ELECTRICAL LEGEND
<br />SYMBOL
<br />DESCRIPTION . ,
<br />REMARKS/MOUNTING
<br />LAMP(S)
<br />FLUORESCENT LIGHTING FIXTURE, CEILING TYPE (1) '
<br />REFER TO FIXTURE SCHEDULE
<br />1 1
<br />A
<br />1
<br />FLUORESCENT STRIP LIGHTING FIXTURE (1) .
<br />REFER TO FIXTURE SCHEDULE
<br />-4
<br />[_
<br />METAL HALIDE LIGHTING FIXTURE, WALL TYPE (1)
<br />REFER TO FIXTURE SCHEDULE
<br />t
<br />SWITCH: SINGLE-POLE, 20A, 120/277VAC,
<br />MND CH1TE MURAL ECEVATf ONS
<br />TOP 48" AFF OR AS NOTED
<br />120
<br />DUPLEX RECEPTACLE: 20A, 125VAC,
<br />TOP 20" AFF OR AS NOTED
<br />1 i
<br />0 1
<br />DUPLEX RECEPTACLES: 20A, 125VAC, ,
<br />TOP 418" AFF OR AS NOTED
<br />ISGMI
<br />ELECTRIC PANEL
<br />NEW REFER TO SCHEDULES
<br />Di
<br />DISCONNECT SWITCH AS NOTED OR AS REQUIRED
<br />AS NOTED OR AS REQUIRED
<br />601
<br />MOTOR: VOLTAGE, HP, PHASE AS NOTED
<br />AS NOTED
<br />El 0
<br />OUTLET OR JUNCTION BOX
<br />AS NOTED OR AS REQUIRED
<br />.....----...N.
<br />FLEXIBLE CONNECTION
<br />AS NOTED OR AS REQUIRED
<br />fa
<br />DEVICE AS NOTED
<br />AS NOTED
<br />NOT E: ALL FIXTURES AS SPECIFIED ABOVE, OR EQUAL AS APPROVED BY OWNER/ARCHITECT.
<br />F'ROVIDE ALTERNATE BID FOR MAGNETIC BALLASTS, IN LIEU OF ELECTRONIC.
<br />CONDUIT RUN CONCEALED IN CEILING SPACE OR WALL
<br />WIRES INDICATED AS FOLLOWS:
<br />44-1 THREE WIRES;
<br />CONDUIT RUN CONCEALED IN FLOOR OR UNDERGROUND
<br />4 FOUR WIRES, ETC.
<br />HOME RUN TO PANEL/CIRCUIT(S) INDICATED
<br />- NEUTRAL WIRE
<br />â ISOLATED GR. MIRE
<br />PROVIDE MINIMUM SIZE 12 AWG CU
<br />IN 1/2" CONDUIT UNLESS OTHER-
<br />WISE NOTED. IN ADDITION, PROVIDE
<br />EQUIPMENT GROUND WIRE (NOT
<br />INDICATED) IN ALL POWER AND
<br />LIGHTING RACEWAYS
<br />-s--
<br />C2)
<br />REFER TO LIKE-NUMBERED NOTE '
<br />ABBREVIATIONS:
<br />(REFER TO MECHANICAL & PLUMBING DRAWINGS FOR EQUIPMENT DESIGN'
<br />IONS)
<br />FLOOR
<br />INTERRUPTER
<br />HGG)
<br />GR: GROUNDING
<br />WP: WEATHER-PROOF
<br />ID: ISOLATED
<br />CONDUCTOR AFF: ABOVE FINISHED
<br />GFI: GROUND FAULT CIRCUIT
<br />GROUND (LEVITON #6898-
<br />LEGEND GENERAL NOTES:
<br />SCHEDULE.
