br />
<br />CONCRETE
<br />MASONRY
<br />UNITS:
<br />
<br />ASTM C90-99b, STANDARD WEIGHT UNITS, fm=1500 PSI
<br />MORTAR TYPE "S" 1800 PSI
<br />CONCRETE GROUT 3000 PSI
<br />CONTINUOUS MASONRY INSPECTION IS REQUIRED DURING CONSTRUCTION
<br />
<br />ALL STRUCTURAL AND MiSCELLANEOUS STEEL A36 36,000 PSI, U.N.O
<br />SHOP AND FIELD WELDS: E70XX ELECTRODES
<br />ALL BOLTS CAST IN CONCRETE: ASTM A36 OR ASTM A-307
<br />
<br />BEAMS, RAFTERS, JOIST, PLATES, ETC. U.N.O.
<br />1\0. 2 SOUTHERN YELLOW PINE (19% M.C.)
<br />ROOF DECK: PLYWOOD C-C/C-D, EXTERIOR, or OSB
<br />FLOOR SHEATHING: T&G A-C GROUP 1 APA RATED (48/24)
<br />WALL SHEATHING: PLYWOOD C-C/C-D, EXTERIOR OR OSB
<br />VERSA LAM BEAM Fb = 2900 PSI (2.0E)
<br />WOOD COLS. PARALLAM 2.0E U.N.O.
<br />
<br />DESIGN LOADS:
<br />TOP CHORD LIVE LOAD: 20 PSF
<br />TOP CHORD DEAD LOAD: 10 PSF
<br />
<br />STRUCTURAL
<br />STEEL:
<br />
<br />WOOD FRAMING:
<br />
<br />WOOD ROOF
<br />TRUSSES:
<br />
<br />BOTTOM CHORD DEAD LOAD:
<br />
<br />10 PSF
<br />40 PSF
<br />
<br />10 PSF
<br />
<br />BOTTOM CHORD ATTIC LIVE LOAD:
<br />
<br />SEE DRAWINGS FOR SPECIAL CONCENTRATED LOADS. DESIGN
<br />FOR NEW WIND UPLIFT AS PER SPECIFIED CODES, DEDUCTING
<br />A MAXIMUM OF 5 P.S.F. DEAD LOAD, BUT NOT EXCEEDING ACTUAL
<br />DEAD LOAD.
<br />
<br />DESIGN LOADS:
<br />DEAD LOAD:
<br />LIVE LOAD:
<br />TOTAL:
<br />
<br />MASONRY WALL CONST.
<br />1. HOLLOW LOAD BEAR/l\G UNITS SHALL BE NORMAL
<br />WEIGHT, GRADE N, TYPE 2, CONFORMING TO ASTM C90,
<br />WITH A MINIMUM NET COMPRESSIVE STRENGTH OF
<br />1900 PSI ( f'm = 1500 PSI)
<br />2. MORTAR SHALL BE TYPE "S", CONFORMING TO
<br />ASTM C270.
<br />3. COARSE GROUT SHALL CONFORM TO ASTM C476 WITH A
<br />MAXIMUM AGGREGATE SIZE OF 3/8" AND A MINIMUM
<br />COMPRESSIVE STRENGTH OF 3000 PSI SLUMP 8" TO 11".
<br />4. VERTICAL REINFORCEMENT SHALL BE AS NOTED ON THE
<br />DRAWINGS WITH THE CELLS FILLED WITH COARSE GROUT.
<br />5. VERTICAL REINFORCEMENT SHALL BE HELD IN POSITION
<br />AT THE TOP AND BOTTOM AND AT A MAXIMUM SPACING
<br />OF 192 BAR DIAMETERS. REINFORCEMENT SHALL BE PLACED
<br />IN THE CENTER OF THE MASONRY CELL TYPICAL UNLESS
<br />OTHERWISE NOTED.
<br />6. REINFORCING STEEL SHALL BE LAPPED A MINIMUM OF 40 BAR
<br />DIAMETERS, UNLESS OTHERWISE NOTED ON THE DRAWINGS
<br />7. GROUT STOPS SHALL BE PROVIDED BELOW BOND BEAM. PLASTIC
<br />SCREEN, METAL LATH STRIP OR CAVITY CAPS MAY BE USED TO
<br />PREVENT THE FLOW GROUT INTO CELLS BELOW. THE USE OF FELT
<br />PAPER AS A STOP IS PROHIBITED.
