Laserfiche WebLink
<br />FIRE - Fire Sprinkler Hydraulics Calculation Program <br />Kenyon & pqrtners Inc. 813-241-6488 813-241-5498 Fax <br />EPCH Wound Care Center Page 5 <br /> <br />Elite Software Development, Inc. <br /> <br />I Fire Sprinkler Output Data <br /> <br /> <br />Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance <br />Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg. <br />Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm) <br /> 2 0 132.47 0.00 0.00 0.00 43.91 <br />2 1 0 -132.47 0.00 0.00 0.00 37.10 -0.00006 <br />2 3 0 32.67 <br />2 5 0 99.80 <br />3 2 0 -32.67 32.75 0.00 0.00 34.20 0.07695 <br />3 4 0 0.00 <br />4 3 0 0.00 0.00 0.00 0.00 34.20 -0.00195 <br />5 2 0 -99.80 0.00 0.00 0.00 31.41 -0.00004 <br />5 6 0 53.33 <br />5 8 0 46.47 <br />6 5 0 -53.33 27.56 0.00 0.00 24.22 0.04572 <br />6 7 0 25.81 <br />7 6 0 -25.81 25.84 0.00 0.00 21.30 0.03172 <br />8 5 0 -46.47 24.02 0.00 0.00 18.40 0.00133 <br />8 9 0 22.45 <br />9 8 0 -22.45 22.50 0.00 0.00 16.14 0.04610 <br /> <br />Active Version <br /> <br />200 Pipe Capacity <br /> <br />Wednesday, March 12,2008 <br />