Laserfiche WebLink
• <br /> Chapter 3 — System Design <br /> Page 3 -15 <br /> REV. 2 <br /> General Piping Requirements <br /> 1. Split piping and straight piping are both allowed <br /> on a PCL -300 and PCL -460 system. , <br /> MS EPER <br /> 2. PCL -600 systems must use split piping only, with SIDE OF TEE BULL <br /> no nozzle located before the split, and with a " <br /> " SPLIT PIPING <br /> (REQUIRED <br /> maximum of 14 flow points per side. 1/2 in. mini- ONPCL 00 SYSTE <br /> mum piping must be used up to the first split. <br /> 3. Maximum volume for 1/4 in. pipe between a <br /> nozzle and the preceding tee is 410 mis. <br /> 4. Maximum flow numbers for 1/4 in. pipe is 6. <br /> 5. Maximum number of elbows between a nozzle " <br /> and the preceding tee is 5. STRAIGHT PIPING <br /> 6. Maximum of 25 elbows are allowed in the total <br /> piping system. <br /> 7. Maximum difference in elevation between the tank 006191Po <br /> outlet and any nozzle, or the tank outlet and the <br /> highest or lowest horizontal pipe run, is 10 ft. <br /> (3.1 m). Figure 3 -18. <br /> 8. No traps are allowed in the piping network. <br /> Design Steps <br /> 9. Pipe lengths are measured from center to center <br /> of fittings. Step No. 1 Determine number of flow points required based <br /> on duct size, plenum size and type, and size of <br /> 10. The internal equivalent length volume of fittings all appliances. <br /> does not have to be considered as part of the total Step No. 2 Determine size and quantity of tanks required. <br /> pipe volume. q Y q <br /> Refer to the chart in "General Piping <br /> 11.When utilizing different size pipe in the system, the Requirements" to determine the maximum <br /> largest size must start first and the additional pipe amount of flow numbers allowed per each tank <br /> must decrease as it approaches the nozzle. size. <br /> 12. Elbow(s) or swivel adaptors located at the nozzles Step No. 3 Layout nozzles, piping diagram, and tank loca- <br /> do not have to be counted In the 25 elbow maxi- lion. Determine pipe lengths as accurate as <br /> mum requirement. possible. Make certain maximum number of <br /> elbows is not exceeded. Note: Tanks cannot <br /> 13. Reducing bushings are allowed when reducing to be manifotded together. Each tank must <br /> a smaller pipe size. have a separate piping network. <br /> Step No. 4 Add all the lengths of each pipe run and multi - <br /> 14. Additional piping requirements when protecting a <br /> range, wok, or a fryer: ply by the mis. /ft. listed in the Volume Chart. If <br /> the sum falls within the acceptable range noted <br /> • PCL -300 - Minimum of 300 ml and four (4) flow in general Piping Requirements, that pipe size <br /> numbers required in total system. Of that mini- <br /> mum, 239 ml and two (2) flow numbers must be is acceptable. If the calculated volume is too <br /> utilized at or before the range, wok, or fryer. large, recalculate the volume using the ml per <br /> foot of a smaller pipe size. Pipe sizes can be <br /> • PCL -460 — Minimum of 660 mi and ten (10) flow mixed but Rule No. 11 of the General Piping <br /> numbers required In total system. Of that mini- Requirements must be followed. <br /> mum, 180 ml and two (2) flow numbers must be Step No. 5 Check to make certain minimum volumes, maxi - <br /> utilized at or before the range, wok, or fryer. mum volumes and maximum volume allowed <br /> • PCL -600 — Minimum of 960 mi and fourteen (14) between first nozzle and last nozzle is not <br /> flow numbers required in total system. Of that exceeded (Tank Chart). Check each rule in <br /> minimum, 120 mi and 2 flow numbers must be "General Piping Requirement" to make certain <br /> utilized at or before the range, wok, or fryer. none have been exceeded. If any requirement <br /> is exceeded, change to a different pipe size and <br /> recalculate. <br /> ULEX 3830 <br /> PN551274(2) April 1, 2004 <br />