<br />
<br />UPLIFT CONNECTORS
<br />
<br />1. UPLIFT CONNECTORS SUCH AS HURRICANE CLIPS, TRUSS
<br />ANCHORS AND ANCHOR BOLTS ARE ONLY REQUIRED ON
<br />MEMBERS IN WALLS THAT ARE EXPOSED TO UPLIFT FORCES.
<br />INTERIOR LOAD BEARING WALLS ARE NOT ALWAYS EXPOSED
<br />TO UPLIFT FORCES. THE MEMBERS OF THESE WALLS WOULD
<br />NOT NEED TO HAVE CONNECTORS APPLIED. PLEASE CONSULT
<br />THE TRUSS ENGINEERING FOR THE LOCATION OF THESE WALLS.
<br />
<br />WOOD FLOOR
<br />TRUSSES:
<br />
<br />15 PSF
<br />50 PSF
<br />65 PSF
<br />
<br />ASSUMED ALLOWABLE SOIL BEARING PRESSURE AFTER COMPACTION: 2000 PSF
<br />SEE SOILS REPORT AND SPECIFICATIONS FOR COMPACTION REQUIREMENTS
<br />IF SOIL CONDITIONS IN THE PROJECT DO NOT MEET OR EXCEED THE CAPACITY
<br />THE GENERAL CONTRACTOR SHALL CONTACT THE EI\GINEER PRIOR TO
<br />FOUNDATION POUR FOR VERIFICATION OF FOUNDATION DESIGN.
<br />
<br />SOIL BEARING
<br />VALUE:
<br />
<br />~
<br />,
<br />
<br />BUILDING DATA
<br />
<br />CONSTRUCTION TYPE - TYPE VI UNPROTECTED
<br />(SECTION 608 - FBC 2001)
<br />MEAN ROOF 15 FT. HIGH
<br />TYPICAL FOR SINGLE HOMES
<br />
<br />WIND SPEED 123 MPH (3 SEC. GUST)
<br />WIND IMPORTANCE FACTOR - (Iw) = 1.0
<br />WIND EXPOSURE - "B" (FBC 1606.1.8)
<br />INTERNAL PRESSURE COEFFICIENT = +/- 0.55 (PARTIALLY
<br />ENCLOSED BLDG)
<br />
<br />WOOD CONSTRUCTION
<br />
<br />1. WOOD CONSTRUCTION SHALL CONFORM TO THE NFPA
<br />"NATIONAL DESIGN SPECIFICATION FOR WOOD
<br />CONSTRUCTION", LATEST EDITION.
<br />2. ALL EXTERIOR WOOD STUD WALLS, BEARING WALLS, SHEAR
<br />WALLS AND MISC. STRUCTURAL WOOD FRAMING MEMBERS,
<br />( I.E. BLOCKING OR GABLE END BRACING) SHALL BE EITHER
<br />SOUTHERN PINE, OR S.P.F. NUMBER 2 GRADE SHALL BE
<br />USED REGARDLESS OF SPECIES.
<br />
<br />DESIGN WIND PRESSURE:
<br />
<br />(COMPONENT AND CLADDING) WORST CASE (10 SF - END ZONE)
<br />WINDOWS AND DOORS
<br />123 MPH + 38 PSF / - 40 PSF
<br />
<br />GARAGE DOORS (V = 123 MPH)
<br />SINGLE 9x7 +37.0 PSF / 40.0 PSF
<br />DOUBLE 16x7 +37.0 PSF / 41.0 PSF
<br />
<br />SEE FLOOR PLAN FOR ACTUAL PRESSURES
<br />
<br />ALL WORK SHALL COMPLY WlTHALL
<br />PREVAILING CODES, FLORIDA BUlLDn-:G
<br />CODE, NATIONAL ELECTRIC CODE AND
<br />CITY OF ZEPHYRHILLS ORDINANCES
<br />
<br />
<br />ENGINEERED PLANS
<br />ON FILE
<br />
<br />REVIEWED
<br />NAY 1 02005
<br />
<br />~&r
<br />
<br />WALDEN GRANDE 2003 STEM WALL
<br />
<br />GENERAL NOTES:
<br />
<br />THE FOLLOWING TECHINCAL CODES
<br />SHAll APPLY:
<br />2001 FLORIDA BUILDING CODE,
<br />WITH 2003 REVISIONS
<br />PLUMBING, MECHANICAL, FUEL GAS,
<br />ENERGY EFFICIENCY, ACCESSIBILITY,
<br />AND NFPA 70-02 NATIONAL ELECTRICAL CODES
<br />
<br />1. TANK TYPE WATER CLOSET VOLUME
<br />1.6 GALLONS
<br />2. WALL MOUNT WATER CLOSET VOLUME
<br />3.5 GALLONS
<br />3. WATER - FLOW RATE.
