<br />Fire Test Specifications
<br />9000 Series Fire Test Mode suppr~$s reports to central General
<br />station so you can test Initiating ana indicating devices Contractor shall furnish and.install, where indicated em
<br />without transmitting alarms. Initiating Fire Test Mode. pl~:ms, a Radionics 9000 Series Control/Commuhlcator.
<br />sends "J=ire Walk Start" to central Station indicating start Panel sh~1l be listed by Underwriters Laboratories for
<br />oftest. Test events become "local only". COmmand center NFPA 72 Applications.
<br />shows how many points are to be tested. 9000 Series shall support initiating and indicating
<br />Each time a device Initiates an alarm, programmed point modules and Radionics Command Centers.. Power
<br />text displays atc:ommand center filnd tire bell.rings for 2 supply shall provide 1,4-amp @12VDCforall processing
<br />seconds, Automatic sensor reset feature allows functions and auxiliary requirements.
<br />continued testing of devices without time consuming trips
<br />to manually .resetsensors. At theer}d of test, cOmmand Software
<br />center displays number of untested points. You can also 9000 Series' programming Of all system funclions shal!
<br />view point text for each untested pc:lint be accomplished on. site using.. Radionics 05200
<br />PrOgramnieror remotely USing Remote AccountManager
<br />Ending Fire Test Mode, sends "Fire Walk End" to central softWare package. A programmable system passcode
<br />station indicating end of test shall be. used to prevent unauthorized remote
<br />Combining Access Control with Security and Fire programming.
<br />Detec;tion (074121D9412) Panel shall accommodate up to fOur separate telephone
<br />9000 Series' combined systems canheJp prevent false numbersJor primary, alternate and backup receivers,
<br />alarms making it easy to use one system that controls automatic test reports, selective relay ildlvation, and
<br />acCess, security, and fire functions. custom.text on associated command centers and
<br />AcCess control features of 07412/09412 candeny .annunciafoi's. . .
<br />a~durlnga",ne(fperlods, grant access only to certain'. 'l,hen resetting alarms, arming or disarming a
<br />authonzed. users depending wheth~r an area Is master., combination firelbUrglary and/or access control system,
<br />a~, pen~ anned or~. A1ann system can user shan be Identified by nameatid number.
<br />automatically dlS8nn when designated authorized users . .. ... .. ...
<br />are granted access. D7212/07412: Up to 99 users
<br />. D7412: Two (2) access doors /75 detection points 09112/09412: Up to 249.u~rs
<br />. 09412: Eight (8) access doors/246 detection points Panel's internal clock shall support Skeds {scheduled
<br />D921 08 A C ntroll teria. Mod I ev~ts,> fe~ture. User shall have OptiOn toaller Sked
<br />ccess 0 n ce . u.. activation times uSing a programmable passcode.
<br />Access Is granted from Wiegand format readers or Re- . .
<br />quest to Enter/Exit devices when connected to 092108. Up to 64 programmable scheduled event functions shall
<br />Also provided are connections for door point, strike, be available for controlling relayS, enablingpasscodes,
<br />buzzer and enclOsure tamper. (One 092108 required windows, and supporting serviCe alert feature,
<br />perdOOr'). .. Other programmable functions shan include fire alann
<br />. Each access door can be configured Independently reset commands, and day/dateltlme adjustments.
<br />. Door point controls ac:tess door and is part of alann Event Logger/Clock .
<br />system (door does not need double contacts) .. . . .
<br />" Door contact can reset strike time when opened 9000 Series' event log shall store up to 1000 events. All
<br />. Door contact can tenninate entry buzzer (if used) system ~vents shall include time, date and event with
<br />· Door contact is shunted when valid access is - area, pOint and user nUmber.
<br />
<br />. ~~~al buzzer can trigger prior to end of door Access events (optional) stored shall include: Access
<br />shunt period, waming user a "door left open- condi- g~nted, no entry, Request ",:0 Enter" and Request To
<br />tlon is about to occur. EXIt.. Logger records certain functIons entered at
<br />. Door point can be configured to generate alann or co":,mand ce:nters. Stored events in Logger shall be
<br />trouble (or have no response) when door Is left open retrievable With a Remote Account Manager software
<br />beyond shunt period package.
<br />. In addition to granting access, cards control whether
<br />system will diSann along with granting access
<br />. Door strik~ can release auto,!,atically during dis
<br />armed penods, then automatically re-lock when area
<br />is armed
<br />. Door can generate an alarm, trouble, (or have no
<br />response) depending on area's anned condition
<br />when door is opened outside authorized access
<br />period
<br />. REQUEST TO ENTER and REQUEST TO EXIT can
<br />be programmed to shunt door without activating
<br />strike
<br />" An option detennines whether access granted, no
<br />entry, request to enter, or request to exit messages
<br />are sent to event log
<br />
<br />1
<br />
<br />I
<br />
<br />~
<br />
<br />
<br />I
<br />I,';
<br />"~I
<br />
<br />Remote Diagnostics and Controls
<br />
<br />9000 Series shall be able to be remote controlled through
<br />use of Remote Account Manager software. Features
<br />shall include: reset of audible signals, activation/
<br />deactivation of 08129 relays, interrogation of battery, point
<br />and armed status, enabling or disabling reporting
<br />functions, and shunting of reporting points during
<br />servicing,
<br />
<br />@ 1998 Radionics, Inc.
<br />
<br />9000 Series Spec/flcation Sheet