Laserfiche WebLink
Zephyrhills Fire Rescue <br /> 6907 Dairy Road, Zephyrhills, FL 33542 <br /> Fire Marshal Bus (813) 780 -0041 <br /> Kerry Barnett Fax (813) 780 -0044 <br /> E -mail: kbarnett !i'c fire.rephyrhills.fl.us <br /> Plan Review #: 09 -112 <br /> Project: Interior Build -Out <br /> Number of Pages: 15 <br /> December 21, 2009 <br /> I have received and reviewed the plans for the interior build -out for Pet Smart located at <br /> 7814 Gall Blvd and will allow the project to move forward. Please note that this review <br /> does not eliminate any further requirements as the project continues moving forward. By <br /> receiving permit, contractor acknowledges to comply with the items listed below. Should <br /> anyone have any questions, please do not hesitate to contact the Fire Marshal's office. <br /> 1. The modification of the fire alarm and fire sprinkler systems requires a <br /> permit. Plans, spec /cut sheets on devices, calcs and copy of contractor's <br /> license required to obtain permit. <br /> 2. Remove exit sign in storage. There cannot be a designated exit through <br /> storage nor can it count toward the total egress capacity. <br /> 3. Welded doors shall be placarded "Welded shut — No longer an access to the <br /> Building" <br /> 4. Extinguishers shall be within 75' of travel distance. Placement will be <br /> determined by Fire Marshal when close to final and most of interior is set up. <br /> A minimum of 3 will be required. <br /> 5. Any penetrations in rated walls shall be sealed in accordance to a UL listing. <br /> 6. Label ceiling tile where duct detector indicating light is located above. <br /> 7. There can be no storage within 3' of electric panel. Contractor may want to <br /> mark floor to help prevent this. <br />