<br />PUBLIC FACILITIES 0.5 G.P.M.
<br />PRIVATE FACILITIES 2.2 G.P.M.
<br />SHOWER HEADS 2.5 G.P.M.
<br />4. ALL WATER LINE PLUMBING
<br />TO BE PVPC
<br />VTR LOCATIONS ARE APPROXIMATE
<br />AND MAY CHANGE DUE TO JOBSITE
<br />CONDITIONS
<br />
<br />THE FOLLOWING SHALL COMPLY
<br />WITH THE 2001 FBC.
<br />
<br />o PORCHES AI\D BALCONIES
<br />SECTION 1014
<br />o HANDRAILS - SECTION 1007.5
<br />o GUARDRAILS - SECTION 1015, 1019.9
<br />o STAIRS - SECTION 1007
<br />o CHIMNEY & FIREPLACE
<br />SECTION 2804-2806 (MFGR)
<br />SECTION 2113-2114 (MAS)
<br />o EGRESS WINDOWS
<br />SECTION 1005.4
<br />
<br />5. ALL OPENINGS SHALL COMPLY WITH
<br />2001 FBC WII\JD LOADS AS STATED
<br />BELOW. ATTACHMENTS OF WINDOWS,
<br />DOORS, SLIDING GLASS DOORS
<br />AND O.H. GARAGE DOORS ARE TO DELEGATED
<br />THE MANUFACTURER OF THESE ITEMS. THE
<br />MANUFACTURER OF THESE ITEMS
<br />SHALL SUBMIT ATTACHMENTS FOR
<br />SITE INSTALLATION.
<br />
<br />SEE ATTACHED SPECIFICATION SHEETS FOR
<br />MANUFACTURERS DESIGN CRITERIA AND
<br />INSTALLATION METHODS FOR WINDOWS,
<br />DOORS, SLIDING GLASS DOORS, OVERHEAD
<br />GARAGE DOORS, AND ROOFING.
<br />
<br />6. ALL DOORS INTERIOR & EXTERIOR ARE
<br />6'-8" UNLESS OTHERWISE NOTED
<br />ALL SHOWER ENCLOSURES TO BE
<br />TEMPERED GLASS
<br />7. ALL WINDOWS WITHIN 24" OF DOORS
<br />(INTERIOR & EXTERIOR) AI\D WITHIN
<br />18" OF FLR TO BE TEMPERED GLASS.
<br />(SECTION 2405.2)
<br />
<br />-'
<br />
<br />SHT NO:
<br />1
<br />2
<br />2A
<br />3
<br />4
<br />5
<br />6
<br />S-1
<br />S-2
<br />S-3
<br />S-4
<br />S-5
<br />S-6
<br />S-7
<br />
<br />S-8
<br />S-9
<br />S-10
<br />S-11
<br />S-12
<br />S-13
<br />S-14
<br />S-15
<br />S-16
<br />S-17
<br />S-18
<br />
<br />INDEX OF DRAWINGS
<br />
<br />TITLE
<br />COVER SHEET
<br />FLOOR PLAN
<br />DIMENSION PLAN
<br />FOUNDATION PLAN
<br />ELECTRICAL PLAN/ INT. ELEV.
