Chapter 4 — System Installation <br /> Page 4 -7 <br /> REV. 2 <br /> The fusible link line can now be put into a set position by LATCHING ARM <br /> applying tension to the fusible link line. This is accomplished PULL PIN <br /> • by using a 1/2 in. hex wrench on the fusible link line ratchet <br /> wheel. The ratchet wheel will be ratcheted in a clockwise <br /> direction until the spring plate makes contact with the top of .:Iiimr;»'. <br /> the control head box. The fusible link line is now in a set <br /> position. See Figure 4 -8. Check to ensure that the fusible <br /> link hanger(s) remain centered in the bracket after the <br /> fusible link line is set. See Figure 4 -12. SLIDE <br /> CAM ARM <br /> F USISL LINK KI 1 <br /> (SOLDSEPAHAI EC G) Figure 4 -13. Control Head In Set Position. <br /> 2. Model ECH3 Electrical Control Head. <br /> Male Once the thermal detectors have been installed, the control <br /> ' ':1 head can be placed in the set position. To set the control <br /> FU_IB , INK head, the slide plate is moved from right to left, ensuring <br /> Lµ tl- /-I S oLDS EPARAILL, the bolt extending from the cam arm is in the slot provided <br /> FUSIBLE LINK - - , I in the slide plate. Continue moving the slide plate to the left <br /> HANGER <br /> until the latching arm is in the locked position. Insert the pull <br /> Figure 4 -12. Fusible Link /Hanger In Set Position. pin into the hole in the slide plate above the latching arm. <br /> 002850PC This will lock the control head in the set position, eliminating <br /> accidental actuation during the rest of the installation <br /> THERMAL DETECTOR procedure. <br /> INSTALLATION Once the Model ECH3 Electrical Control Head is in the set <br /> position, it can be connected to the detection /actuation <br /> Thermal detectors are always used in conjunction with the circuit. <br /> Model ECH3 Electrical Control Head. After mounting the <br /> cylinder and control head, the thermal detector(s) can be NOTE <br /> installed. See Chapter III for detector placement guidelines. No electrical connections shall be made inside the <br /> Follow the instructions included with the detector for proper control head. All electrical wiring shall exit the control <br /> detector mounting procedures. head through the knock -out on the side of the box. All <br /> electrical connections must be made in an approved <br /> SETTING THE CONTROL HEAD electrical box. <br /> ► Model MCH3 /NMCH3 Mechanical Connect one of the black wires on the solenoid in the con - <br /> Control Head. ► trol head to the red wire of the Model MS -SPDT Micro <br /> • Switch. The brown wire from the micro switch is then con - <br /> Once the fusible link line is set, the control head can be nected to one side of the first thermal detector in series. <br /> placed in the set position. To set the control head, the slide Connect the other side of the first thermal detector in series <br /> plate is moved from right to left, ensuring the bolt extending and the remaining black wire on the solenoid in the control <br /> from the cam arm is in the slot provided in the slide plate. head to the appropriate power source after installing the <br /> Continue moving the slide plate to the left until the latching Model SM- 24/120 Solenoid Monitor. <br /> arm is in the locked position. Insert the pull pin into the hole <br /> in the slide plate above the latching arm. This will lock the CAUTION <br /> control head in the set position, eliminating accidental actu- The solenoid must never be wired "hot" (not through <br /> ation during the rest of the installation procedure. See the micro - switch). If wired this way, the non -field <br /> Figure 4 -13. replaceable solenoid will be damaged and the com- <br /> plete control head will require replacement. <br /> ULEX 3437 CEx732 <br /> March 17, 2004 <br />