Laserfiche WebLink
1. Panel side ribs shall be fastened along side of the panel inside rib, one <br /> fastener at the overlap. Field panel ribs shall be fastened with one fastener <br /> per rib the side of the panel. <br /> 2. All fasteners at center ribs and overlap rib shall be spaced at a maximum <br /> distance as noted in Table A below parallel to the roof slope. See detail <br /> herein. <br /> 3. Pane overlap shall be fastened at the high point with' /4 -7/8" long Hex <br /> Head corrosion resistant fasteners with sealing washer spaced at a <br /> maximum distance as noted in Table A below parallel to the roof slope. <br /> See detail herein. <br /> TABLE A <br /> Maximum Design Pressure <br /> Field Perimeter and Corner' <br /> Maximum Design Pressure -61.8 psf -1143 psf <br /> Maximum Fastener Spacing 30" o.c. 24" o.c. <br /> 1. Extrapolation shall not be allowed <br /> • <br /> i NOA No.: 07- 0713.03 <br /> Expiration Date: 09/05/12 <br /> Approval Date: 09/06/07 <br /> fir!. <br /> Page4of6 <br /> \ <br />