<br />ELEVATIONS
<br />TRUSS LAYOUT
<br />MASONRY DETAILS
<br />LINTEL PLAN AND DETAILS
<br />DETAILS
<br />DETAILS
<br />DETAILS
<br />DETAILS
<br />STRUC. NOTES &
<br />HANGER INFORMATION
<br />DETAILS
<br />DET AI LS
<br />ROOFING DETAILS
<br />DETAILS
<br />DETAILS
<br />PRODUCT APPROVAL
<br />WINDOW DETAILS
<br />WINDOW DETAILS
<br />DETAILS
<br />DETAILS
<br />DETAILS
<br />
<br />NOTICE TO BUILDER
<br />
<br />IT IS THE INTENT OF THIS DESIGNER THAT
<br />THESE PLANS ARE ACCURATE AND ARE
<br />CLEAR ENOUGH FOR THE LICENSED PROFESS-
<br />ONAL TO CONSTRUCT THIS PROJECT.
<br />IN THE EVENT THAT SOMETHING IS UNCLEAR
<br />OR NEEDS CLARIFICATION..STOP..AND CALL
<br />THE DESIGNER LISTED IN THIS TITLE PAGE. IT
<br />is THE RESPONSIBILITY OF THE LICENSED
<br />PROFESSIONAL THAT IS CONSTRUCTING THIS
<br />PROJECT TO FULLY REVIEW THESE DOCUMENTS
<br />BEFORE CONSTRUCTION BEGINS AND ANY AND
<br />ALL CORRECTIONS, IF NEEDED, TO BE MADE
<br />BEFORE ANY WORK IS DONE.
<br />
<br />W
<br />LL~C(
<br />w'oa:fr
<br />~w:2=1-
<br />:2=90~
<br />W x~C(O
<br />U O::::)LLU
<br />L- C(OZU
<br />r- CL"",w<l:
<br />O CL""'::S::I-
<br /><l:0<l:0
<br />Z wC(l-z
<br />C(LLW
<br />W <l:zC(O
<br />I'M ow<l:O
<br />~ w::s::(/)O
<br /><Cf- 01-;:: Z Z
<br />o<l:
<br />O ::::)w-w
<br />oC((/)"'"
<br /><l: z "'" .
<br />o ~(/)W<l:z
<br />LL t:lZ~a:Q
<br /><l:0001-
<br />w 5CJ;C(1-()
<br />0::: 06]Q::S:::J
<br /><C LL"",C(UCL
<br />W""'wOCL
<br />=> C(ol-~<l:
<br />'"'" <l: Z u.J ...J
<br />~ ::J...J-o::...J
<br />CJ) o(/) ~ u) 0 ~<l:
<br />C(...J........
<br />w.....JO
<br />::j>~zC(
<br /><l:0::><l:0
<br />
<br />tJ)
<br />Q)Q)...J
<br />(l)ta~
<br />Q)._ 0
<br />Q)(.)CJ;
<br />~ ~ ~
<br />I tJ) ~
<br />(l)caCL
<br />Q)C@
<br />- 'OJ) u:
<br />n:s.- -
<br />...tJ)~
<br />OQ)w
<br />e"CU
<br />
<br />
<br />w t:l 0
<br />I ~ ~ Z
<br />1-. (/) 3: CD
<br />t:lZw <l:CDM
<br />(/)~Qo C(NCD (I)
<br />- 01-0 OM:t.t: Z
<br />ffiz()u w~~Li 0
<br />~;::u:t:l II:t.t:. i=
<br />_(/)-z I-I-..JL/J ::;)
<br />t:l C( ~ 0 C( LL U. 0.. ..J
<br />zWCL.....J 00.. 0
<br />W9(/)S(/)LLZ~~ (I)
<br />wZ(/)a::lZOO C Z
<br />I::JZWQ::Ji=z.o: ~-
<br />I-OjI(/)<l:C(3::J
<br />i5ZCLI->lJ.J~Oa:l (I)
<br /><l: I W (/) 0:' IJ.I
<br />~w~t::C(O~a:I~ C
<br />wgO::3:(V)zC( 'L/J _
<br />a::lw::::) O<l:::::)otot .....
<br />w.....JI-~~OI-..J:c C
<br />I3:UCL wuo:o 0::
<br />1-0::::):2=IZ::::)ot;:;: -
<br />C( I- t:l C( 0 0=: 0
<br />o Z I- 0 :> - 1-00 ..J
<br />I-::S::(/)U::>(/)(/) U.
