Laserfiche WebLink
0 NOTIFIER` System Power Requirements <br /> by Honeywell <br /> NFW2 -100 Fire Alarm Control Panel <br /> Protected Premises: Twelve Oaks Medical Center Date: 7/7/2009 <br /> Address: 6748 Gall Blvd. <br /> City: ZephyrtMls State: FI. Zip: 33542 <br /> Prepared By: The Hart line Alarm Co, Inc.- Chuck Caudill Phone: (863) 678 -0678 <br /> Address: 401 N. Scenic Hwy. Email: <br /> City: Lake Wales State: FI. Zip: 33859 <br /> AC Branch Current Requirements I 3.00 IAMPS @ 120 VAC <br /> Current required by source to power the fire alarm <br /> system. <br /> Primary Standby Load I 0.37 I Amps <br /> Current load on the primary power supply during <br /> non -alarm conditions. <br /> Primary Alarm Load I 4.46 I Amps <br /> Current load on the primary power supply during <br /> alarm conditions. <br /> Secondary Load Requirements I 8.61 I Amp Hours <br /> Total Secondary Load from the calculation table below. <br /> Current Dray: Time (hours) Total (AH) <br /> Seconday Standby Load Required Standby Time <br /> 0.283 A 24 hours 1 6.80 <br /> Secondary Alarm Load Required Alarm Time (hours) <br /> 4.463 A 0.084 hours 1 0.37 <br /> Auxiliary Power Supply Load Required Alarm Time (hours) <br /> 0.000 A 0.084 hours 0.00 <br /> Total Secondary Load 7.18 <br /> Derating factor x 1.2 <br /> Secondary Load Requirements 8.61 AH <br /> Battery Selection I 12 I Amp Hours <br /> Select batteries from the list below. <br /> 112 AH BAT -12120 Battery (12 volt) 1 SUBMITTED PLAN(S) HAVE BEEN REVIEWED <br /> • Two Fotr(Mo 121/DC sets inparallel) BY ZEPHYRHILL• FI :1 ' SHAL'S OFFICE <br /> Date: 7 /f <br /> Reviewer: �;!!v <br /> Page 1 of 2 <br />