Zephyrhills Fire Rescue <br /> 6907 Dairy Road, Zephyrhills, FL 33542 <br /> Fire Marshal Bus (813) 780 -0041 <br /> Kerry Barnett Fax (813) 780 -0044 <br /> E -mail: kbarnett@fire.zephyrhills.fl.us <br /> Plan Review #: 09 -060 <br /> Project: Fire Alarm — All -Tech Air <br /> Number of Pages: 1 plus packet and calcs <br /> July 22, 2009 <br /> I have received and reviewed the plans for the fire alarm system located at 38147 16 <br /> Ave and will allow this to move forward. Obtaining permit, the applicant acknowledges <br /> complying with the items listed below. <br /> Should anyone have any questions, please do not hesitate to contact the Fire Marshal's <br /> office. <br /> 1. Installation shall be completed within the scope of NFPA 72, latest edition. <br /> 2. Mark both telephone jacks <br /> 3. Label breaker and lock off (breaker that controls fire alarm panel) <br /> 4. Zone map shall be located at panel <br /> 5. Documentation shall be provided at acceptance test to show monitoring <br /> company is a listed central station. <br /> 6. Date battery in panel <br /> Inspections Required: <br /> 1. Acceptance test completed <br /> KE ' ' , FIRE MARSHAL <br /> ** *Please be advised this review of plans submitted is a cursory review to assist the contractor in <br /> compliance with applicable fire safety codes. This review is not intended to be a final approval of the <br /> submitted plans. It is the contractor's sole responsibility to ensure that the plans are in complete compliance <br /> with all applicable NFPA codes and local ordinances. In the event that further examination or site <br /> inspection reveals areas of non - compliance, it shall be the contractor's sole responsibility, at their sole <br /> expense to bring those areas in compliance. The City assumes no responsibility for the contractor's failure <br /> to be in compliance with all applicable NFPA codes and local ordinances. <br />