<br />(1) LETTER INSIDE OR ADJACENT TO FIXTURE SYMBOL INDICATES TYPE. REFER TO FIXTURE
<br />LIGHTING FIXTURE SCHEDULE
<br />'TYPE
<br />MANUFACTURER
<br />CATALOG NUMBER
<br />LAMP(S)
<br />VOLTS
<br />MOUNTING
<br />REMARKS
<br />A
<br />WILLIAMS
<br />50G-S12-2320O-RWKA1
<br />E2320C- GLR- LP
<br />'
<br />5 2-F032/835;
<br />3500K, T8,
<br />SYLVAN IA
<br />OCTRON
<br />120
<br />LAY-IN,
<br />GRID
<br />1' X 4' FLUORESCENT WITH
<br />1/8", PATTERN #12 ACRYLIC
<br />LENS.
<br />WILLIAMS
<br />17-4-2320C- E2320C
<br />- GLR- LP
<br />2-F032/835;
<br />350C/K, T8,
<br />SYLVAN IA
<br />OCTRON
<br />120
<br />SURFACE,
<br />ON CEILING
<br />4' FLUORESCENT WRAPAROUND
<br />WITH ACRYLIC LENS
<br />1 i
<br />0 1
<br />INFINITY
<br />PH60-218Q-F-MOD-EB
<br />2-CF18DD/
<br />E/ 835;
<br />3500⢠Kâ
<br />SYLVANIA
<br />DULUX
<br />120
<br />RECESSED
<br />COMPACT FLUORESCENT DOWN -
<br />LIGHT WITH CLEAR REFLECTOR
<br />AND ELECTRONIC BALLAST
<br />0
<br />WILLIAMS
<br />76-4-2320C- E2320C-
<br />GLR-LP
<br />2-F032/835;
<br />3500*K, TB,
<br />SYLVAN IA
<br />OCTRON
<br />120
<br />SURFACE
<br />4' FLUORESCENT STRIP,
<br />E
<br />WILLIAMS
<br />. 76-3-2250C- E2250C
<br />GLR- LP
<br />2-F025/835;
<br />3500K, T8,
<br />SYLVAN IA
<br />120
<br />SURFACE
<br />3 ' FLUORESCENT STRIP.
<br />NOT E: ALL FIXTURES AS SPECIFIED ABOVE, OR EQUAL AS APPROVED BY OWNER/ARCHITECT.
<br />F'ROVIDE ALTERNATE BID FOR MAGNETIC BALLASTS, IN LIEU OF ELECTRONIC.
<br />0
<br />f.A1
<br />PACE
<br />TYPE MANUFACTURER CATALOG NUMBER LAMP(S)
<br />A
<br />Al
<br />DAYBRITE
<br />WILLIAMS
<br />DAYBRITE
<br />WILLIAMS
<br />DAYBRITE
<br />WILLIAMS
<br />LIGHTING FIXTURE
<br />DALTOR CA10-2-26PLV-V
<br />MOD/ES
<br />200232-RA21-120- 2-F032/835;
<br />1/3-EB-GLR 3500*K, T8,
<br />SYLVANIA
<br />50G-S24-2320C OCTRON
<br />RWKAl25-E2320C- GLR-
<br />LP
<br />2DG232-RA21-120-
<br />1/3-EB-GLR-B50Srp
<br />(acmiNE)
<br />500-S24-2320C
<br />RWKAl25-E2320C-GLR-
<br />LP- EM/B5OST (BODINE)
<br />T-232-120-1/2-E0- 2-F032/835;
<br />GLR 3500"K, TB,
<br />SYLVAN IA
<br />7672- E2320C- GLR-LP OCTRON
<br />16'
<br />() EXISTING WIRING/DEVICES IN RESPECTIVE AREA SHALL REMAIN.
<br />0 CONNECT TO NEW 1P-20 AMP CIRCUIT BREAKER IN EXISTING PANEL INDICATED.
<br />POWER & MISC. PLAN
<br />SCALE: 1 /8" = 1 â0"
<br />POWER & MISC. PLAN NOTES:
<br />-
<br />2-F032/835;
<br />3500K, 18,
<br />SYLVANIA
<br />OCTRON
<br />2- CF26DD
<br />E/835
<br />SYLVANIA
<br />OCTRON
<br />SCHE:DULE
<br />VOLTS MOUNTING
<br />120 I A'-IN
<br />GRI)
<br />120 LAY-IN
<br />GRI
<br />120 SURFACE
<br />120 SURFACE
<br />GRID
<br />0 EXISTING PANEL : 225 AMP MAIN CIRCUIT BREAKER: 120/208 VOLT, 30, 4 WIRE, SHALL REMAIN.