<br />
<br />
<br />~Il'
<br />~ ~ 0
<br />~<(CO
<br />
<br />(/)
<br />w
<br />o
<br />t:l
<br />Z
<br />o
<br />...J
<br />::J
<br />co
<br />
<br />...J
<br /><l:
<br />0::
<br />I-
<br />:2=
<br />o
<br />(/)
<br />(/) w
<br />o U
<br />.....J (V) u: ><
<br />co 0 LL <l:
<br />w1'- OLL
<br />t:l N (V) '<t
<br />Z (V) (V) 0
<br /><l:.....J (V) (V)
<br />C(LL NN
<br />o ... . I
<br />.;2 ~ ~
<br />(/) CL co co
<br />LI)O ~~
<br />'<tCL 00
<br />O'l <l: '<t '<t
<br />
<br />O'l
<br />o
<br />(V)
<br />N
<br />6 z
<br />co 0
<br />...: 0;> ~
<br />I- b(/)b!
<br />E '<t
<br />~ ~w
<br />:g LL
<br />as8~z~
<br />~~~
<br />c(V).,j- w
<br />~...J....,C(
<br />OLLCO::::)
<br />. , I- U
<br />ujC01'-uu:....,
<br />-6. ~ ::::) i= O'l I-
<br />""'0 C(C(.......
<br />li)Q.II-WO .......
<br />O'l <l: CL (/) U Z a
<br />
<br />
<br />o
<br />o
<br />III
<br />W
<br />f-
<br />- 0
<br />::J ~
<br />Z Ul ,... I:'
<br />o 0 ,... I:'
<br />- > I N
<br />Ul..JC'\lfl
<br />- OJ 0 I
<br />> III C'\
<br />(iWMIll
<br />Il: I:'
<br />( 0 M I
<br />Q.I..JM
<br />Ul lL ,...
<br />~f-<(OJ
<br />(Ulll. I
<br />I- W ,...
<br />~ ~
<br />.1-
<br />Z
<br />o
<br />o
<br />I.ll
<br />
<br />o
<br />z W
<br />" Z
<br />u;~~ 0
<br />Wf-(/)W::J
<br />oz(/)==<
<br />O-I>
<br />~~!=?:(/)
<br /><C\lwo::l:
<br />"rl:;Coo
<br />~o::ooO
<br />?:~W~()
<br />C202=t::5~
<br />o::Jo::(/)~
<br />~~too::
<br />2=~<~a
<br />
<br /> LI)
<br /> C'\J(J) 0
<br /> ........
<br /> ....,
<br /> 'Z U"-
<br /> ~O I-(V)
<br /> <l:CL
<br /> C'\J- 1'-0
<br /> M(J) c.o........
<br /> > '<t<l:
<br /> ....,0
<br /> W '::S::
<br /> 0::: ~:2=
<br /><.0 l.1J-I
<br />~ :2=
<br />(j) 0-1 w 0
<br />0 C(
<br /> z<( U >-LLZ
<br />.....J zl-O
<br />0 <(~ <l:z-
<br />.....J f- ZW~
<br /> -(/)>
<br />I o::~ 0 oZo
<br />N - tsO<l:
<br />:c z ::::)UO
<br />L() 0lLJ oz-
<br /> owC(
<br /> Zl- f- O::f:S
<br />I S CL-LL
<br />I'- I wC(.....J
<br /> l.1J(/) C(3:<l:
<br /> WWC(
<br />~ lLJ ~ COIl-
<br />wO(Y) 1-1-6]
<br /> Ol-u
<br />~ - ~ -I 0 0::: Z::::) .
<br />> >-OCL
<br /> ~ <( 0 >- <l:Ic(
<br />L() ~ :2=t::0
<br />Z~ N 0... z3:U
<br />~ jO::w
<br />(j) 0 w:2=
<br />:5 CLZO
<br /> (/)ZI
<br />>- lLJ Q.. U -<(/)
<br /> 2=:2=::::)
<br />0::: 0::: SHEET NO. CL
<br /> C(
<br />'-' 0
<br />0 1 U
<br /> w
<br />~ <.0 :2=
<br /> 0
<br /> OF I
<br />Z (/)
<br />~ 25 ::::)
<br /> (V)
<br />lLJ 0
<br />~ 0
<br />> LAST PLOT DATE N
<br /> @
<br />0 March 02,2005
<br />Z
<br />.....J COVER SHEET
<br />-
<br />
|