Zephyrhills Fire Rescue <br /> 6907 Dairy Road, Zephyrhills, FL 33542 <br /> Fire Marshal Bus (813) 780 -0041 <br /> Kerry Barnett Fax (813) 780 -0044 <br /> E -mail: kbarnett@fire.zephyrhills.fl.us <br /> Plan Review #: 09 -0042 <br /> Project: Interior remodel for Mercantile Occupancy <br /> Number of Pages: Single Page <br /> June 2, 2009 <br /> I have received and reviewed the single page plan for an interior remodel located at 5953 <br /> Gall Blvd. This project will be allowed to move forward with comments made below. <br /> Paying for permit, contractor acknowledges complying with the following items below. <br /> Be advised no revision fees were charged. <br /> Should anyone have any questions, please do not hesitate to contact the Fire Marshal's <br /> office. <br /> 1. Certified fire extinguishers shall be installed in accordance with NFPA 10. <br /> Extinguishers shall be located in front and rear of unit. <br /> 2. Employees are required to have training on the use of fire extinguishers. <br /> Zephyrhills Fire Rescue may be contacted for the training. <br /> 3. Firewalls shall be maintained on each side of the unit. Any penetrations to the <br /> walI(s) shall be properly sealed. <br /> 4. Unit shall be addressed both in front and rear. <br /> 5. The secondary egress consists of two doors. One of the doors shall have either <br /> a hotel latch or panic hardware. <br /> 6. Install emergency light in restroom, if not one present. <br /> Inspections Required: <br /> 1. Final <br /> KE ' ',' : ARNETT, FIRE MARSHAL <br /> ** *Please be advised this review of plans submitted is a cursory review to assist the contractor in <br /> compliance with applicable fire safety codes. This review is not intended to be a final approval of the <br /> submitted plans. It is the contractor's sole responsibility to ensure that the plans are in complete compliance <br /> with all applicable NFPA codes and local ordinances. In the event that further examination or site <br /> inspection reveals areas of non - compliance, it shall be the contractor's sole responsibility, at their sole <br /> expense to bring those areas in compliance. The City assumes no responsibility for the contractor's failure <br /> to be in compliance with all applicable NFPA codes and local ordinances. <br />