Laserfiche WebLink
<br />FIRE - Fire Sprinkler Hydraulics Calculation Program <br />Kenyon & Pa.rtners Inc. 813-241-6488 813-241-5498 Fax <br />EPCH Wound Care Center Page 8 <br /> <br />Elite Software Development, Inc. <br /> <br />I Fire Sprinkler Output Summary <br /> <br /> <br />HMD Sprinkler Node Number: <br />HMD Actual Residual Pressure: <br />HMD Actual GPM: <br /> <br />9 <br />16.14 psi <br />22.50 gpm <br /> <br /> <br />Sprinkler System Type: <br />Specified Area Of Application: <br />Minimum Desired Density: <br />Application Average Density: <br />Application Average Area Per Sprinkler: <br />Sprinkler Flow: <br />Average Sprinkler Flow: <br /> <br />WET <br />1500.00 ft2 <br />0.100 gpm/ft2 <br />0.088 gpm/ft2 <br />300.00 ft2 <br />132.67 gpm <br />26.53 gpm <br /> <br /> <br />Maximum Flow Velocity ( In Pipe 5 - 6 ) <br />Maximum Velocity Pressure ( In Pipe 5 - 6 ) <br /> <br />19.80 ftlsec <br />0.05 psi <br /> <br />Allowable Average Nodal Pressure Imbalance: <br />Actual Maximum Nodal Pressure Imbalance: <br />Actual Average Nodal Pressure Imbalance: <br />Actual Maximum Nodal Flow Imbalance: <br />Actual Average Nodal Flow Imbalance: <br /> <br />0.0500 psi <br />0.0653 psi <br />0.0269 psi <br />0.0770 gpm <br />0.0227 gpm <br /> <br /> <br />Number Of Unique Pipe Sections: <br />Number Of Flowing Sprinklers: <br /> <br />8 <br />5 <br /> <br />Sprinkler Flow: <br />Non-Sprinkler Flow: <br />Total System Demand Flow: <br /> <br />132.67 gpm <br />0.00 gpm <br />132.67 gpm <br /> <br />Minimum Required Residual Pressure At System Inflow <br />Node: <br />Demand Flow At System Inflow Node: <br /> <br />43.91 psi <br />132.47 gpm <br /> <br />Active Version <br /> <br />200 Pipe Capacity <br /> <br />Wednesday, March 12,2008 <br />