Laserfiche WebLink
<br />Chapler 3 - Syslem DesIgn <br />. Page 3-18 <br />REV. 1 <br /> <br />Step No.5 Check 10 make certain mInimum volumes end <br />maximum volume allowed between first nozzle <br />and lasl nozzle are not exceeded (Tenk Chert). <br />Check each rule In "General PipIng Requirements" <br />10 make certain nDne have been exceedad. If any <br />requirement Is exceeded, changa 10 a different <br />pipe size and recalculale. See Figure 3-22. <br /> <br />Refer to Tank Chart <br /> <br />MinImum Pipe Volume for PCL-300 15 300 <br />mlllllllers protecllng a fryer, wok, or range <br />(Example sYBlem pIpe volume Is 1781 mlll/lIlers, <br />lharefore OK) <br />Maximum PIpe Volume for PCL.300 Is 1910 <br />milliliters (Example system pipe volume Is <br />1781 mlllflflars, Iherefore OK) <br />MaxImum Volume Allowed Between First <br />Nozzle and Last Nozzle for PCL-300 Is 1125 <br />mIllIliters (Example system, the amount of 318 <br />In. piping belween G and L, Is 25.5 feel. 25.5 <br />feet x 37.5 mls./ft. = 956.3 ml, therefore, OK) <br /> <br />Refer to General Piping RequIrements <br /> <br />1. Split ptplng and stratght pipIng are both <br />allowed on PCL-300 and PCL-460 <br />systems. (Example syslem OK) <br />2. PCL-600 systems must use split pipIng <br />only, with no nozzle located bBfore the <br />split, and wllh a maxImum of 14 flDW <br />poInts per side. 1/2 In. minImum piping <br />must be used up to the first spill. <br />(Example system N/A) <br /> <br />3. Maximum volume for 1/4 In. pIpe <br />between a nozzle and the precedIng tee <br />Is 410 mls. (Example system N/A) <br /> <br />4. MaxImum flow numbers for 1/4 In. pipe <br />Is 6. (Example system N/A) <br /> <br />5. Maximum number of elbows botwoBn e <br />nozzle and the preceding too Is 5. <br />(Example syslem has a maximum number <br />of 2, lherefore, OK) <br /> <br />6. MaxImum of 25 elbows are aI/owed In <br />the total pIpIng system. (Example Syslem <br />has 11 elbows, therefora, OK) <br /> <br />7. MaxImum dIfference In elevation between <br />the tank outlet end any nozzle, or the tank <br />outlet and the highest or lowest horIzontal <br />pIpe run, Is 10ft. (3.1 m) (Example syslem <br />has 5'-6" (1.7 m). therefore, OK) <br /> <br />8. ND traps are allowed In the pIpIng <br />network. (Example sYBlem has nD lraps, <br />tharefore, OK) <br /> <br />9. PIpe lengths are measured from center to <br />center of fIttings. (Example syslem pipe <br />lengths were meesured from cenler 10 conter <br />of fittings, therefore. OK) <br /> <br />ULEX 3830 <br />April 1, 2004 <br /> <br />PN551274(2) <br /> <br />10. The Internal equivalent length volume Df <br />flllIng8 doen not have 10 be considered <br />as part of the total pIpe volume. <br />(Example system OK) <br /> <br />11. When utilizIng different sIze pipe In Ihe <br />total system, the largest sIze must start <br />first and the addItional pIpe must <br />decrease liS It approaches the nozzle. <br />(Example syslem N/A) <br /> <br />12. Elbow(s) or swIvel adaptors located at <br />the nozzles do not have to be counted In <br />the 25 elbow mBxlmum requirement. <br />(Exemple syslem OK) <br /> <br />13. AddltlonBI pipIng requirements when <br />protecting B range, wok, or a fryer: <br />. PCL-300 - MInimum of 300 ml and four <br />(4) flow numbers required In total <br />system. Of that mInimum, 239 ml and <br />two (2) flow numbers must be ullllzed <br />at or before the range, wok, or fryer. <br />(Example syslem has 1781 ml and 10 <br />flDW numbers, Iherefore, OK. The exam- <br />ple sYBlem has 1050 ml and 3 flows <br />Including Ihe fryer. Iherefore, OK) <br /> <br />PCL-460 - MInimum of 660 ml and len <br />(10) fiDW numbers required In lolel <br />system. Of that mInImum, 180 ml and <br />two (2) flow numbers must be utilIzed at <br />or belore (he range, wok, or fryer. <br /> <br />peL-600 - MinImum of 960 ml and four- <br />teen (14) flow numbers required In lolal <br />sYBtem. Of Ihat mInimum, 120 ml and 2 <br />flow numbers must be ullllzed al or <br />before the range, wok, or fryer. <br /> <br /> <br />TANK CHART . <br />MAX. VoL. <br />BETWEEN <br />FIRST AND <br />LAST NOZZLE <br />GEN. PIPING <br />RULE NO. 12 <br /> <br />GEN. PIPING <br />RULE NO. lJ <br /> <br />005r.]pc <br /> <br />FIgure 3-22. <br />