1 <br /> SECTION IV — SYSTEM DESIGN <br /> • UL EX. 3470 ULC CEx747 Page 4 -5 <br /> 10 -1 -02 REV.3 <br /> 0 Plenum Protection <br /> The R -102 system uses the 1W Nozzle (Part No. 419336) or the <br /> • 1100 Nozzle (Part No. 430192) or the 1N Nozzle (Part No. 419335) , <br /> for plenum protection. The 1W nozzle tip is stamped with 1W and 20 IN. (51 cm) <br /> 0 . <br /> • the 1N nozzle tip is stamped with 1 N, indicating they are one -flow MAXIMUM <br /> nozzles and must be counted as one flow number each. When pro- <br /> tecting a plenum chamber, the entire chamber rnust be protected <br /> ► regardless of filter length. 1 IN. (2.5 cm) <br /> MINIMUM <br /> I. • VERTICAL PROTECTION — GENERAL <br /> u <br /> ► One 1W nozzle or 1100 nozzle will protect 4 linear feet (1.2 m) of 1 t <br /> 0 . plenum. The maximum distance from the end of the hood to the 20 IN. (51 cm) <br /> first and last nozzle must be no more than 2 ft. (.6 m). After the first MAXIMUM <br /> nozzle, any additional nozzles must be positioned at a maximum <br /> of 4 ft. (1.2 m) apart down the entire length of the plenum. The t <br /> ► plenum width must not exceed 4 ft. (1.2 m). (The 1W or 1100 noz 1 IN. (2.5 cm) <br /> • zle can be used on single or V -bank filter arrangements.) See MINIMUM <br /> ► Figure 6. 1 <br /> 2 FT. (.6 m) <br /> II <br /> MAXIMUM -► ■ FIGURE 7 <br /> 4FT.(1.2m) 000199 <br /> MAXIMUM <br /> '' 4 FT. (1.2 m) ��a FT. (1.2 m) • Option 2: The 1 W or 1100 nozzle must be placed perpendicular, <br /> 2 FT. (.6 m) MAXIMUM MAXIMUM 8 -12 in. (20 -30 cm) from the face of the filter and angled <br /> MAXIMUM to the center of the filter. The nozzle tip must be within <br /> ► 2 in. (5 cm) from the perpendicular center line of the fil- <br /> ' : � <br /> � ter. See Figure 8. <br /> -4/4 • 12 IN. (30 cm) <br /> 0 1 . 1 MAXIMUM <br /> ��(/ ? i 41N. Alliko\. <br /> \ w B IN. (20cm) <br /> l s. <br /> �, /- I� i� MINIMUM <br /> � ^ 4 �ii ••: <br /> G MUST NOZZLE BE WITHIN TIP ���� <br /> FIGURE 6 THIS AREA <br /> 000197 d <br /> ► When protecting plenums with the 1W or 1100 nozzle, two options <br /> of coverage are available: 116 0 ► Option 1: The 1100 or 1W nozzle must be on the center line of the FIGURE 8 <br /> 000200 <br /> single or "V" bank filter and positioned within 1 -20 in. <br /> (2.5 -51 cm) above the top edge of the filter. See ► HORIZONTAL PROTECTION — OPTION 1 <br /> ► Figure 7. 1N NOZZLE — PART NO. 419335 — SINGLE BANK PROTECTION <br /> 0 .... One 1N nozzle will protect 10 linear feet (3.1 m) of single filter bank <br /> • plenum. The nozzle(s) must be mounted in the plenum, 2 to 4 in. <br /> (5 to 10 cm) from the face of the filter, centered between the filter <br /> I height dimension, and aimed down the length. See Figure 9. <br /> / <br /> I <br /> 2 - 4 IN. 10 FT. (3.1 m) <br /> a (5 - 10 cm) MAXIMUM <br /> a - <br /> • 000201 1011 <br /> I <br /> 1I <br /> . 000202 <br /> 1 ► FIGURE 9 <br />