<br />Gamewell
<br />r:':n FIRE CONTROL
<br />- I.i..:U li\JSTRUMENTS
<br />
<br />Ill-MB-E3
<br />
<br />by Honeyvvell
<br />
<br />Series
<br />
<br />Description
<br />
<br />11I-MB-E3
<br />
<br />The Intelligent Loop Interface-Main Board (/L1-MB-E3) is
<br />the main interface for the E3 Series™ product line. With its
<br />state-of-the-art 32 bit RISC processor, this compact "panel
<br />on a board" provides a powerful addition to Gamewell-
<br />FCl's single pair conductor solutions. This intuitive design
<br />provides two (2), signalin';J line circuits, two (2), notification
<br />application circuits, local energy city box output, auxiliary
<br />relay functions, and auxiliary power output. These features,
<br />combined with built-in nE,twork and serial protocols, allow
<br />this module to support a host of new and existing products,
<br />resulting in a building block approach to fire alarm panel
<br />design.
<br />
<br />Intelligent Loop
<br />
<br />Interface-Main Board
<br />
<br />
<br />Il'~]J~~~~~~ff~'i"'~<~'~~~=:'1
<br />:""it. 7~ ':~:-F;"'~;x."'" ;~-fi1.::',-.! _< _.
<br />_.~r ..".- ,.,oil!';'.!". ~'.~i-;'\ 1:;;,..'-6;-'-'..!..,.'.. :~1
<br />. ., .;or-' -.. ".,. . I ~ ~ "~"J 1 . "'-./. I
<br />. _I ..i-.!:\- ....1. ., '>"j '.0- "__ .
<br />
<br />1:;:~'~j;I~:j,i ill' i-li t}i't~ :;1
<br />~~:~:pli;.'.,'~;.J:: . ~,; '.llt.:... ~ '.: . . .
<br />~i.~. .!;~~tl-~ _: ~:::.) -',.-3ij I
<br />""',. .....:."'t....'-~ ~-. -,~~ 0>'"00' J ;.......;--;, "'1' ;""'" ~.
<br />_.~. .....",... I~. .l I'....... . .. "
<br />'4 - . I~ " !..~';!!~t.-;~,. 1_~:.:..::.:...'"_. ~_':-
<br />
<br />
<br />ILI-MB-E3
<br />
<br />Features
<br />
<br />The ILI-MB..E3 is network ready and occupies one of 64
<br />nodes, operating at 625K baud. When this sub-assembly is
<br />integrated with proven Broadband components, the result
<br />is a flexible yet powerful integrated audio solution. When
<br />transmitting to remote locations, the optional RPT-E3 pro-
<br />vides the ILI-MB-E3 with valuable signal boosting and tran-
<br />sient protection, as well as connectivity using both wire and
<br />fiber-optic cables.
<br />
<br />IL.I-MB-E3 and 11I-S-E3:
<br />. Listed under UL Standard 864, 9th Edition.
<br />. Network ready integral 625K baud ARCNET.
<br />. 115.2K baud RS-232.
<br />. Signaling line circuits with:
<br />- Two (2), Class A, Style 6, 7* or Class 8, Style 4
<br />circuits.
<br />- 40 Character user-defined text per device.
<br />- Capacity of 159 sensors and 159 addressable.
<br />modules per circuit.
<br />. 4'100 event history log.
<br />*Style 7 wiring requires the use of System Sensor M500X
<br />Isolator Modules.
<br />ILI-ftIIB-E3 Only:
<br />. Two (2), notification appliance circuits, Class "A", Style Z
<br />or Class 8, Style Y rated at 2.0 amps. per circuit.
<br />. RS-485 supporting sixteen (16), ASM-16 switch mod-
<br />ules and/or ANU-48 LED driver modules.
<br />. Aiarm, trouble, and supervisory dry contacts Form "C",
<br />rated at 2 amp. @ 30 VDC (resistive).
<br />. S:Jpports six (6), locallremote LCD-E3 annunciators and
<br />five (5), LCD-7100 annunciators.
<br />
<br />The ILI-MB-E3 provides two (2), signaling line circuits and
<br />terminals for the connections to up to 159 detectors and
<br />159 modules per SLC in Velociti. In clip mode, each SLC
<br />supports tl9 detectors and 98 modules. The RS-485 inter-
<br />face can support up to a total of sixteen (16), ASM-16 and/
<br />or sixteen (16), ANU-48 remote LED driver modules.
<br />
<br />The ILI-MI3-E3 relay outputs include system alarm, super-
<br />visory, and system trouble contacts. The ILI-MB-E3 pro-
<br />vides output I'or a local energy city master box or remote
<br />location which is non power-limited. All other wiring is
<br />power-limited.
<br />
<br />An ISO 9000-2000 Company
<br />
<br />. ~~~I 1
<br />I 12 Clintonville Road Northford CT 06472-1610 USA. Tel: (203) 484-7161 . Fax: (203) 484-7118
<br />Speeiflcallons are for information only, are not intended for ir,stallatlon purposes. and a;e subject to c~ange without nollee. No responsibility is assumed by Gamewel~FCI for Iheir use. ,.,1
<br />l @2006 Hone)'YIelllmematlonallnc. All rights reserv~j. www.gamewell-fCI.com 9020-0605 Rev. E page 1 of 2 .
<br />
<br />--~--~------------~----~---~-
<br />
<br />SIGNAUNG
<br />
<br />@<S>MEA
<br />
<br />LISTED APPi;lOVED P.pPfOVell Appro...ed Denver
<br />S1869 30250415 231-oH 7165-0694:268 ~:::j Approved
<br />;165-0694:269 High Rl...
<br />
<br />City of
<br />Cbica.o
<br />
<br />City of
<br />
<br />E3 Series'" ana NetSOLO'" are trademarks of Honeywelllnlemalionallnc.
<br />
|