<br />CONTRACTOR SHALL TRACE OUT ALL CIRCUITS IN THE PANEL. PROVIDE TYPE WRITTEN DIRECTORY LISTING EAC H
<br />BRANCH CIRCUIT, IDENTIFYING EQUIPMENT IT CONTROLS AND INDENTIFY CIRCUIT BREAKERS WHERE LOADS ARE BEING
<br />REMOVED AS SPARES WITH PENCIL. PROVIDE CIRCUIT NUMBER LABEL AT EACH CIRCUIT BREAKER WITH CONSLC: UTNE
<br />ODD NUMBERS ON THE LEFT (1-41) AND CONSECUTIVE EVEN NUMBERS ON THE RIGHT (2-42)
<br />REMARKS
<br />2' X 4' FLUORESCENT WITH 1/8"
<br />PATTERN 112 ACRYLIC LENS,
<br />SAME AS TYPE "A" EXCEPT
<br />WITH SELF TESTING EMERGENCY
<br />BALLAST FOR ONE LAMP (1,100
<br />LUMENS)
<br />4' FLUORESCENT STRIP,
<br />BRONZE PAINTED ALUMINUM
<br />QUARTER CYLINDER WITH
<br />TEMPERED GLASS LENS
<br />PACE
<br />LIGHTING. PLAN
<br />SCALE: 1 /8" = 1 I-0"
<br />C.3) CONNECT 10 NEW 1P-20 AMP CIRCUIT BREAKER IN EXISTING PANEL INDICATED
<br />EXISTING LIGHTING FIXTURES(S) IN RESPECTIVE AREA SHALL BE REMOVED.
<br />1 6'
<br />LIGHTING PLAN NOTES:
<br />0 CONNECT TO EXISTING CIRCUIT/SWITCH CONTROL
<br />0 CONNECT VIA NEW TIME SWITCH WHICH SHALL BE PROVIDED IN THE ELECTRIC ROOM
<br />K CONNECT EMERGENCY LIGHTING BALLAST SUCH THAT WHEN THE WALL SWITCH IS IN THE "OFF" POSITION,
<br />THE EMERGENCY LAMP WILL BE ENERGIZED DURING A POWER OUTAGE ONLY, PROVIDE ADDITIONAL WIRING
<br />AS REQUIRED.
<br />Notes:
<br />Revisions:
<br />767sultants:
<br />LEAL. ENGNEEP440 & APCHTECTURAL LXfTM tic.
<br />8313 W. HILLSBOROUGH AYE.,SUITE 16O TAMPA, FLORIDA 33515
<br />TEL(813)884-5723 FAX(813)884--2654
<br />MG (98006)
<br />ateatamingeetar.malleantew
<br />Architectsilnterior Designers
<br />0 \
<br />Ak Igg'2411 0 11*1 Rk tott,
<br />\I a t i f
<br />°S°.°41 i A O
<br />4t*ti,4
<br />The Edgewater Building
<br />600 South vlagnolia Avenue
<br />Suite 150
<br />Tampa, Florida 33606
<br />Phone (813) 251-0565
<br />Fax (813) 251-0567
<br />E-1
<br />ELEMENTS
<br />Drawing No./Date
<br />First Union National Bank
<br />of Florida
<br />FUNI5e012431/eE3006
<br />Drawing Title/Scale/Drawn by
<br />ELECTRICAL
<br />SCALE: i/a"
<br />ZEPHYRNILLS MA IN BRANC.:;--4
<br />30421 )TH AVENUE
<br />ZEP1-4YRNILLS, PLORIIDA
<br />-12
<br />Mc
<br />PLOT DATE: 6-1 2-98
<br />
|